Thermodynamic Process Control LFC001TPCMVPMV Thermodynamic Controller User Manual 02

Thermodynamic Process Control, LLC Thermodynamic Controller 02

Contents

User manual 02

TPC-FI SoloNet O&M Page 36
TPC-FI SoloNet O&M Page 37
Appendix A
TPC-FI SoloNet O&M Page 38
GUI
Parameters
TPC
Parameter
Ranges
TPC
Default
TPC Descriptions
System
Parameters
Design Inputs
Units Fahrenheit,
Celsius Fahrenheit Choose the convention in which you would like to display system
information.
Sum Reporting Zone
Loads Enable / Disable Disable
Choose "Enable" if you are using multiple flow meters attached to
"Zone Load Controllers" to report back loads in one or more zones.
Chose "Disable" if using single point flow measurement attached to
the "System Information Field Device"
Outdoor Design
Temperature -40 - 40 F 0
Choose the outdoor air temperature this system was designed to
overcome worst case. This will be the coldest temperatures you
would expect to see in this climate.
Indoor Design
Temperature 60 - 80 F 70 Choose the indoor temperature the building is designed to maintain
under full-load conditions.
Redundancy Factor 1.00 - 10.00 4
Choose the factor by which the design MBH input (sum of boiler
MBH inputs) is greater than the required MBH needed under
maximum load conditions.
System Circulation
Delay minutes 1 - 30 Min 10 Chose the delay time desired from the start of the system pumps
until the selection and start of the first boiler stage.
Initial Delay Minutes 10 - 240 Min 60
Choose the number of minutes you desire to delay an additional
boiler staging on when the outdoor air temperature has reached just
reached the "Winter Heat On Set-point". This delay is designed to
allow a single boiler stage to gradually warm the system during
light load times only. This delay is linked to the initial switching
from off to on of a call for heat and will not affect control action as
long as heat remains enabled.
Minimum Hysteresis 2 - 40 F 5
Chose the maximum number of degrees that you desire to allow the
system temperature to drop below set-point and sustain for the
"Stage Delay Time" before enabling another stage of heat.
Maximum Hysteresis 5 - 80 F 15
Chose the maximum number of degrees that you desire to allow the
system temperature to overshoot set-point before disabling all
boilers on the system.
TPC-FI SoloNet O&M Page 39
Minimum Stage
Delay Minutes 1 - 60 Min 30
Choose the number of minutes conditions ( load deficit ) must
persist before activating the next stage of heat. This delay will
work between every stage selection except in the case of a heating
emergency as defined in the O&M manual
System Delta T Set-
point 0-50 F 10
Enter the Delta T you wish to keep across the system. To use this
feature you must also designate a system pump for Delta T
operation.
Pipe Type Steel, Copper,
CPVC- Steel Enter the type of pipe in which the flow meter is inserted
Pipe Schedule 20, 40, 80 40 Enter the code of construction of the pipe in which the flow meter
is inserted.
Pipe Size 2 - 48 In 8 Enter the diameter of the pipe in which the flow meter is inserted.
Default Flow Rate
GPM
10 - 150,000
GPM 500 Enter the estimated maximum flow rate of this system.
Manual Override of
System Flow Input Enable / Disable Disable
Choose to manually override the flow meter by enabling this
function. If you enable this function then the control will choose to
read the maximum flow rate. You will only want to enable this
function when you are servicing the flow meter or if it otherwise
not operating.
Heat Priority
Winter Heat On Set-
point 30 - 150 F 60 Choose the outdoor air temperature at which you desire to enable
the heating plant.
NonCondensing
Outdoor Set-point -20 - 80 F 0 Choose the outdoor air temperature at which you desire to begin
utilizing the non-condensing control loop Reset 2.
Heat Reset 1 -
Condensing
Maximum System
Supply Set-point 60 - 210 F 120 Choose the maximum supply temperature allowed on this system
while the condensing reset loop is active.
Minimum System
Supply Set-point 40 - 200 F 80 choose the minimum supply temperature allowed while the
condensing reset loop is active.
Maximum Outdoor
Temperature Set-
point
30 - 150 F 60
Choose the maximum outdoor air temperature which the
condensing reset loop will use to calculate the Supply water
temperature set-point.
Minimum Outdoor
Temperature Set-
point
-40 - 40 F 0
Choose the minimum outdoor air temperature which the condensing
reset loop will use to calculate the Supply water temperature set-
point.
Reset Shift Degrees 0 - 40 F 0
After the system has been in operation you may further fine tune
this reset loop by shifting the slope up or down. This is a linear
function which means the entire reset slope will shift.
Heat Reset 2 -
NonCondensing
Maximum System
Supply Set point 60 - 210 F 180 Choose the maximum supply temperature allowed on this system
while the Non-condensing reset slope is active.
TPC-FI SoloNet O&M Page 40
Minimum System
Supply Set point 40 - 200 F 140 Choose the minimum supply temperature allowed while the Non-
condensing reset slope is active.
Maximum Outdoor
Temperature Set
point
30 - 150 F 60
Choose the maximum outdoor air temperature which the Non-
condensing reset loop will use to calculate the Supply water
temperature set-point.
Minimum Outdoor
Temperature Set
point
-40 - 40 F 0
Choose the minimum outdoor air temperature which the Non-
condensing reset loop will use to calculate the Supply water
temperature set-point.
Reset Shift Degrees 0 - 40 F 0
After the system has been in operation you may further fine tune
this reset loop by shifting the slope up or down. This is a linear
function which means the entire reset slope will shift.
Heat Reset 3 - Reheat
Maximum System
Supply Set point 60 - 210 F 120 Choose the maximum supply temperature allowed on this system
while the Reheat reset slope is active.
Minimum System
Supply Set point 40 - 200 F 100 Choose the minimum supply temperature allowed while the Reheat
reset slope is active.
Maximum Outdoor
Temperature Set
point
80 - 160 F 100
Choose the maximum outdoor air temperature which the Reheat
reset slope will use to calculate the Supply water temperature set-
point.
Minimum Outdoor
Temperature Set
point
40 - 100 F 70
Choose the minimum outdoor air temperature which the Reheat
reset slope will use to calculate the Supply water temperature set-
point.
Reset Shift Degrees 0 - 40 F 0
After the system has been in operation you may further fine tune
this reset slope by shifting the line up or down. This is a linear
function which means the entire reset slope will shift.
Optimum Stop / Start
Night Setback Value 0 - 40 F 10 Choose the number of degrees you wish to let the system fall to
under night setback conditions.
Boost Value 0 - 40 F 0
Choose the number of degrees you wish to allow the control to take
the system above the set point at morning warm up. A value
greater than zero may or may not be required for optimum start.
Boost Runtime
Minutes 0 - 120 Min 60 Choose the number of minutes you wish for boost above the active
reset to operate before returning to the calculated reset value.
Monday
Night Setback Enable / Disable Disable Choose to enable or disable this operation.
Begin Setback Hour /
Minute 0:00 - 23:59 1
Choose the time before the unoccupied period you wish to allow
the control to begin a "controlled descent" to the unoccupied
temperature.
Complete Setback
Hour / Minute 0:00 - 23:59 1 Enter the time you expect the building to be unoccupied for this day
of the week.
Day Return Enable / Disable Disable
Choose enable if you desire to bring the system back up to
temperature from the previous day. If you choose to designate this
day of the week as unoccupied simply disable day return.
TPC-FI SoloNet O&M Page 41
Begin Return Hour /
Minute 0:00 - 23:59 0
Choose the time before the building is occupied that you desire to
start a controlled ramp up to the calculated reset + Boost value
temperature.
Complete Return
Hour / Minute 0:00 - 23:59 0 Choose the time of day you expect the building to be occupied.
Tuesday
Night Setback Enable / Disable Disable Choose to enable or disable this operation.
Begin Setback Hour /
Minute 0:00 - 23:59 1
Choose the time before the unoccupied period you wish to allow
the control to begin a "controlled descent" to the unoccupied
temperature.
