Standard Industrie COFACWCA CONTROL PANEL FOR AIRCHOC WIRELESS APPLICATION User Manual NOTCOFACW US H1

Standard Industrie CONTROL PANEL FOR AIRCHOC WIRELESS APPLICATION NOTCOFACW US H1

User Manual

NOTCOFACW-US.doc 1 December 6th, 2012       Produced on:   December 20th, 2012  By:  DESIGN OFFICE  Checked on:   By:  BOISLEUX.M  Signature:     TECHNICAL INSTRUCTIONS   Revision Level: H1  NOTCOFACW-US  Date: December 6th, 2012  HEAD OFFICE- Standard Industrie : 139-141 rue du Luxembourg-BP50207 59054            ROUBAIX CEDEX 1- FRANCE   +33 (0)3 20 28 32 32 / @ :  info@standard-industrie.com
 NOTCOFACW-US.doc 2 December 6th, 2012  1- PRINCIPLE OF AIRCHOC WIRELESS  Page 3   2- AIRCHOC WIRELESS TRANSMITTER INSTALLATION  Page 3   2-1          Control panel fixation Page 3 2-2 Antenna Connection  Page 3 2-3 Antenna Placement  Page 3 2-4  Control panel Presentation  Page 4 2-5  Control panel Electrical Hook-up  Page 5 2-51  Electrical Characteristics  Page 5 2-52  Environmental Characteristics  Page 6 2-53  Additional Exterior Characteristics  Page 6 2-54  Explanation of different symbol on the labels  Page 6          2-55  Switching device  Page 6 2-54  Control panel Circuit Board Operation  Page 6 2-56 Instructions  Page 6 2-57  Control panel circuit board operation  Page 7 2-58  Servo-control Hook-up  Page 7 2-59  Alarm, Cycle, and Fault Relay Output  Page 8 2-60  Changing fuses  Page 8  3-RECEIVER UNIT CHARACTERISTICS  Page 9    3-1  Receiver Unit Batteries  Page 9  3-2  Recycling  Page 9  3-3  Warranty  Page 9     4-WIRELESS RECEIVER UNIT START-UP  Page 10  5- CONTROL PANEL START-UP Page 12  6- MAIN MENU  Page 12        6-1           Menu Operation  Page 13 6-11       Display Menu  Page 13 6-12       Manu Discharge  Page 13 6-13       Erasure Menu  Page 14 6-13a   Fault Presence  Page 14 6-13b   Fault Deletion  Page 15 6-13c   General Fault Deletion  Page 15 6-13d   Airchoc Deletion  Page 15 6-13e   Sequence Deletion  Page 16 6-13f    Super Sequence Deletion  Page 16 6-13g   Factory Reset  Page 16 6-14       Airchoc Programming Menu  Page 17 6-14a   Receiver Unit MAC Address  Page 17 6-14b   Airchoc Registration   Page 18 6-14c   Counters  Page 19 6-14d   Reception Level between Control panel and Receiver Unit  Page 19 6-14e   Network Monitoring  Page 19 6-15       Sequence Programming Menu  Page 20 6-16       Super Sequence Programming Menu  Page 22 6-16a   Super Sequence Configuration Page 22 6-16b   Super Sequence Programming  Page 22 6-17       Access Code Management  Page 23 6-17a   Code Creation / Modification  Page 23   6-17b   Code Level  Page 23   6-17c   Code Table Initialization  Page 24        6-18        Language Setting Menu  Page 24 6-19       Control USB Key Menu  Page 24 6-20a   Save Program  Page 25 6-20b   Upload Program to Control panel  Page 25 6-20c   Update Control panel Version Page 26 6-21       Communication Test  Page 26  7-CHANGING RECEIVER UNIT BATTERIES  Pages 27 to 30 CONTENTS
 NOTCOFACW-US.doc 3 December 6th, 2012 1- Principle of Airchoc Wireless
 NOTCOFACW-US.doc 4 December 6th, 2012 2- AIRCHOC WIRELESS TRANSMITTER INSTALLATION  2-1. Control panel fixation  Attachment lugs are provided to mount the control panel on a wall.   2-2. Antenna Module Connection   NB. The antenna module is provided with 20 m of cable. If additional length is required, please contact us.  2-3. Antenna Module Placement   We suggest placing the antenna as high as possible in order to radiate towards the receiver unit and obtain better reception. Communication between the transmitter Control panel and the receiver units takes place by means of this antenna module. This antenna module is sealed and may be installed outdoors.   2-31 Wireless external antenna characteristics  Standard Industrie Reference : COFANTENNA  65Set of 4 brackets . Preserves the protection index . Possibility of vertical or horizontal mounting . kit consisting of 4 brackets + screws  brackets (internal dimensions) Screw the antenna Screw the antenna connector to the box presence of a label keyed A=385
