Wireless Outdoor Sensor 087Installation & Operation Manual087_D05/16AccessoriesReplaces: New© 2016   087_D - 05/161 of 8A Watts Water Technologies CompanyThe tekmar Wireless Outdoor Sensor 087 provides a simple solution to include outdoor temperature measurement in any application without exterior wiring. The transmitter and receiver are sold pre-linked and are installation-ready. With exceptional range and an 8 year battery life, the Wireless Outdoor Sensor 087 provides maximum accuracy, convenience and reliability.FeaturesWireless Outdoor Sensor 087ReceiverCommunicationPowerLow BatteryLink• Compatible with all tekmar controls and thermostats as well as other manufacturers products• 10K (type 2 and 3), 5K, 12K and 20K resistance setting options• Low transmitter battery status indicator on the receiver• Power and communication indicator lights• Transmitter temperature range of -40°F to 140°F (-40°C to 60°C)• Long battery life (minimum 8 years) with included 1.5V Lithium AA batteries• 5000 ft. open range• 8 walls / 250 ft. indoor range
© 2016   087_D - 05/16 2 of 8To avoid serious personal injury and damage to the equipment:It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. tekmar is not responsible for damages resulting from improper installation and/or maintenance.• Read Manual and all product labels BEFORE using the equipment. Do not use unless you know the safe and proper operation of this equipment.•  Keep this Manual available for easy access by all users.•  Replacement Manuals are available at tekmarControls.com•  Disconnect all power before opening the control.• Do not attempt to service the control. There are no user serviceable parts inside the control. Attempting to do so voids warranty.FCC ID: 2AHQR-10850A  IC ID: 21247-10850AFCC: This product has been tested and found to comply with FCC part 15 subpart C. Operation is subject to the following two conditions: (1) this device may not cause Harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation of the device. However, there is no guarantee that interference will not occur in a particular installation. If this device does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on. The user is encouraged to try to correct the interference by one or more of the following measures:• Reorient or relocate the receiving antenna.• Increase the separation between the equipment and receiver.• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.• Consult the dealer or an experienced radio/TV technician for helpWarning: Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment. Industry Canada: This Device complies with Industry Canada License-exempt RSS standard(s). Operation is subject to the following two conditions: 1) this device may not cause interference, and 2) this device must accept any interference, including interference that may cause undesired operation of the device under Industry Canada regulations.Warning: FCC and IC Radiation Exposure StatementThe Transmitter device must provide a separation distance of at least 20 cm (8 chines) from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter.
© 2016   087_D - 05/163 of 8Check the contents of this package. If any of the contents listed are missing or damaged, please refer to the Limited Warranty and Product Return Procedure on the back of this brochure and contact your wholesaler or tekmar sales representative for assistance.• One Receiver Unit (for indoor installation) • One Transmitter Unit (for outdoor installation) • 2 1.5V AA Lithium batteries • Installation hardware • One Installation & Operation ManualWhen choosing the location for the receiver unit, consider the following:•  Interior Wall.•  Keep dry. Avoid potential leakage onto the unit.•  Relative Humidity less than 90%. Non-condensing environment.•  No exposure to extreme temperatures beyond 32 to 122°F (0 - 50°C)•  Away from equipment, appliances, or other sources of electrical interference.•  Easy access for wiring•  Approximately 5 feet (1.5 m) off the finished floor.•  DO NOT mount the transmitter or receiver in a metal enclosure, or on a surface with conductive properties. It will reduce the signal strength and affect the communication distance and reliability.Step 2 - Install receiverStep 1 - Check the ContentsGrasp the front cover by the fingertip grips on the top and bottom of the enclosure and pull the front cover off. Remove the wiring cover screw. The enclosure is either mounted flush onto a wall or it can be placed onto a 2" x 4" electrical box. The mounting holes in the enclosure accept #6 screws. Wiring to the control enters the wiring chamber through the back or bottom of the enclosure.