Complete Setback
Hour / Minute 0:00 - 23:59 1 Enter the time you expect the building to be unoccupied for this day
of the week.
Day Return Enable / Disable Disable
Choose enable if you desire to bring the system back up to
temperature from the previous day. If you choose to designate this
day of the week as unoccupied simply disable day return.
Begin Return Hour /
Minute 0:00 - 23:59 0
Choose the time before the building is occupied that you desire to
start a controlled ramp up to the calculated reset + Boost value
temperature.
Complete Return
Hour / Minute 0:00 - 23:59 0 Choose the time of day you expect the building to be occupied.
Wednesday
Night Setback Enable / Disable Disable Choose to enable or disable this operation.
Begin Setback Hour /
Minute 0:00 - 23:59 1
Choose the time before the unoccupied period you wish to allow
the control to begin a "controlled descent" to the unoccupied
temperature.
Complete Setback
Hour / Minute 0:00 - 23:59 1 Enter the time you expect the building to be unoccupied for this day
of the week.
Day Return Enable / Disable Disable
Choose enable if you desire to bring the system back up to
temperature from the previous day. If you choose to designate this
day of the week as unoccupied simply disable day return.
Begin Return Hour /
Minute 0:00 - 23:59 0
Choose the time before the building is occupied that you desire to
start a controlled ramp up to the calculated reset + Boost value
temperature.
Complete Return
Hour / Minute 0:00 - 23:59 0 Choose the time of day you expect the building to be occupied.
Thursday
Night Setback Enable / Disable Disable Choose to enable or disable this operation.
Begin Setback Hour /
Minute 0:00 - 23:59 1
Choose the time before the unoccupied period you wish to allow
the control to begin a "controlled descent" to the unoccupied
temperature.
Complete Setback
Hour / Minute 0:00 - 23:59 1 Enter the time you expect the building to be unoccupied for this day
of the week.
Day Return Enable / Disable Disable
Choose enable if you desire to bring the system back up to
temperature from the previous day. If you choose to designate this
day of the week as unoccupied simply disable day return.
Begin Return Hour /
Minute 0:00 - 23:59 0
Choose the time before the building is occupied that you desire to
start a controlled ramp up to the calculated reset + Boost value
temperature.
Complete Return 0:00 - 23:59 0 Choose the time of day you expect the building to be occupied.
TPC-FI SoloNet O&M Page 42
Hour / Minute
Friday
Night Setback Enable / Disable Disable Choose to enable or disable this operation.
Begin Setback Hour /
Minute 0:00 - 23:59 1
Choose the time before the unoccupied period you wish to allow
the control to begin a "controlled descent" to the unoccupied
temperature.
Complete Setback
Hour / Minute 0:00 - 23:59 1 Enter the time you expect the building to be unoccupied for this day
of the week.
Day Return Enable / Disable Disable
Choose enable if you desire to bring the system back up to
temperature from the previous day. If you choose to designate this
day of the week as unoccupied simply disable day return.
Begin Return Hour /
Minute 0:00 - 23:59 0
Choose the time before the building is occupied that you desire to
start a controlled ramp up to the calculated reset + Boost value
temperature.
Complete Return
Hour / Minute 0:00 - 23:59 0 Choose the time of day you expect the building to be occupied.
Saturday
Night Setback Enable / Disable Disable Choose to enable or disable this operation.
Begin Setback Hour /
Minute 0:00 - 23:59 0:00
Choose the time before the unoccupied period you wish to allow
the control to begin a "controlled descent" to the unoccupied
temperature.
Complete Setback
Hour / Minute 0:00 - 23:59 0:00 Enter the time you expect the building to be unoccupied for this day
of the week.
Day Return Enable / Disable Disable
Choose enable if you desire to bring the system back up to
temperature from the previous day. If you choose to designate this
day of the week as unoccupied simply disable day return.
Begin Return Hour /
Minute 0:00 - 23:59 1
Choose the time before the building is occupied that you desire to
start a controlled ramp up to the calculated reset + Boost value
temperature.
Complete Return
Hour / Minute 0:00 - 23:59 1 Choose the time of day you expect the building to be occupied.
Sunday
Night Setback Enable / Disable Disable Choose to enable or disable this operation.
Begin Setback Hour /
Minute 0:00 - 23:59 0:00
Choose the time before the unoccupied period you wish to allow
the control to begin a "controlled descent" to the unoccupied
temperature.
Complete Setback
Hour / Minute 0:00 - 23:59 0:00 Enter the time you expect the building to be unoccupied for this day
of the week.
Day Return Enable / Disable Disable
Choose enable if you desire to bring the system back up to
temperature from the previous day. If you choose to designate this
day of the week as unoccupied simply disable day return.
Begin Return Hour /
Minute 0:00 - 23:59 1
Choose the time before the building is occupied that you desire to
start a controlled ramp up to the calculated reset + Boost value
temperature.
Complete Return
Hour / Minute 0:00 - 23:59 1 Choose the time of day you expect the building to be occupied.
Winter Priority
TPC-FI SoloNet O&M Page 43
Winter Priority
Staging Enable / Disable Disable
Choose to enable Winter Priority if you have a large mass boiler
that you desire to put into the lead position for a portion of the
heating season.
Winter Priority Start
Date mm/dd 12/25 Choose the date you would like to begin Winter Priority
Winter Priority Stop
Date mm/dd 2/14 Choose the date you would like to stop Winter Priority.
Winter Boilers
Rotation Hours 24 - 720 Hours 168
If you have more than one large mass boiler that will be designated
as Winter Priority choose the number of hours you would like for
each boiler to be in the lead position.
Reheat
Reheat Enable / Disable Disable Choose to enable the reheat reset slope if you are using reheat in
this application.
Reheat On Set point 60 - 90 F 70 Choose the outdoor air temperature at which you desire the reheat
reset slope to be enabled.
Reheat Warm
Weather Shutdown 80 - 160 F 100 Choose the outdoor air temperature at which you desire the reheat
to be disabled due to warm weather.
System Pump
Parameters
Activation Enable / Disable Enable Choose Enable to activate this pump to be used in this system.
Dedicated Lead Enable / Disable Enable Choose Enable to always use this pump as the lead pump in this
system. Pump = on when heating operations are on
Lead-Lag / Lead-
Help
Lead-Lag / Lead-
Help Lead-Lag
Choose "Lead/Lag" if this pump will be rotated into the lead
position as an either or pumping scenario. For lead/lag switching +
help when using variable speed pumping chose "Lead/Help" in
order to meet flow requirements of the system based on Delta P or
Delta T system needs.
Lead Shutdown
Delay (for Lead-Lag) 10 - 120 Sec 30 Choose the number of seconds you would like to delay the
shutdown of the lead pump in this system.
Lag Help Enable
Output % (for Lead-
Help)
51-100% 100 Choose the percentage of sustained pump output required to enable
the lag pump.
Lag Help Disable
Output % (for Lead-
Help)
1-50% 40 Choose the percentage of sustained pump output required to disable
the lag pump.
Lag Help Delay (for
Lead-Help) 1 - 60 Min 30
Choose the number of minutes the conditions (Output %) for lag
help Enable/Disable must be sustained before action is taken to
Enable or Disable the lag pump
Rotation Hours (for
Lead-Lag or Lead-
Help)
12 - 720 Hrs 168 Choose the number of hours you desire this pump to stay in the lead
position.
TPC-FI SoloNet O&M Page 44
Heat Enable
Shutdown Delay
Time
1 - 120 Min 60
Choose the number of minutes you would like the pumps to
continue to operate after the system has been shut down on outdoor
air temperature.
System Pump
Maximum
Modulation
Percentage
50 - 100 % 100 Choose the maximum modulation signal expressed as a percentage
you desire to be sent to this pump.