 NOTCOFACW-US.doc 5 December 6th, 2012 2-4. Control panel Presentation    2-5. Control panel Electrical Hook-up   White terminal block Emergency stop button Start / Stop button Display LED indicators Keyboard USB socket Release to open the Control panel   The insulation of the conductors from the circuits with hazardous voltage and the other circuits need to be insulated by double/reinforced insulation for 300V outside and inside the equipment and to accessible parts
 NOTCOFACW-US.doc 6 December 6th, 2012 2-51. Control panel Electrical Characteristics  -Control panel universal supply voltage    120Vac -Frequency                                                 60 Hz -Consumption                                           15W Max -Protection, can withstand 105% of the initial power and the power source automatically cuts-off and turns back on. - If there is a power surge, the power source automatically cuts-off and turns back on after the repair. - RF transmission module - 915 MHz as per IEEE 802.15.4 -2003/2006  2-52. Environmental characteristics:  -  Protection Index:  IP66 IK 08  - Service temperature:  - Humidity : - Max altitude - Pollution degree Minimum: -10°C Maximum: +70°C no more than 80% e.g up to 2000 m 2  -  Material :          Polycarbonate UL    2-53. Additional exterior Characteristics : 2-54.Explanation of the different symbols on the labels :    Direct current                           Alternating current                2-55. Switching device :  The control panel is permanently connected  to building installation, the installer must provide a current isolation device, easy accessible to operator and marked as disconnecting device to use in case of intervention in the control panel.  Attention : it is forbidden to clean the control panel in the high-pressure water. The protection is impaired if equipment is used in a manner not specified by the manufacturer.  2-56.Instructions :  Changes or modifications not expressly approved by Standard Industrie could void the user's authority to operate the equipment.  This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can -  Operator interface:  - 4 line LCD backlit display of 20 characters each - 8-key keyboard - Indicator LED: - system (system operational) - fault (fault detected) - Front USB (software update and program upload) Earth  The user must disconnect the control panel before access to the fuse. - A connection to the earth of the control panel is required - Electric cable used for connecting have to be in accordance with the standard IEC 60320-1, 60227
 NOTCOFACW-US.doc 7 December 6th, 2012 radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: —Reorient or relocate the receiving antenna. —Increase the separation between the equipment and receiver. —Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. —Consult the dealer or an experienced radio/TV technician for help.  This portable equipment with it’s antenna complies with FCC’s radiation exposure limits set forth for an uncontrolled environment. To maintain compliance, follow the instructions below : 1.  This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter. 2.  Avoid direct contact to the antenna, or keep contact to a minimum while using this equipment.  2-57. Control panel Circuit Board Operation      2-58. Servo-control hook-up   There are 16 servo-control inputs named Ent1, Ent2, etc. Normally open (NO) or normally closed (NC) dry contacts may be connected to it. These contacts may come from various systems (selector switch, sensor, automation output...). When programming a sequence, a number may be assigned to the servo-control that will start the sequence. See page 20 A sequence may therefore be started by the selected servo-control input number. If you do not want a servo-control, you must select INACTIVE in the selection  Control panel Power Source Terminal Block 16 servo-control inputs  RS485 Alarm, Cycle, and Fault Relay Output Ent1  Ent2  Ent3  Ent4  Ent9 Ent10  Ent11 Ent12 Ent5  Ent6  Ent7  Ent8  Ent13 Ent14 Ent15 Ent16