© 2016   087_D - 05/16 4 of 8Step 4 - Confirm LinkStep 3 - Provide power 24 V (ac) Power to the receiver unitConnect the 24 V (ac) power supply to the R and C terminals (1 and 2) on the receiver unit. Replace the cover.Use a separate power supply for the receiver when connecting to a 24 V (ac) powered control.1Power2CR24 V (ac)RCBatteries in the transmitter unitRemove the cover from the transmitter unit. Pull out the plastic tab that is keeping the batteries from making contact. Put the cover back on the base and secure with screws.Please note: 1.5V Lithium batteries are required to provide the specified battery life and temperature range. If the communication light is displayed on the control, the transmitter is linked properly.If the light is not on, the devices will need to be linked. Remove the cover on the transmitter so that the button below the battery terminals can be accessed. Press and hold both the button on the transmitter and the button on the receiver simultaneously for 5 seconds. Linking is successful when the communication LED is on.Wireless Outdoor Sensor 087ReceiverCommunicationPowerLow BatteryLinkWireless Outdoor Sensor 087ReceiverCommunicationPowerLow BatteryLink
© 2016   087_D - 05/165 of 8LED OperationStep 5 - Install transmitter• The transmitter should be mounted on an exterior wall which best represents the heat load on the building (a northern wall for most buildings and a southern facing wall for buildings with large south facing glass areas)• In order to prevent heat transmitted through the wall from affecting the sensor reading, it may be necessary to install an insulating barrier behind the enclosure.• The 087 should not be exposed to heat sources such as ventilation or window openings.• The 087 should be installed at an elevation above the ground that will prevent accidental damage or tampering.• Do not install the transmitter on a conductive surface.Loss of Communication TroubleshootingIf the Communication LED is not on, please try the following:1.  Confirm that the receiver is powered with 24 V (ac) by observing that the green Power LED is on.2.  Confirm that batteries are still good. If the batteries are dead, the Communication and Low Battery LEDs will be off.3.  Try re-linking the devices, as described on page 4.4.  Reset the receiver by pressing the link button momentarily.  5.  If the communication LED remains off, please call Technical Customer Support at (250) 545-7749 or email tekmar.customerservice@wattswater.com.LED Indicator Status DescriptionPower On (Green) Normal operationOff No power. Check that the wires are securely  connected to the device.Communication On (Green) Signal is good.Off No signal. There is a loss of communication or the transmitter battery is dead, resulting in an open circuit error on the control.Flashing Signal is weak. Consider relocating a device to obtain a stronger signal.Low Battery On (Red) Battery life is low. Replace within 3 months.Off Battery is good.
© 2016   087_D - 05/16 6 of 8Resistance Temperature336095 -40°C242426 -35°C176801 -30°C130307 -25°C97007 -20°C72910 -15°C55303 -10°CResistance Temperature42316 -5°C32651  0°C25395  5°C19903  10°C15714  15°C12493  20°C10000  25°CResistance Temperature8056  30°C6530  35°C5325  40°C4367  45°C3601  50°C2985  55°C2487  60°C10K Type 2 (tekmar)ONResistance Temperature239686 -40°C179200 -35°C135185 -30°C102861 -25°C78913 -20°C61020 -15°C47543 -10°CResistance Temperature37313 -5°C29490  0°C23457  5°C18780  10°C15130  15°C12263  20°C10000  25°CResistance Temperature8194  30°C6752  35°C5592  40°C4655  45°C3893  50°C3271  55°C2760  60°C10K Type 3ONSensor Resistance SettingsSensor terminal wiringDIP switches in the right side of the wiring chamber are configured to match the sensor requirements of the connected control.'10K Type 2' is the default setting that works with all tekmar controls and thermostats with outdoor sensor inputs. To determine the correct setting for other control types, refer to the following temperature resistance charts.Connect 2-conductor wire between the control or device that requires an outdoor temperature reading and the sensor terminals (3 and 4) on the receiver. This connection is not polarity sensitive. Set the DIP switches to match the type of resistance reading required.ON12310850ARPower: 24 V (ac) ±10%, 50/60 Hz, X VASensor Voltage Limit: 5 V (dc) maximumWireless Outdoor Sensor 087ReceiverH3017ACommunicationPowerLow BatteryLink41PowerSensor2C3RDate CodeMeets Class B: CanadianICES-003, FCC Part 15  1   2   3 SensorOFF  OFF  OFF  10K TYPE 2 (tekmar)ON  OFF  OFF  10K TYPE 3OFF  ON  OFF  5KON  ON  OFF  12KOFF  OFF  ON  20KDesigned andassembled in Canada4Sensor3To outdoor sensor terminals on tekmar or other manufacturers control