System Pump
Minimum
Modulation
Percentage
0 - 50 % 35 Choose the minimum modulation signal expressed as a percentage
you desire to be sent to this pump.
System Pump Process
Acceleration 0 - 100.0 20 Select the process acceleration speed. (Lower numbers cause faster
response to changes)
System Pump
Modulation Signal
0-10 Vdc,
4-20mA 0-10 Vdc
Choose the type of signal you desire to be sent to modulate this
pump, 0-10 Vdc or 4-20mA. (also requires wiring to the correct
terminal on the control)
System Pump Delta T
Operations Enable / Disable Disable Choose enable if you desire to modulate this pump based on the
system Delta T.
System Pump Delta P
Operations Enable / Disable Disable Choose enable if you desire to modulate this pump based on the
system Delta P.
Delta P Transducer
Pressure at 10Vdc
(20mA) Input
0-50 Psi 30 Input the value of the pressure (in Psig 0.0) the transducer will
experience at 20mA or 10Vdc
Delta P Transducer
Pressure at 0Vdc
(4mA) Input
0-10 Psi 0 Input the value of the pressure (in Psig 0.0) the transducer will
experience at 4mA or 0Vdc
Delta P Pressure Set
point 0-50 Psi 10 Choose the differential pressure the pump is modulated to maintain
Delta P Pressure
Transducer Input
Signal
0-10 Vdc,
4-20mA 0-10 Vdc Choose the input signal of the pressure transducer (0-10 Vdc or
4-20mA)
Zone Pump
Parameters
Activation Enable / Disable Enable Choose Enable to activate this pump to be used in this system.
Dedicated Lead Enable / Disable Enable Choose Enable to always use this pump as the lead pump in this
system. Pump = on when heating operations are on
Lead-Lag / Lead-
Help
Lead-Lag / Lead-
Help Lead-Lag
Choose "Lead/Lag" if this pump will be rotated into the lead
position as an either or pumping scenario. For lead/lag switching +
help when using variable speed pumping chose "Lead/Help" in
order to meet flow requirements of the system based on Delta P or
Delta T system needs.
Lead Shutdown
Delay (for Lead-Lag) 10 - 120 Sec 30 Choose the number of seconds you would like to delay the
shutdown of the lead pump in this system.
Lag Help Enable
Output % (for Lead-
Help)
51-100% 100 Choose the percentage of sustained pump output required to enable
the lag pump.
Lag Help Disable
Output % (for Lead-
1-50% 40 Choose the percentage of sustained pump output required to disable
the lag pump.
TPC-FI SoloNet O&M Page 45
Help)
Lag Help Delay (for
Lead-Help) 1 - 60 Min 30
Choose the number of minutes the conditions (Output %) for lag
help Enable/Disable must be sustained before action is taken to
Enable or Disable the lag pump
Rotation Hours (for
Lead-Lag or Lead-
Help)
12 - 720 Hrs 168 Choose the number of hours you desire this pump to stay in the lead
position.
Heat Enable
Shutdown Delay
Time
1 - 120 Min 60
Choose the number of minutes you would like the pumps to
continue to operate after the system has been shut down on outdoor
air temperature.
Zone Pump
Maximum
Modulation
Percentage
50 - 100 % 100 Choose the maximum modulation signal expressed as a percentage
you desire to be sent to this pump.
Zone Pump
Minimum
Modulation
Percentage
0 - 50 % 35 Choose the minimum modulation signal expressed as a percentage
you desire to be sent to this pump.
Zone Pump Process
Acceleration 0 - 100.0 20 Select the process acceleration speed. (Lower numbers cause faster
response to changes)
Zone Pump
Modulation Signal
0-10 Vdc,
4-20mA 0-10 Vdc
Choose the type of signal you desire to be sent to modulate this
pump, 0-10 Vdc or 4-20mA. (also requires wiring to the correct
terminal on the control)
Zone Pump Delta T
Operations Enable / Disable Disable Choose enable if you desire to modulate this pump based on the
Zone Delta T.
Zone Pump Delta T
Set-point 0 - 100 F 10 Choose the Delta T you desire to be kept across this zone.
Zone Pump Delta P
Operations Enable / Disable Disable Choose enable if you desire to modulate this pump based on the
system Delta P.
Delta P Transducer
Pressure at 10Vdc
(20mA) Input
0-50 Psi 30 Input the value of the pressure (in Psig 0.0) the transducer will
experience at 20mA or 10Vdc
Delta P Transducer
Pressure at 0Vdc
(4mA) Input
0-10 Psi 0 Input the value of the pressure (in Psig 0.0) the transducer will
experience at 4mA or 0Vdc
Delta P Pressure Set
point 0-50 Psi 10 Choose the differential pressure the pump is modulated to maintain
Delta P Pressure
Transducer Input
Signal
0-10 Vdc,
4-20mA 0-10 Vdc Choose the input signal of the pressure transducer (0-10 Vdc or
4-20mA)
Boiler Parameters
Activation Enable / Disable Enable Choose enable to activate this boiler for use in this system.
TPC-FI SoloNet O&M Page 46
Flow Sensitive Yes/No Yes
Choose Yes unless the boiler you are configuring is rated by its
manufacturer as having no minimum flow requirements. Choosing
"No" allows boiler secondary pump modulation off the boiler
device. It allows another Field Device dedicated to boiler
secondary pumping to control boiler pump modulation through
wireless network traffic of boiler inlet and outlet temperatures.
Choosing "Yes" forces boiler secondary pump modulation to occur
local on the Boiler Field Device only.
Boiler Type - Cond /
NonCond Cond / NonCond Cond Choose Cond. For condensing boilers, Choose NonCond for non-
condensing boilers
Boiler Fire Delay
Seconds 30 - 300 Sec 90 Choose the number of seconds between when this boiler is enabled
until it has established main flame.
Boiler Low Fire Hold
Minutes 5 - 60 Min 15 Choose the number of minutes you desire for the control to keep
this boiler in low fire at the beginning of every cycle
Boiler Maximum
Runtime Hours 1 - 24 Hrs 12 Choose the maximum number of hours you desire for this boiler to
run in any single cycle.
Maximum Boiler
MBH Output 1 - 52,000 MBH 3000 Enter in MBH the maximum output of this boiler. (Mbh =
Btu/1000)
Minimum Boiler
MBH Output 1 - 26,000 MBH 1500 Enter in MBH the minimum output of this boiler. (Mbh =
Btu/1000)
Maximum Boiler
Outlet Temperature 160 - 210 F 180 Enter the maximum outlet water temperature allowed to be supplied
by this boiler.
Minimum Boiler Inlet
Temperature 20 - 150 F 130 Enter the minimum inlet water temperature allowed to be returned
to this boiler.
Maximum Boiler
Output Percentage 50 - 100 % 100
Enter the maximum output percentage signal that you would like to
send this boiler. This is used to help establish the relationship
between output signal and Mbh output value of the boiler. ( If 9.00
Vdc = maximum boiler output then enter 90%)
Minimum Boiler
Output Percentage 0 - 50 % 18
Enter the minimum output percentage signal that you would like to
send this boiler. This is used to help establish the relationship
between output signal and Mbh output value of the boiler. ( If 1.80
Vdc = minimum boiler output then enter 18%)
Boiler Ignition
Output Percentage 0 - 50 % 0
Enter the output percentage at which main flame is ignited. Some
boilers light off at greater than minimum signal. If light off of the
boiler is 50% of output then enter 50%. This modulation signal
will be sent to the boiler during the entire fire delay.
Boiler Next Stage
Percentage 10 - 100 % 85 This is the percentage of boiler output that must be sustained for the
entire "Stage Delay Time" before another boiler is enabled.
Boiler Turn Down 2:1-10:1 0
Enter the turn-down of this boiler. For turn-down's greater than 5:1
check with the start-up technician to confirm the field configured
turn-down for the boiler.
Boiler Maximum
Output Manual Limit 10 - 100 % 100
This is the maximum output signal to the boiler. It is not linked to
the load calculation. It is used to limit a boilers output. Suggested
use is a limit for output during start up and combustion analization.