 NOTCOFACW-US.doc 8 December 6th, 2012  2-59. Alarm, Cycle, and Fault Relay Output   Relays used by these outputs:  -1 contact (NO and NC) for the alarm (emergency stop output).  -2 NO contacts for Cycle (operational report output), Fault (fault output). -These outputs must be correctly configured based on the items connected to their terminals (sirens, flashing light, automation input...). An external power source is required for sirens, flashing lights...  The maximum switching current and voltage of Alarm, Cycle and fault relays Alarm : 6A-240 Vac, Cycle and fault relays : 8A-240 Vac     2-60. Changing fuses  Normally closed (NC) contact Normally open (NO) contact T: Working C: Common R: Rest  F1 F2  Fuse description Two identical fuses The user must disconnect the control panel before access to the fuse. The fuses cuts the phase of 110Vac/240Vac and 12VDC after power supply Meanwell
 NOTCOFACW-US.doc 9 December 6th, 2012 3- RECEIVER UNIT CHARACTERISTICS   Material  : ABS + Aluminum Dimensions  : 100 x 114 x 83 mm Weight: 195 g without batteries Supply voltage: 7.2V Service temperature: - 20 to +60°C Equipped with an 915 MHz RF module Standard Industrie reference: REWCASEV     3-1. Receiver Unit Batteries  You must use only our batteries,   Standard Industrie reference: BATACW  Voltage  : 7.2V-13Ah (2 x 3.6Vdc) Type    : Lithium-ion non rechargeable Service temperature: - 20 to +85°C Max. storage temperature: 30°C Weight    : 240 g for both  Recommendation   Do not recharge, short-circuit,  dispose of in fire,  expose to temperatures greater than 100°C,  immerse, or alter its shape. Any one of these actions may damage the battery, or cause it to combust or explode. Store in a dry place at constant temperature.  3-2. Device Recycling (environment)    At the end of the batteries’, receiver units’, or Control panel’s service life, you must not dispose of these produces with ordinary household waste. They must be disposed of at an electrical and electronic device recycling point. Comply with applicable regulations in your country.  3-3. Warranty  The warranty does not cover damage caused by external factors such as lightning, flooding, and fire. No warranty shall apply if the device was repaired or modified by the purchaser or if its serial number has been modified, removed, or rendered illegible. Comply with the instructions for use contained in the manual.
 NOTCOFACW-US.doc 10 December 6th, 2012 4- WIRELESS AIRCHOC RECEIVER UNIT START-UP  Use a flat screwdriver with a max. blade thickness of 0.5.                  Press on the connectors until you hear a click                     *The MAC address will be used when registering the Airchoc and for communications between the Control panel and the receiver unit CONNECT THE BATTERIES CLOSE THE COVER  3 Remove the screw Open the cover 1  2 Attach the battery connectors to the device. Direction is unimportant. The batteries must be identical.4 5 Find the MAC* address 4 characters
 NOTCOFACW-US.doc 11 December 6th, 2012                     The housing must abut the base  Ensure than the manual solenoid valve control is correctly positioned in relation to the oblong hole 6 7 8 ATTACH THE RECEIVER UNIT HOUSING TO THE SOLENOID VALVE TIGHTEN THE HOUSING TO THE SOLENOID VALVE Compress the cover until you are in front of the screw hole. The screw will tighten the housing through the solenoid valve 9
 NOTCOFACW-US.doc 12 December 6th, 2012   5- CONTROL PANEL START-UP            6- MAIN MENU   It has 10 menus accessible using the ▼ / ▲ keys.  Functions are accessed using the VALID key.  Access to all menus requires an access code, except for selecting the display, language, and communications test.  Generally: -  the  keys ▼   ▲ are used to select a line -  the  keys ◄   ► are used to select a field -  the  keys +   –  are used to modify a field - the VALID key is used to validate data and save - the MENU key is used to enter the menu and get out of an action without savingSTANDARD INDUSTRY Control panel Airchoc Soft version: 3.01Display  Control panel power on LED indicator Main Menu: Display Manu discharge Erasure Airchoc prog  Sequence prog Sup- sequence prog Code Management Language Setting Control USB key Communication test An access code must be entered to access these menus Explanation on page 23 EMERGENCY STOP TRIGGERED ORFaults Emergency Stop Unlock  by turning the button  +  press VALID Red LED ACCESS FUNCTION WITHOUT NETWORK CREATION OR TO DIRECTLY ACCESS THE MAIN MENU Simultaneously press  MENU and VALIDOR WAIT WHILE SEEKING RECEIVER UNITS STANDARD INDUSTRYControl panel Airchoc Receivers searchingSTANDARD INDUSTRY Control panel Airchoc Network Creation STANDARD INDUSTRYControl panel Airchoc Antenna FaultEnsure the antenna is correctly connected or check for a cable problem POWER-UP  On / Off button Green LED WIRELESS CONTROL PANEL OPERATION