© 2016   087_D - 05/167 of 8Wireless Outdoor Sensor 087 Literature 087_D, 087_CDimensions Transmitter: 130mm x 68mm x 50mmReceiver: 120mm x 74mm x 23mmApprovals FCC and ICOperating range Transmitter: -40 to 140°F (-40 to 60°C)Receiver: 32 to 122°F (0 to 50°C)Receiver power 24 V (ac) +/- 10%, 1 VATechnical DataResistance Temperature168243 -40°C121342 -35°C88487 -30°C65210 -25°C48540 -20°C36479 -15°C27666 -10°CResistance Temperature21166 -5°C16325  0°C12698  5°C9952  10°C7857  15°C6247  20°C5000  25°CResistance Temperature4028  30°C3265  35°C2663  40°C2184  45°C1801  50°C1493  55°C1244  60°C5KONResistance Temperature309396 -40°C229504 -35°C171839 -30°C129824 -25°C98932 -20°C76018 -15°C58878 -10°CResistance Temperature45953 -5°C36129  0°C28606  5°C22804  10°C18297  15°C14773  20°C12000  25°CResistance Temperature9803  30°C8053  35°C6651  40°C5522  45°C4607  50°C3862  55°C3252  60°C12KONResistance Temperature806800 -40°C574400 -35°C413400 -30°C300400 -25°C220600 -20°C163500 -15°C162280 -10°CResistance Temperature92240 -5°C70160  0°C53780  5°C41560  10°C32340  15°C25360  20°C20000  25°CResistance Temperature15892  30°C12704  35°C10216  40°C8264  45°C7220  50°C5498  55°C4520  60°C20KON
All specifications are subject to change without notice8 of 8 087_D - 05/16.Product design, software and literature are Copyright ©2016 by tekmar Control Systems Ltd., A Watts Water Technologies Company.  Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-984-0815 Web Site: tekmarControls.comWARNING: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm.  For more information: Watts.com/prop65Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.The tekmar  Limited Warranty to  the  Purchaser on  the Products  sold hereunder  is  a  manufacturer’s pass-through  warranty  which  the  Purchaser  is  authorized  to  pass through  to its  customers. Under  the  Limited Warranty,  each tekmar  Product is  warranted against  defects  in workmanship  and  materials  if  the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and / or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liability, for any  other losses,  costs, expenses,  inconveniences,  or damages,  whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract.The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the war-ranty  period.  This  Limited  Warranty  does  not  cover  the  cost  of  the  parts  or  labor  to  remove  or  transport  the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.Any representations or warranties about the Products made by Purchaser to its customers which are different from or  in excess of  the  tekmar  Limited  Warranty  are  the  Purchaser’s  sole  responsibility and  obligation. Pur-chaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers.The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifica-tions, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and / or the local codes and ordi-nances; or if due  to defective installation of the Product;  or if  the  Product was not  used in  compliance  with tekmar’s instructions.THIS  WARRANTY  IS  IN  LIEU  OF  ALL  OTHER  WARRANTIES,  EXPRESS  OR  IMPLIED,  WHICH  THE  GOV-ERNING  LAW  ALLOWS  PARTIES  TO  CONTRACTUALLY  EXCLUDE,  INCLUDING,  WITHOUT  LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABIL-ITY  OR  DESCRIPTION  OF  THE  PRODUCT,  ITS  NON-INFRINGEMENT  OF  ANY  RELEVANT  PATENTS  OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTU-ALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERN-ING LAW. Product Warranty Return Procedure All Products that are believed to have defects in workmanship or mate-rials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact information regarding the appropriate Representative.Limited Warranty and Product Return Procedure