Boiler Maximum
Allowable Delta T. 2 - 160 F 20
Enter the maximum allowable Delta T for this boiler. This is the
manufacturers maximum allowable Delta T the boiler is allowed to
achieve.
Boiler Maximum
operating Delta T. 0 - 158 F 15
Enter the maximum operating Delta T for this boiler. This is the
set-point for the user to choose a number at least 2 degrees
Fahrenheit below maximum allowable boiler Delta T. This number
shall be used for modulation limits and error calculations
TPC-FI SoloNet O&M Page 47
Standby Mode Enable / Disable Disable
Choose enable if you desire this boiler to be used as a standby
boiler. A standby boiler is the lowest priority for operation and will
be selected if all other boilers on the network are failing to meet the
load requirements
Winter Priority Mode Enable / Disable Disable
Choose enable if you desire this boiler to be a "Winter Priority"
boiler. Note: You must have activated winter priority under system
settings and chosen a date to put this boiler into priority to use this
feature.
Boiler Water Volume
Gallons 1 - 12,000 Gal 100 Enter the volume of water in this boiler.
Maximum Rated
Efficiency 65 - 99 % 85 Enter the maximum rated efficiency for this boiler
Process Output
Acceleration 1 - 100.0 30 Select the process acceleration speed. (Lower numbers cause faster
response to changes)
Boiler Modulation
Signal
0-10 Vdc,
4-20mA 0-10 Vdc
Choose the type of signal you desire to be sent to modulate this
boiler, 0-10 Vdc or 4-20mA. (also requires wiring to the correct
terminal on the control)
DHWP (on-board or
Network) Enable / Disable Disable Select to enable this boiler for DHWP operations. This must be
selected of either on board priority or Network priority
DHWP Set-point (on-
board only) 110-240F 140F Provide the outlet water temperature this boiler will be asked to
provide when producing domestic hot water.
DHWP Maximum
Hysteresis (on-board
only)
5-30F 10F
This is the maximum allowable overshoot of the DHWP set-point
for boiler water temperature. Outlet temperatures exceeding this
value will cause the boiler to disable until the DHWP Minimum
Hysteresis value has been reached
DHWP Minimum
Hysteresis (on-board
only)
3-20F 3F
This is the minimum allowable under-shoot of the DHWP set-point
for boiler water temperature. Outlet temperatures less than or equal
to this value will cause the boiler in priority to enable until the
DHWP Maximum Hysteresis value has been reached or until the
priority has ended
DHWP Override (on-
board only) 15 - 181 Min 30 Choose the maximum number of minutes this boiler can be used to
provide DHW when there is simultaneously a call for comfort heat.
Boiler Pump
Parameters
Activation Enable / Disable Enable Choose enable to activate this boiler pump for use in this system.
Pump control / Valve
control Pump / Valve Pump Choose the device that is being controlled
Boiler Pump Off
Delay 1 - 15 Min 10 Enter the number of minutes you would like this pump to run after
the boiler has finished a cycle.
Boiler Pump
Modulation Enable / Disable Disable Enter "enable" if this pump is connected to a frequency drive and
you wish to modulate that drive based on boiler Delta T
Boiler Delta T Set
point 0 - 158 F 20
Enter the Delta T that you desire across this boiler. This number
needs to be less than or equal to the value chosen as the maximum
operating Delta chosen under Boiler Parameters for the boiler
assigned to this pump.
Boiler Pump
Maximum
Modulation
50 - 100 % 100 Choose the maximum modulation signal expressed as a percentage
you desire to be sent to this pump.
TPC-FI SoloNet O&M Page 48
Percentage
Boiler Pump
Minimum
Modulation
Percentage
0 - 50 % 30 Choose the minimum modulation signal expressed as a percentage
you desire to be sent to this pump.
Boiler Pump Process
Acceleration 1 - 100.0 30 Select the process acceleration speed. (Lower numbers cause faster
response to changes)
Boiler Pump
Modulation Signal
0-10 Vdc,
4-20mA 0-10 Vdc
Choose the type of signal you desire to be sent to modulate this
pump, 0-10 Vdc or 4-20mA. (also requires wiring to the correct
terminal on the control)
Damper Parameters
Activation Enable / Disable Enable Choose enable to allow this damper to be used in this system.
Boiler Association 1-1, 1-16 Range (1 - 1)
Identify the boiler(s) that this damper will work with. Boilers must
be in sequential order. For example: Inputting 1-3 will not enable
the damper on just 1 and 3. If 1-3 is chosen then boiler 1,2 & 3 will
enable this damper if any or all of these boilers are enabled.
TPC-FI SoloNet O&M Page 49
Appendix B
TPC-FI SoloNet O&M Page 50
ADDRESS TAG NAME TAG
DATATYPE
NOD
E
405000 MODBUS_ON_OFF_WRITE UNSIGNED_16 PLC1
405001 BMS_ENABLE_CONTROL_WRITE UNSIGNED_16 PLC1
405002 SYSTEM_SETPOINT_WRITE UNSIGNED_16 PLC1
405003 REMOTE_ENABLE UNSIGNED_16 PLC1
405004 SYSTEM_SETPOINT_READ UNSIGNED_16 PLC1
405005 CONDENSING UNSIGNED_16 PLC1
405006 OPTIMUM_STOP UNSIGNED_16 PLC1
405007 OPTIMUM_START UNSIGNED_16 PLC1
405008 OCCUPIED_OPERATIONS UNSIGNED_16 PLC1
405009 UNOCCUPIED_OPERATIONS UNSIGNED_16 PLC1
405010 WINTER_HEAT UNSIGNED_16 PLC1
405011 SUMMER_HEAT UNSIGNED_16 PLC1
405012 WINTER_PRIO UNSIGNED_16 PLC1
405013 SYSTEM_SUPPLY_TEMP SIGNED_16 PLC1
405014 SYSTEM_RETURN_TEMPERATURE SIGNED_16 PLC1
405015 OUTDOOR_AIR_TEMPERATURE SIGNED_16 PLC1
405016 SYSTEM_GPM_FLOW UNSIGNED_16 PLC1
405017 SYSTEM_MBH_LOAD UNSIGNED_32 PLC1
405018 PLC1
405019 MBREG_MAX_HYST SIGNED_16 PLC1
405020 MBREG_MIN_HYST SIGNED_16 PLC1
405021 SYSTEM_DELTA_T SIGNED_16 PLC1
405022 WINTER_HEAT_ON_SP SIGNED_16 PLC1
405023 WINTER_HEAT_OFF_SP SIGNED_16 PLC1