 NOTCOFACW-US.doc 13 December 6th, 2012  6-1. Menu Operation    Display mode provides for viewing Airchoc program, sequence, and super sequence lines, as well as the counters and faults using the keys.        The manual firing menu provides for manually triggering an Airchoc whether it is active or inactive. This is used to check correct Airchoc operation               PRESS VALID AFTER MAKING YOUR Manu Discharge Airchoc  01       XXXX  Press VALIDEnsure there is no danger before firing Manual discharge AC In Progress Manu discharge menu  Code  Entry    :   0000 Enter Your Access Code6-11. MENU - DISPLAY 6-12. MENU – MANU DISCHARGE No. Name  T1  Config 01 XXXX      0.5s    Active Select an Airchoc that you previously registered in the Airchoc prog menu (see page 17) Scroll keys PRESS VALID AGAIN TO FIRE
 NOTCOFACW-US.doc 14 December 6th, 2012        6-13a FAULT PRESENCE   Display fault type:   : Transmission error : Receptor batt. 25%   : Solenoid valve cut   : Airchoc Maintenance     Only the 4 faults in bold will be saved: Each fault displayed will be dependent on an Airchoc and may be acknowledged one by one.   6-13b FAULT DELETION  Select the fault type using the ▼ / ▲ keys.    ERASURE choice :  Faults      Airchoc      Sequence Super - Sequences      Reset by default Display sub-menus Red LEDReceptor batt.   < 25%  Nr01   XXXX  Batt. ok Transmission error Nr01   XXXX   0 Fault Solenoid valve cut Nr01   XXXX  coil ok Airchoc Maintenance Nr01   XXXX  maint. ok Transmission error Nr01   XXXX     0 Fault Nr02   XXXX       Nb: 01 DELETE  PRESS  then Select the line to delete 6-13. MENU - ERASURE
 NOTCOFACW-US.doc 15 December 6th, 2012    Go to the menu  Only the last 50 faults are visible.  6-13d AIRCHOC DELETION        N  b   N  a  m  e     A  d  r e s s M a c  0  1   A  C  0  1         0 0 6 4          0  2   A  C  0  2         0 0 5 3          0  3   A  C  0  3         0 0 5 4           ERASURE OF  THE AIRCHOC Number  : 01   ? Valid Quit Select Valid ◄ key+ VALID Quit flashes PRESS ERASURE choice  :       Faults   Airchoc       Sequence Select the line Erase menu      Code Entry : XXXX Select the Airchoc to be deletedFaults :  Transmission error  Receptor batt.    25%  Solenoid Valve cut Delete all faults   Valid Quit Select the option with ◄   ► +  SIMULTANEOUSLY PRESS FOR 3S    6-13c GENERAL FAULT DELETION  ON
 NOTCOFACW-US.doc 16 December 6th, 2012 6-13e SEQUENCE DELETION     6-13f  SUPER SEQUENCE DELETION    6-13g  FACTORY RESET   ERASURE       choice :      Sequence      Super Sequence  Factory ResetFactory  Reset  Simultaneously press     to validate Number       Config   01        Active       02        InactiveERASURE       choice :   Sequence      Super Sequence      Factory Reset Select the line Select the Super sequence to delete ERASURE OF THE SUPER-SEQUENCE Number:   01  ? Valid  Quit Select the option with ◄   ►  +      Number       Config      01         Active  02         InactiveERASURE       choice :   Sequence      Super Sequence      Factory Reset Select the line Select the Sequence to deleteERASURE OF THE SEQUENCE Number:   02 ? Valid  Quit Select the option with ◄   ►  +
 NOTCOFACW-US.doc 17 December 6th, 2012        From the main menu, press the key until the Airchoc prog line flashes. Then press the VALID key in order to enter the menu. The Airchoc, receiver unit MAC address, and configuration lines are displayed.                            Key to use :                                     to increase                           Key to use :             to go to the next character                                           Press and hold :              to fast forward         Main Menu: Prog Airchoc      Prog Sequence      Prog Supsequence   Nb    Name          AdressMAC01     AC01          0030 02     AC02          0035 4 alphanumeric characters possible Physical Airchoc number 4 characters address MAC address 6-14. MENU -AIRCHOC PROGRAMMING6-14a Receiver Unit MAC Address