405024 REHEAT_ON_SETPOINT SIGNED_16 PLC1
405025 REHEAT_OFF_SETPOINT SIGNED_16 PLC1
405026 DATE UNSIGNED_16 PLC1
405027 24HR_TIME UNSIGNED_16 PLC1
TPC-FI SoloNet O&M Page 51
405028 SYS_7 UNSIGNED_16 PLC1
405029 SYS_8 UNSIGNED_16 PLC1
405030 SYS_9 UNSIGNED_16 PLC1
405031 MBREG_TPCMODBUS_VERSION UNSIGNED_16 PLC1
405032 MBREG_NUM_MAIN_PUMPS UNSIGNED_16 PLC1
405033 MBREG_FIRST_MAIN_PUMP_ADDR UNSIGNED_16 PLC1
405034 MBREG_NUM_BOILERS UNSIGNED_16 PLC1
405035 MBREG_FIRST_BOILER_ADDR UNSIGNED_16 PLC1
405036-40
5099 Reserved PLC1
405100 MP_EXISTING PUMP1 UNSIGNED_16 PLC1
405101 MP_ON UNSIGNED_16 PLC1
405102 MP_LEAD UNSIGNED_16 PLC1
405103-40
5105 Reserved PLC1
405106 MP_EXISTING PUMP2 UNSIGNED_16 PLC1
405107 MP_ON UNSIGNED_16 PLC1
405108 MP_LEAD UNSIGNED_16 PLC1
405109-40
5111 Reserved PLC1
405112 MP_EXISTING PUMP3 UNSIGNED_16 PLC1
405113 MP_ON UNSIGNED_16 PLC1
405114 MP_LEAD UNSIGNED_16 PLC1
405115-40
5117 Reserved PLC1
405118 MP_EXISTING PUMP4 UNSIGNED_16 PLC1
405119 MP_ON UNSIGNED_16 PLC1
405120 MP_LEAD UNSIGNED_16 PLC1
405121-40
5123 Reserved PLC1
405124 MP_EXISTING PUMP5 UNSIGNED_16 PLC1
405125 MP_ON UNSIGNED_16 PLC1
405126 MP_LEAD UNSIGNED_16 PLC1
405127-40
5129 Reserved PLC1
405130 MP_EXISTING PUMP6 UNSIGNED_16 PLC1
405131 MP_ON UNSIGNED_16 PLC1
405132 MP_LEAD UNSIGNED_16 PLC1
405133-40 Reserved PLC1
TPC-FI SoloNet O&M Page 52
5135
405136 MP_EXISTING PUMP7 UNSIGNED_16 PLC1
405137 MP_ON UNSIGNED_16 PLC1
405138 MP_LEAD UNSIGNED_16 PLC1
405139-40
5141 Reserved PLC1
405142 MP_EXISTING PUMP8 UNSIGNED_16 PLC1
405143 MP_ON UNSIGNED_16 PLC1
405144 MP_LEAD UNSIGNED_16 PLC1
405145-40
5147 Reserved PLC1
405148 MP_EXISTING PUMP9 UNSIGNED_16 PLC1
405149 MP_ON UNSIGNED_16 PLC1
405150 MP_LEAD UNSIGNED_16 PLC1
405151-40
5153 Reserved PLC1
405154 MP_EXISTING PUMP10 UNSIGNED_16 PLC1
405155 MP_ON UNSIGNED_16 PLC1
405156 MP_LEAD UNSIGNED_16 PLC1
405157-40
5159 Reserved PLC1
405160 MP_EXISTING PUMP11 UNSIGNED_16 PLC1
405161 MP_ON UNSIGNED_16 PLC1
405162 MP_LEAD UNSIGNED_16 PLC1
405163-40
5165 Reserved PLC1
405166 MP_EXISTING PUMP12 UNSIGNED_16 PLC1
405167 MP_ON UNSIGNED_16 PLC1
405168 MP_LEAD UNSIGNED_16 PLC1
405169-40
5171 Reserved PLC1
405172 MP_EXISTING PUMP13 UNSIGNED_16 PLC1
405173 MP_ON UNSIGNED_16 PLC1
405174 MP_LEAD UNSIGNED_16 PLC1
405175-40
5177 Reserved PLC1
405178 MP_EXISTING PUMP14 UNSIGNED_16 PLC1
405179 MP_ON UNSIGNED_16 PLC1
405180 MP_LEAD UNSIGNED_16 PLC1
TPC-FI SoloNet O&M Page 53
405181-40
5183 Reserved PLC1
405184 MP_EXISTING PUMP15 UNSIGNED_16 PLC1
405185 MP_ON UNSIGNED_16 PLC1
405186 MP_LEAD UNSIGNED_16 PLC1
405187-40
5189 Reserved PLC1
405190 MP_EXISTING PUMP16 UNSIGNED_16 PLC1
405191 MP_ON UNSIGNED_16 PLC1
405192 MP_LEAD UNSIGNED_16 PLC1
405193-40
5199 Reserved PLC1
405200 B_EXISTING BOILER1 UNSIGNED_16 PLC1
405201 B_ACTIVE UNSIGNED_16 PLC1
405202 B_ALARM UNSIGNED_16 PLC1
405203 B_CON_NON UNSIGNED_16 PLC1
405204 B_WINTER UNSIGNED_16 PLC1
405205 B_DHWP UNSIGNED_16 PLC1
405206 B_ON UNSIGNED_16 PLC1
405207 B_PUMP_EXISTING UNSIGNED_16 PLC1
405208 B_PUMP_ON UNSIGNED_16 PLC1
405209 B_VALVE_EXISTING UNSIGNED_16 PLC1
405210 B_VALVE_ON UNSIGNED_16 PLC1
405211 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405212 B_DAMPER_ON UNSIGNED_16 PLC1
405213 B_DAMPER_PROVE UNSIGNED_16 PLC1
405214 B_OUTLET_TEMP SIGNED_16 PLC1
405215 B_INLET_TEMP SIGNED_16 PLC1
405216 B_STACK_TEMP SIGNED_16 PLC1
405217 B_CYCLE_TIME UNSIGNED_16 PLC1
405218 B_CYCLE_COUNT UNSIGNED_32 PLC1
405219 PLC1
405220 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405221 PLC1
405222 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405223 PLC1
405224 B_MBH_OUTPUT UNSIGNED_32 PLC1
405225 PLC1
TPC-FI SoloNet O&M Page 54
405226-40
5249 Reserved PLC1
405250 B_EXISTING BOILER2 UNSIGNED_16 PLC1
405251 B_ACTIVE UNSIGNED_16 PLC1
405252 B_ALARM UNSIGNED_16 PLC1
405253 B_CON_NON UNSIGNED_16 PLC1
405254 B_WINTER UNSIGNED_16 PLC1
405255 B_DHWP UNSIGNED_16 PLC1
405256 B_ON UNSIGNED_16 PLC1
405257 B_PUMP_EXISTING UNSIGNED_16 PLC1
405258 B_PUMP_ON UNSIGNED_16 PLC1
405259 B_VALVE_EXISTING UNSIGNED_16 PLC1
405260 B_VALVE_ON UNSIGNED_16 PLC1
405261 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405262 B_DAMPER_ON UNSIGNED_16 PLC1
405263 B_DAMPER_PROVE UNSIGNED_16 PLC1
405264 B_OUTLET_TEMP SIGNED_16 PLC1
405265 B_INLET_TEMP SIGNED_16 PLC1
405266 B_STACK_TEMP SIGNED_16 PLC1
405267 B_CYCLE_TIME UNSIGNED_16 PLC1
405268 B_CYCLE_COUNT UNSIGNED_32 PLC1
405269 PLC1
405270 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405271 PLC1
405272 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405273 PLC1
405274 B_MBH_OUTPUT UNSIGNED_32 PLC1
405275 PLC1
405276-40
5299 Reserved PLC1
405300 B_EXISTING BOILER3 UNSIGNED_16 PLC1
405301 B_ACTIVE UNSIGNED_16 PLC1
405302 B_ALARM UNSIGNED_16 PLC1
405303 B_CON_NON UNSIGNED_16 PLC1
405304 B_WINTER UNSIGNED_16 PLC1
405305 B_DHWP UNSIGNED_16 PLC1
405306 B_ON UNSIGNED_16 PLC1
405307 B_PUMP_EXISTING UNSIGNED_16 PLC1
TPC-FI SoloNet O&M Page 55
405308 B_PUMP_ON UNSIGNED_16 PLC1
405309 B_VALVE_EXISTING UNSIGNED_16 PLC1
405310 B_VALVE_ON UNSIGNED_16 PLC1
405311 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405312 B_DAMPER_ON UNSIGNED_16 PLC1
405313 B_DAMPER_PROVE UNSIGNED_16 PLC1
405314 B_OUTLET_TEMP SIGNED_16 PLC1
405315 B_INLET_TEMP SIGNED_16 PLC1
405316 B_STACK_TEMP SIGNED_16 PLC1
405317 B_CYCLE_TIME UNSIGNED_16 PLC1
405318 B_CYCLE_COUNT UNSIGNED_32 PLC1
405319 PLC1
405320 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405321 PLC1
405322 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405323 PLC1
405324 B_MBH_OUTPUT UNSIGNED_32 PLC1
405325 PLC1
405326-40
5349 Reserved PLC1
405350 B_EXISTING BOILER4 UNSIGNED_16 PLC1