 NOTCOFACW-US.doc 18 December 6th, 2012   Go to the last line saved, press and hold the key      Go to the Airchoc to be deleted, press and hold the key         After selecting the Airchoc using the ▼ and ▲ keys, you may access the settings using the ◄   ► keys. 3 fields are accessible for each Airchoc:  The T1 field is 0.5 s by default.  The Config field is used to deactivate an Airchoc. If an Airchoc is in inactive mode and present in a sequence, the canon may not be triggered. It is inactive by default.  6-14b AIRCHOC REGISTRATION    After configuring the Airchocs, a communication test may be performed in order to ensure correct communications between the Control panel and the receiver units.        ADD AN AIRCHOC DELETE AN AIRCHOC CONFIGURING THE AIRCHOC AIRCHOC COMMUNICATION TEST Pressing MENU + VALID will register the Airchoc AIRCHOC Record validation No: Menu  Yes: Valid In the same menu, go to the Airchoc line to be tested Communication test   : Airchoc AC01  No Menu  Yes Valid PRESS VALID AIRCHOC Name  T1 (Pulse time)Configuration (active / inactive) Step no. Press the  key to accept N  b   N  a m e     T 1     C o n f i  g   0  1   A  C 0 1   0 . 5 s   A c t i v  e  > 0  2   A  C 0 2   0 . 5 s   A c t i v  e   0  3   A  C 0 3   0 . 5 s   I n a c t  i  v  N  b   N  a m e     T 1     C o n f  i  g   0  1   A  C 0 1 0 . 5 sAc t i  v  e  >
 NOTCOFACW-US.doc 19 December 6th, 2012    Display Various Counters       - Client counter (CustCount): number of Airchoc firings (may be reset).                                                    The counter increases every time it communicates with the receiver unit.    Simultaneously press VALID + ◄  - Counter (MaxClient) is an adjustable maintenance threshold. When the CptClient exceeds the MaxClient value a maintenance fault will be triggered. By default it is set to 0050000. The value may be increased or decreased from 50000 by 1000s with the keys  - STANDARD INDUSTRIE counter (Sindcount): The counter increases every time it communicates with the receiver unit. This counter may not be initialized. It is used for monitoring by our technical services.  5-14d RECEPTION LEVEL BETWEEN THE CONTROL PANEL ANTENNA MODULE AND THE RECEIVER UNIT    The Airchoc Signal Level is a means of checking reception quality between the Control panel antenna module and the receiver units. This value may range from 0, meaning no signal, to 28, meaning perfect signal quality. This value must be greater than 5 for the facility to operate correctly. A value less than 5 may cause communication faults.  6-14e NETWORK MONITORING  The presence or absence of the various components composing the network may be checked. Go to                 COUNTER RESET Nb  Name  Signal Level 01   AC01         20 02   AC02 03   AC03            Code required for AdressMac            State       0056           This      A       0063           Absent         A       0045           This              R       0002           This              TA= Airchoc R= Router T= Remote Control Nb  Name      CustCount 01   AC01       0000000 02   AC02       0000000 Nb  Name     Max Client 01   AC01       0050000 02   AC02       0000000 Nb  Name    Sindcount 01  AC01       0000000 02  AC02       0000000 Main Menu : DisplayDisplay choice :      Super Sequence      Faults      General NetworkLast tab 6-14c COUNTERS