405351 B_ACTIVE UNSIGNED_16 PLC1
405352 B_ALARM UNSIGNED_16 PLC1
405353 B_CON_NON UNSIGNED_16 PLC1
405354 B_WINTER UNSIGNED_16 PLC1
405355 B_DHWP UNSIGNED_16 PLC1
405356 B_ON UNSIGNED_16 PLC1
405357 B_PUMP_EXISTING UNSIGNED_16 PLC1
405358 B_PUMP_ON UNSIGNED_16 PLC1
405359 B_VALVE_EXISTING UNSIGNED_16 PLC1
405360 B_VALVE_ON UNSIGNED_16 PLC1
405361 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405362 B_DAMPER_ON UNSIGNED_16 PLC1
405363 B_DAMPER_PROVE UNSIGNED_16 PLC1
405364 B_OUTLET_TEMP SIGNED_16 PLC1
405365 B_INLET_TEMP SIGNED_16 PLC1
405366 B_STACK_TEMP SIGNED_16 PLC1
405367 B_CYCLE_TIME UNSIGNED_16 PLC1
TPC-FI SoloNet O&M Page 56
405368 B_CYCLE_COUNT UNSIGNED_32 PLC1
405369 PLC1
405370 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405371 PLC1
405372 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405373 PLC1
405374 B_MBH_OUTPUT UNSIGNED_32 PLC1
405375 PLC1
405376-40
5399 Reserved PLC1
405400 B_EXISTING BOILER5 UNSIGNED_16 PLC1
405401 B_ACTIVE UNSIGNED_16 PLC1
405402 B_ALARM UNSIGNED_16 PLC1
405403 B_CON_NON UNSIGNED_16 PLC1
405404 B_WINTER UNSIGNED_16 PLC1
405405 B_DHWP UNSIGNED_16 PLC1
405406 B_ON UNSIGNED_16 PLC1
405407 B_PUMP_EXISTING UNSIGNED_16 PLC1
405408 B_PUMP_ON UNSIGNED_16 PLC1
405409 B_VALVE_EXISTING UNSIGNED_16 PLC1
405410 B_VALVE_ON UNSIGNED_16 PLC1
405411 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405412 B_DAMPER_ON UNSIGNED_16 PLC1
405413 B_DAMPER_PROVE UNSIGNED_16 PLC1
405414 B_OUTLET_TEMP SIGNED_16 PLC1
405415 B_INLET_TEMP SIGNED_16 PLC1
405416 B_STACK_TEMP SIGNED_16 PLC1
405417 B_CYCLE_TIME UNSIGNED_16 PLC1
405418 B_CYCLE_COUNT UNSIGNED_32 PLC1
405419 PLC1
405420 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405421 PLC1
405422 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405423 PLC1
405424 B_MBH_OUTPUT UNSIGNED_32 PLC1
405425 PLC1
405426-40
5449 Reserved PLC1
TPC-FI SoloNet O&M Page 57
405450 B_EXISTING BOILER6 UNSIGNED_16 PLC1
405451 B_ACTIVE UNSIGNED_16 PLC1
405452 B_ALARM UNSIGNED_16 PLC1
405453 B_CON_NON UNSIGNED_16 PLC1
405454 B_WINTER UNSIGNED_16 PLC1
405455 B_DHWP UNSIGNED_16 PLC1
405456 B_ON UNSIGNED_16 PLC1
405457 B_PUMP_EXISTING UNSIGNED_16 PLC1
405458 B_PUMP_ON UNSIGNED_16 PLC1
405459 B_VALVE_EXISTING UNSIGNED_16 PLC1
405460 B_VALVE_ON UNSIGNED_16 PLC1
405461 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405462 B_DAMPER_ON UNSIGNED_16 PLC1
405463 B_DAMPER_PROVE UNSIGNED_16 PLC1
405464 B_OUTLET_TEMP SIGNED_16 PLC1
405465 B_INLET_TEMP SIGNED_16 PLC1
405466 B_STACK_TEMP SIGNED_16 PLC1
405467 B_CYCLE_TIME UNSIGNED_16 PLC1
405468 B_CYCLE_COUNT UNSIGNED_32 PLC1
405469 PLC1
405470 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405471 PLC1
405472 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405473 PLC1
405474 B_MBH_OUTPUT UNSIGNED_32 PLC1
405475 PLC1
405476-40
5499 Reserved PLC1
405500 B_EXISTING BOILER7 UNSIGNED_16 PLC1
405501 B_ACTIVE UNSIGNED_16 PLC1
405502 B_ALARM UNSIGNED_16 PLC1
405503 B_CON_NON UNSIGNED_16 PLC1
405504 B_WINTER UNSIGNED_16 PLC1
405505 B_DHWP UNSIGNED_16 PLC1
405506 B_ON UNSIGNED_16 PLC1
405507 B_PUMP_EXISTING UNSIGNED_16 PLC1
405508 B_PUMP_ON UNSIGNED_16 PLC1
405509 B_VALVE_EXISTING UNSIGNED_16 PLC1
TPC-FI SoloNet O&M Page 58
405510 B_VALVE_ON UNSIGNED_16 PLC1
405511 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405512 B_DAMPER_ON UNSIGNED_16 PLC1
405513 B_DAMPER_PROVE UNSIGNED_16 PLC1
405514 B_OUTLET_TEMP SIGNED_16 PLC1
405515 B_INLET_TEMP SIGNED_16 PLC1
405516 B_STACK_TEMP SIGNED_16 PLC1
405517 B_CYCLE_TIME UNSIGNED_16 PLC1
405518 B_CYCLE_COUNT UNSIGNED_32 PLC1
405519 PLC1
405520 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405521 PLC1
405522 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405523 PLC1
405524 B_MBH_OUTPUT UNSIGNED_32 PLC1
405525 PLC1
405526-40
5549 Reserved PLC1
405550 B_EXISTING BOILER8 UNSIGNED_16 PLC1
405551 B_ACTIVE UNSIGNED_16 PLC1
405552 B_ALARM UNSIGNED_16 PLC1
405553 B_CON_NON UNSIGNED_16 PLC1
405554 B_WINTER UNSIGNED_16 PLC1
405555 B_DHWP UNSIGNED_16 PLC1
405556 B_ON UNSIGNED_16 PLC1
405557 B_PUMP_EXISTING UNSIGNED_16 PLC1
405558 B_PUMP_ON UNSIGNED_16 PLC1
405559 B_VALVE_EXISTING UNSIGNED_16 PLC1
405560 B_VALVE_ON UNSIGNED_16 PLC1
405561 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405562 B_DAMPER_ON UNSIGNED_16 PLC1
405563 B_DAMPER_PROVE UNSIGNED_16 PLC1
405564 B_OUTLET_TEMP SIGNED_16 PLC1
405565 B_INLET_TEMP SIGNED_16 PLC1
405566 B_STACK_TEMP SIGNED_16 PLC1
405567 B_CYCLE_TIME UNSIGNED_16 PLC1
405568 B_CYCLE_COUNT UNSIGNED_32 PLC1
405569 PLC1
TPC-FI SoloNet O&M Page 59
405570 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405571 PLC1
405572 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405573 PLC1
405574 B_MBH_OUTPUT UNSIGNED_32 PLC1
405575 PLC1
405576-40
5599 Reserved PLC1
405600 B_EXISTING BOILER9 UNSIGNED_16 PLC1
405601 B_ACTIVE UNSIGNED_16 PLC1
405602 B_ALARM UNSIGNED_16 PLC1
405603 B_CON_NON UNSIGNED_16 PLC1
405604 B_WINTER UNSIGNED_16 PLC1
405605 B_DHWP UNSIGNED_16 PLC1
405606 B_ON UNSIGNED_16 PLC1
405607 B_PUMP_EXISTING UNSIGNED_16 PLC1
405608 B_PUMP_ON UNSIGNED_16 PLC1
405609 B_VALVE_EXISTING UNSIGNED_16 PLC1
405610 B_VALVE_ON UNSIGNED_16 PLC1
405611 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405612 B_DAMPER_ON UNSIGNED_16 PLC1
405613 B_DAMPER_PROVE UNSIGNED_16 PLC1
405614 B_OUTLET_TEMP SIGNED_16 PLC1
405615 B_INLET_TEMP SIGNED_16 PLC1
405616 B_STACK_TEMP SIGNED_16 PLC1
405617 B_CYCLE_TIME UNSIGNED_16 PLC1
405618 B_CYCLE_COUNT UNSIGNED_32 PLC1
405619 PLC1
405620 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405621 PLC1
405622 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405623 PLC1
405624 B_MBH_OUTPUT UNSIGNED_32 PLC1
405625 PLC1
405626-40
5649 Reserved PLC1
405650 B_EXISTING BOILER1
0UNSIGNED_16 PLC1
TPC-FI SoloNet O&M Page 60
405651 B_ACTIVE UNSIGNED_16 PLC1
405652 B_ALARM UNSIGNED_16 PLC1
405653 B_CON_NON UNSIGNED_16 PLC1
405654 B_WINTER UNSIGNED_16 PLC1
405655 B_DHWP UNSIGNED_16 PLC1
405656 B_ON UNSIGNED_16 PLC1
405657 B_PUMP_EXISTING UNSIGNED_16 PLC1
405658 B_PUMP_ON UNSIGNED_16 PLC1
405659 B_VALVE_EXISTING UNSIGNED_16 PLC1
405660 B_VALVE_ON UNSIGNED_16 PLC1
405661 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405662 B_DAMPER_ON UNSIGNED_16 PLC1
405663 B_DAMPER_PROVE UNSIGNED_16 PLC1
405664 B_OUTLET_TEMP SIGNED_16 PLC1
405665 B_INLET_TEMP SIGNED_16 PLC1
405666 B_STACK_TEMP SIGNED_16 PLC1
405667 B_CYCLE_TIME UNSIGNED_16 PLC1
405668 B_CYCLE_COUNT UNSIGNED_32 PLC1
405669 PLC1
405670 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405671 PLC1
405672 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405673 PLC1
405674 B_MBH_OUTPUT UNSIGNED_32 PLC1
405675 PLC1
405676-40
5699 Reserved PLC1
405700 B_EXISTING BOILER1
1UNSIGNED_16 PLC1
405701 B_ACTIVE UNSIGNED_16 PLC1
405702 B_ALARM UNSIGNED_16 PLC1
405703 B_CON_NON UNSIGNED_16 PLC1
405704 B_WINTER UNSIGNED_16 PLC1
405705 B_DHWP UNSIGNED_16 PLC1
405706 B_ON UNSIGNED_16 PLC1
405707 B_PUMP_EXISTING UNSIGNED_16 PLC1
405708 B_PUMP_ON UNSIGNED_16 PLC1
405709 B_VALVE_EXISTING UNSIGNED_16 PLC1
TPC-FI SoloNet O&M Page 61
405710 B_VALVE_ON UNSIGNED_16 PLC1
405711 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405712 B_DAMPER_ON UNSIGNED_16 PLC1
405713 B_DAMPER_PROVE UNSIGNED_16 PLC1
405714 B_OUTLET_TEMP SIGNED_16 PLC1
405715 B_INLET_TEMP SIGNED_16 PLC1
405716 B_STACK_TEMP SIGNED_16 PLC1
405717 B_CYCLE_TIME UNSIGNED_16 PLC1
405718 B_CYCLE_COUNT UNSIGNED_32 PLC1
405719 PLC1
405720 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405721 PLC1
405722 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405723 PLC1
405724 B_MBH_OUTPUT UNSIGNED_32 PLC1
405725 PLC1
405726-40
5749 Reserved PLC1
405750 B_EXISTING BOILER1
2UNSIGNED_16 PLC1
405751 B_ACTIVE UNSIGNED_16 PLC1
405752 B_ALARM UNSIGNED_16 PLC1
405753 B_CON_NON UNSIGNED_16 PLC1
405754 B_WINTER UNSIGNED_16 PLC1
405755 B_DHWP UNSIGNED_16 PLC1
405756 B_ON UNSIGNED_16 PLC1
405757 B_PUMP_EXISTING UNSIGNED_16 PLC1
405758 B_PUMP_ON UNSIGNED_16 PLC1
405759 B_VALVE_EXISTING UNSIGNED_16 PLC1
405760 B_VALVE_ON UNSIGNED_16 PLC1
405761 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405762 B_DAMPER_ON UNSIGNED_16 PLC1
405763 B_DAMPER_PROVE UNSIGNED_16 PLC1
405764 B_OUTLET_TEMP SIGNED_16 PLC1
405765 B_INLET_TEMP SIGNED_16 PLC1
405766 B_STACK_TEMP SIGNED_16 PLC1
405767 B_CYCLE_TIME UNSIGNED_16 PLC1
405768 B_CYCLE_COUNT UNSIGNED_32 PLC1
TPC-FI SoloNet O&M Page 62
405769 PLC1
405770 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405771 PLC1
405772 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405773 PLC1
405774 B_MBH_OUTPUT UNSIGNED_32 PLC1
405775 PLC1
405776-40
5799 Reserved PLC1
405800 B_EXISTING BOILER1
3UNSIGNED_16 PLC1
405801 B_ACTIVE UNSIGNED_16 PLC1
405802 B_ALARM UNSIGNED_16 PLC1
405803 B_CON_NON UNSIGNED_16 PLC1
405804 B_WINTER UNSIGNED_16 PLC1
405805 B_DHWP UNSIGNED_16 PLC1
405806 B_ON UNSIGNED_16 PLC1
405807 B_PUMP_EXISTING UNSIGNED_16 PLC1
405808 B_PUMP_ON UNSIGNED_16 PLC1
405809 B_VALVE_EXISTING UNSIGNED_16 PLC1
405810 B_VALVE_ON UNSIGNED_16 PLC1
405811 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405812 B_DAMPER_ON UNSIGNED_16 PLC1
405813 B_DAMPER_PROVE UNSIGNED_16 PLC1
405814 B_OUTLET_TEMP SIGNED_16 PLC1
405815 B_INLET_TEMP SIGNED_16 PLC1
405816 B_STACK_TEMP SIGNED_16 PLC1
405817 B_CYCLE_TIME UNSIGNED_16 PLC1
405818 B_CYCLE_COUNT UNSIGNED_32 PLC1
405819 PLC1
405820 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405821 PLC1
405822 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405823 PLC1
405824 B_MBH_OUTPUT UNSIGNED_32 PLC1
405825 PLC1
405826-40
5849 Reserved PLC1
TPC-FI SoloNet O&M Page 63
405850 B_EXISTING BOILER1
4UNSIGNED_16 PLC1
405851 B_ACTIVE UNSIGNED_16 PLC1
405852 B_ALARM UNSIGNED_16 PLC1
405853 B_CON_NON UNSIGNED_16 PLC1
405854 B_WINTER UNSIGNED_16 PLC1
405855 B_DHWP UNSIGNED_16 PLC1
405856 B_ON UNSIGNED_16 PLC1
405857 B_PUMP_EXISTING UNSIGNED_16 PLC1
405858 B_PUMP_ON UNSIGNED_16 PLC1
405859 B_VALVE_EXISTING UNSIGNED_16 PLC1
405860 B_VALVE_ON UNSIGNED_16 PLC1
405861 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405862 B_DAMPER_ON UNSIGNED_16 PLC1
405863 B_DAMPER_PROVE UNSIGNED_16 PLC1
405864 B_OUTLET_TEMP SIGNED_16 PLC1
405865 B_INLET_TEMP SIGNED_16 PLC1
405866 B_STACK_TEMP SIGNED_16 PLC1
405867 B_CYCLE_TIME UNSIGNED_16 PLC1
405868 B_CYCLE_COUNT UNSIGNED_32 PLC1
405869 PLC1
405870 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405871 PLC1
405872 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405873 PLC1
405874 B_MBH_OUTPUT UNSIGNED_32 PLC1
405875 PLC1
405876-40
5899 Reserved PLC1
405900 B_EXISTING BOILER1
5UNSIGNED_16 PLC1
405901 B_ACTIVE UNSIGNED_16 PLC1
405902 B_ALARM UNSIGNED_16 PLC1
405903 B_CON_NON UNSIGNED_16 PLC1
405904 B_WINTER UNSIGNED_16 PLC1
405905 B_DHWP UNSIGNED_16 PLC1
405906 B_ON UNSIGNED_16 PLC1
405907 B_PUMP_EXISTING UNSIGNED_16 PLC1
TPC-FI SoloNet O&M Page 64
405908 B_PUMP_ON UNSIGNED_16 PLC1
405909 B_VALVE_EXISTING UNSIGNED_16 PLC1
405910 B_VALVE_ON UNSIGNED_16 PLC1
405911 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405912 B_DAMPER_ON UNSIGNED_16 PLC1
405913 B_DAMPER_PROVE UNSIGNED_16 PLC1
405914 B_OUTLET_TEMP SIGNED_16 PLC1
405915 B_INLET_TEMP SIGNED_16 PLC1
405916 B_STACK_TEMP SIGNED_16 PLC1
405917 B_CYCLE_TIME UNSIGNED_16 PLC1