 NOTCOFACW-US.doc 20 December 6th, 2012     Example of sequence programming   Programming a sequence From the main menu, press the ▼ key until the Prog Sequence line flashes. Then press VALID to begin programming. Always enter the access code to gain access to sequence configuration.    Go to the last sequence and press and hold ▼   Servo-control Assignment Move to the sequence of your choice and press the VALID key to select it.  Access the settings using the ▼   ▲ keys. 3 fields are accessible for each sequence: Change fields using the keys    The Config field activates or deactivates the sequence. If a sequence is deactivated, no servo-control is assigned to that sequence. If a sequence is in inactive mode and it is present in a super sequence, it may not be triggered.   The Servo-control is used to assign the corresponding servo-control to a dry contact On/Off controller input. 16 servo-controls are possible.(See page 7)   The state field provides for defining the type of servo-control assigned to the sequence: 5 statuses are possible: NO Reset, NC Reset, NO Pause, NC Pause, and Inactive. “Reset” reinitializes the cycle, “Pause” stops the cycle, “NO” and “NC” define the status type. “Inactive” deactivates the servo-control input.  Sequence      Config 01               Active 02          Inactive ADD A SEQUENCE CONFIGURE A SEQUENCE Sequence      Nr: 01 Config:   Active      Servo-control               : 01 State: NO RESET  Step 1 Press  To go to step 2 T1 AIRCHOC AC01 Step no.1 T2 Step no. 1=15s T1 AIRCHOC AC02 Step no. 2 T2 Step no. 2=30s T1 AIRCHOC AC03 Step no. 3 T2 Step no. 3=15s T1 AIRCHOC AC04 Step no. 4 T3 for Sequence 1 =1min. 6-15. MENU –SEQUENCE PROGRAMMING
 NOTCOFACW-US.doc 21 December 6th, 2012     Sequences are programmed line by line. Each line corresponds to a step in the sequence. For each step, an Airchoc – its address – must be assigned. Moreover, between 2 steps, a time (T2) must be indicated, except for the last sequence step which will have a time (T3) before the cycle repeats.    Press and hold      Key    Key     Key     Key     Press and hold        CREATING THE PROGRAM Step 2  Sq01      Airchoc  T2m:s      001         AC01      000 :15 002       AC02 T3 ( h:m:s )= 00 : 15 : 00Sq01      Airchoc  T2m:s      001         AC01      000 :15 002       AC02 T3 ( h:m:s )= 00 : 15 : 00Step no. in the Sequence Sequence No.  Time T2 Time T3 SELECT AN AIRCHOC CHANGE STEP GO TO SETTINGS CHANGE TIMES INCREASE QUICKLY LEAVE THE SEQUENCE Save the program VALIDATE THE PROGRAM  VALID Key MENU 2x INSERT A STEP 
 NOTCOFACW-US.doc 22 December 6th, 2012   Program creation:   Super sequences are programmed line by line. Each line corresponds to a step in the super sequence. For each step, a sequence must be assigned by number. Moreover, between 2 steps, there is a time (T3) corresponding to the T3 time programmed in the sequence. Lastly, the last sequence step has a time (T4) before the cycle repeats.            Example of super sequence programming:    6-16a SUPER SEQUENCE CONFIGURATION       Servo-control and status settings are the same as for the Sequence menu.  6-16b SUPER SEQUENCE PROGRAMMING  Use the same keys as for a sequence  After programming the various steps, you must set the T4 time. To do so move to the last line using the    key and then use the key   . Move to the T4 time and change the values using the keys   /     Step 1  SupSequence          Config 01 02 Select the Super-sequence to configure +  - VALIDATE THE PROGRAM  VALID Key MENU 2x SupSeq01 Sq      001   01   00:01:00     002 T4(h:m:s)  = 00:05:30Super-sequence no. Sequence no. Time T3 Super -Sequence    Nr 01 Config: Inactive       Servo-control              : 01 State : Reset NOPRESS VALID SEQUENCE  no.1 step no.1 SEQUENCE  no. 3 step no. 3 SEQUENCE  no. 2 step no. 2 T3 sequence no.1  T3 sequence no. 2 T4 for super-sequence 1 SupSeq01 Sq           002     02      00:01:00 T4 (h: m: s) = 00:05:30 6-16. MENU - SUPER SEQUENCE PROGRAMMING    Save the program
 NOTCOFACW-US.doc 23 December 6th, 2012    This menu is used to create, modify, or initialize access codes used to enter the various menus. To access this code management menu, you must enter code 2 (by default this code is 0000). We suggest you change this code the first time you use the Control panel.  6-17a CODE CREATION / MODIFICATION      Use the keys   to access the various codes or characters.  Use the keys                        to increase or decrease the digits.    OR    6-17b CODE LEVELS  Code 1:  this code provides access to manual Airchoc firing, the view menu, and                       language selection.  