405918 B_CYCLE_COUNT UNSIGNED_32 PLC1
405919 PLC1
405920 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405921 PLC1
405922 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405923 PLC1
405924 B_MBH_OUTPUT UNSIGNED_32 PLC1
405925 PLC1
405926-40
5949 Reserved PLC1
405950 B_EXISTING BOILER1
6UNSIGNED_16 PLC1
405951 B_ACTIVE UNSIGNED_16 PLC1
405952 B_ALARM UNSIGNED_16 PLC1
405953 B_CON_NON UNSIGNED_16 PLC1
405954 B_WINTER UNSIGNED_16 PLC1
405955 B_DHWP UNSIGNED_16 PLC1
405956 B_ON UNSIGNED_16 PLC1
405957 B_PUMP_EXISTING UNSIGNED_16 PLC1
405958 B_PUMP_ON UNSIGNED_16 PLC1
405959 B_VALVE_EXISTING UNSIGNED_16 PLC1
405960 B_VALVE_ON UNSIGNED_16 PLC1
405961 B_DAMPER_EXISTING UNSIGNED_16 PLC1
405962 B_DAMPER_ON UNSIGNED_16 PLC1
405963 B_DAMPER_PROVE UNSIGNED_16 PLC1
405964 B_OUTLET_TEMP SIGNED_16 PLC1
405965 B_INLET_TEMP SIGNED_16 PLC1
405966 B_STACK_TEMP SIGNED_16 PLC1
TPC-FI SoloNet O&M Page 65
405967 B_CYCLE_TIME UNSIGNED_16 PLC1
405968 B_CYCLE_COUNT UNSIGNED_32 PLC1
405969 PLC1
405970 B_HOURS_OF_OPERATION UNSIGNED_32 PLC1
405971 PLC1
405972 B_MBH_LOAD_ASSIGNMENT UNSIGNED_32 PLC1
405973 PLC1
405974 B_MBH_OUTPUT UNSIGNED_32 PLC1
405975 PLC1
405975-40
9999 Reserved PLC1
TPC-FI SoloNet O&M Page 66
Appendix C
TPC-FI SoloNet O&M Page 67
TPC-FI SoloNet O&M Page 68
GROUP Parameter Logging Type Sample Size
Design Inputs Supply Temp Hourly Average >= 10 samples/hour
Design Inputs Return Temp Hourly Average >= 10 samples/hour
Design Inputs Outdoor Air Temp Hourly Average >= 10 samples/hour
Design Inputs GPM Flow Hourly Average >= 10 samples/hour
Design Inputs Set Point Hourly Average >= 10 samples/hour
Design Inputs Display Load (Supply Return * GPM) Hourly Average >= 60 samples/hour
Heat Priority Event Driven On Delta
Heat Priority Event Driven On Delta
Operation in reset Event Driven On Delta
Operation in reset Event Driven On Delta
Heat Reset 3 (Reheat) Operation in reset Event Driven On Delta
Winter Priority Active / Inactive Event Driven On Delta
System Pumps Alarm Status Event Driven On Delta
System Pumps On/Off Status Event Driven On Delta
System Pumps Output Percentage (Modulation) Hourly Average >= 60 samples/hour
Zone Pump Alarm Status Event Driven On Delta
Zone Pump On/Off Status Event Driven On Delta
Zone Pump Output Percentage (Modulation) Hourly Average >= 60 samples/hour
Boiler Pump Alarm Status Event Driven On Delta
Boiler Pump On/Off Status Event Driven On Delta
Boiler Pump Output Percentage (Modulation) Hourly Average >= 60 samples/hour
Boilers Hours of Operation Event Driven To a minute
Boilers Alarm Status Event Driven On Delta
Boilers On/Off Status Event Driven On Delta
Boilers Output Percentage (Modulation) Hourly Average >= 60 samples/hour
Damper Alarm Status Event Driven On Delta
Winter Heat On Setpoint
NonCondensing Outdoor Setpoint
Heat Reset 1 (Condensign)
Heat Reset 2 (NonCondensing)
Notices of software licenses used in this product:
FreeRTOS(tm):
-------------
This product uses FreeRTOS.org, version 4.7.0. FreeRTOS is distributable under a modified version of
the GNU General Public License. Should you desire to obtain the version of FreeRTOS used in this
product, you may do so at http://www.thermodynamicprocesscontrol.com/software/oss. The full text
of the license governing the use of FreeRTOS.org may be found on the same page.
You may learn more about FreeRTOS.org from http://www.freertos.org.
FreeModbus:
------------
FreeModbus Libary: A portable Modbus implementation for Modbus ASCII/RTU.
Copyright (c) 2006 Christian Walter <wolti@sil.at>
All rights reserved.
Redistribution and use in source and binary forms, with or without
modification, are permitted provided that the following conditions
are met:
1. Redistributions of source code must retain the above copyright
notice, this list of conditions and the following disclaimer.
2. Redistributions in binary form must reproduce the above copyright
notice, this list of conditions and the following disclaimer in the
documentation and/or other materials provided with the distribution.
3. The name of the author may not be used to endorse or promote products
derived from this software without specific prior written permission.
THIS SOFTWARE IS PROVIDED BY THE AUTHOR ``AS IS'' AND ANY EXPRESS OR
IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES
OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED.
IN NO EVENT SHALL THE AUTHOR BE LIABLE FOR ANY DIRECT, INDIRECT,
INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING,
BUT
NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE,
DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY
THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT
(INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF
THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
Linux Kernel:
TPC-FI SoloNet O&M Page 69
---------------
The Linux kernel is used by this product. The kernel itself is
distributed under the GNU General Public License, Version 2. To obtain a copy of
the kernel source used in this product, please visit
http://www.thermodynamicprocesscontrol.com/software/oss.
Other Programs:
----------------
Other programs under the GPL or other open-source license terms may be distributed
with the product. To obtain the sources for these programs, please visit
http://www.thermodynamicprocesscontrol.com/software/oss.
Alternative source:
-------------------
If you prefer to obtain the sources for the open-source programs used by this product
by way of CD or DVD, you may do so for a cost of $9.99. Please contact Thermodynamic Process
Control for more details.
TPC-FI SoloNet O&M Page 70

Navigation menu