Code 2:  this code provides access to all menus and programming, allows resetting                      counters, except for the Standard Industrie counter. Fault deletion.  Code 3:  this code is exclusively reserved for Standard Industrie access.     Using this code a Standard Industrie technician has access to all Control                        panel functions and may reset the Standard Industrie counter. Code Management       Create - Modify InitializeVALID Key Config Password Code  1 :   0000 Code  2 :   0000 Code  3 :  xxxxMENU Key Quit without saving PRESS  VALID key MENU Save the code Menu selection 6-17. MENU-ACCESS CODE MANAGEMENT
 NOTCOFACW-US.doc 24 December 6th, 2012 6-17c CODE TABLE INITIALIZATION      From the main menu press the ▼ key until the Language setting line flashes. Then press VALID to save the language.  L  a  n  g  u  a  g  e   s  e  t   t  i n g          F  r  a  n  c  a  i  s                 E  n  g  l  i  s  h                  E  s  p  a  g  n  o  l                 D  e  u  t  s  c  h                  I  t  a  l  i  a  n  o                This menu is used to upload a new program or download a program from the Control panel with our “AIRCHOC TRANSFER SYSTEM” software.  Menu    USB Key       Enter code: XXXX Code Management      Create - Modify       InitializeVALID Key Reinitialize Completing the Code table Record No: Menu  Yes: Valid Simultaneously press  6-18  Menu - Language Setting 6-19  Menu – Control USB Key
 NOTCOFACW-US.doc 25 December 6th, 2012  6-20a SAVE PROGRAM  -Insert the key into the Control panel which has been turned on.   - Go to the menu USB Key on the Control panel   -  When you return to the main menu, remove the key. -   Insert the key in the PC where the “AIRCHOC TRANSFER SYSTEM” software is installed.        - Run the “Airchoc Transfer System” software - Select “Load” - The “Select” to find the location on the USB key (for example “removable disk (D:)”). - Then validate - The 3 boxes Airchoc – Sequences – Super Sequences are displayed.  The Control panel settings are present in these 3 tables.  Here, you can modify or add an Airchoc for example. Each time you press “modify,” “add,” or “delete” it is saved to the key!  6-20b UPLOADING PROGRAMS TO THE CONTROL PANEL    HANDLING Save
 NOTCOFACW-US.doc 26 December 6th, 2012   - Go to the menu USB Key on the Control panel - Select “Upload”  All the changes made are now in the Control panel.  6-20c UPDATING THE CONTROL PANEL VERSION           Using this menu, you may check the connection between the Control panel and the receiver units at any time.   The same functions as when starting-up the Control panel are available.     Main Menu:     Language Setting     Control USB Key   Communication Test Select the menu VALID Key TURN OFF THE CONTROL PANEL TURN THE CONTROL PANEL BACK ON STANDARD INDUSTRY Control  panel Airchoc Version soft : 3 :01 2 LEDs ON Updating the software does not erase existing program Control USB Key   Code Entry : XXXX     6.21- COMMUNICATION TEST
 NOTCOFACW-US.doc 27 December 6th, 2012 7- CHANGING RECEIVER UNIT BATTERIES  Use a flat screwdriver with a max. blade thickness of 0.5     If the Airchoc is hard to reach, remove the receiver unit from the solenoid valve        1 Unscrewing the M3x35 screw Disconnect the 2 connectors 3 2 REMOVE THE BATTERIES
 NOTCOFACW-US.doc 28 December 6th, 2012                                      BATTERY INSTRUCTIONS, REMINDER Do not recharge, to short circuit, do not throw into fire, to expose above 100°C,  to dump, to deform : one of these actions make damages, fire or explosion of the battery. To be stocked into dry area and stable temperature. INSTALLING NEW BATTERIES 4  5
 NOTCOFACW-US.doc 29 December 6th, 2012         CONNECTING THE CONNECTORS CLOSE THE COVER Press the connectors until you hear a click  6 7 ATTACH THE HOUSING TO THE SOLENOID VALVE
 NOTCOFACW-US.doc 30 December 6th, 2012                The housing must abut the base  Ensure than the manual solenoid valve control is correctly positioned in relation to the oblong hole 8 ATTACH THE HOUSING TO THE SOLENOID VALVE Press down on the cover until you are in front of the screw hole