 Commissioning a project  8.5 Commissioning an RFID tag Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  201 4. Press "Save ID". The ID is sent to the RFID tag and stored there. A check mark is set in the "Tag" list, if the configured tag ID is successfully written to the RFID tag.  NOTICE   Recording the ID of the RFID tag If you replace the RFID tag at a later date due to a defect, for example, you will always need the ID of the RFID tag. Therefore, record the ID of the RFID tag so that it is at hand at all times. For example, write it on the front of the RFID tag using a permanent marker.  5. Repeat steps 2 to 4 for all RDIF tags of this effective range. When all the RFID tags of an effective range have an ID, the selected effective range has a check mark in the "Effective range" list. 6. Repeat steps 1 to 5 for all effective ranges. The "Calculate" button is gray and only becomes black again, and thus enabled, when all RFID tags have successfully been assigned an ID. 7. Press "Calculate". The CRC checksum is displayed.  8. Record the checksum or enter it immediately in "Effective ranges (RIFD)" in the WinCC flexible editor. 9. Click "Exit" to close the dialog. Result You have assigned a unique identifier to all RFID tags and determined a checksum. Transfer the project with the added CRC checksum again to the HMI device. You can log onto a machine and operate the machine in fail-safe mode. See also Replacing an RFID tag (Page 202) PRELIMINARY II 1.7.2010
Commissioning a project   8.6 Replacing an RFID tag  Wireless Teach Pendant F IWLAN V2 202 Operating Instructions, 08/2010, A5E02453837-01 8.6 Replacing an RFID tag If it is not possible to log onto an effective range, the HMI device or RFID tag may be defective. This section describes the configuration work carried out after replacement of a defective RFID tag. Requirement  ●  The defective RFID tag has been replaced. ●  The ID of the defective RFID tag is available. ●  The project, in which the RFID tag has failed, is still on the HMI device. Procedure  Proceed as follows: 1. Switch on the HMI device. 2. Open the Control Panel. 3. Press the "RFID Config" icon. The following dialog appears:  4. Select the effective range ID in the "Effective range" selection box and the ID of the defective RFID tag in the "Tag" selection box. 5. Bring the HMI device into the effective range of the RFID tag. 6. Press "Save ID". The HMI device transmits the ID to the RFID tag. The new RFID tag has the ID of the previously used RFID tags. 7. Click "Exit" to close the dialog. 8. Close the Control Panel and start the project. 9. Log the HMI device onto a machine to check the new RFID tag. –  When the logon is successful, you can continue working in the project. –  If logon is not possible close the dialog and repeat steps 2 to 8. PRELIMINARY II 1.7.2010
 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  203 Commissioning the plant 99.1 Overview The acceptance of the plant involves the following:  ●  Safety-related project ●  Safety program ●  RFID tags with effective ranges 9.2 Acceptance of the plant All of the relevant application-specific standards and the procedure described in this section must be observed in the course of final acceptance of the plant.    Note This section provides a detailed description of the additional tasks required for the fail-safe operation of the HMI device. Read the detailed description provided in the "System Acceptance Test" section of the "S7 Distributed Safety, Configuring and Programming" manual when performing an acceptance procedure for the plant.  The acceptance of the plant involves the following tasks: ●  Configure the F-CPU and F-I/O ●  Create a safety program Requirement  ●  The hardware configuration has been created in HW Config. ●  The safety program has been created and generated. ●  A backup of the STEP 7 project has been created. Configuring the F-CPU and F-I/O  ●  Printing and archiving the hardware configuration. ●  Check the following parameters in the hardware configuration: –  Parameters of the F-CPU –  Parameters of the F-I/O This includes unique PROFIsafe addresses and additional PROFIsafe parameters. ●  Save the hardware configuration with the STEP 7 project. A detailed description is provided in the "Acceptance test for the configuration of the F-CPU and the F-I/O" section of the "S7 Distributed Safety, Configuring and Programming" manual. PRELIMINARY II 1.7.2010
Commissioning the plant   9.3 Diagnostics  Wireless Teach Pendant F IWLAN V2 204 Operating Instructions, 08/2010, A5E02453837-01 Acceptance of the safety program  ●  Print and archive the safety program. ●  Check the printed copy of the safety program for existence of the criteria specified in the "S7 Distributed Safety, Configuring and Programming" manual, section "Acceptance of a safety program." ●  Download the entire safety program to the F-CPU. ●  Test all functions of the safety program. A detailed description is provided in the "Acceptance test for the configuration of the F-CPU and the F-I/O" section of the "S7 Distributed Safety, Configuring and Programming" manual. See also Programming and operation manual "S7 Distributed Safety - Configuring and Programming" (http://support.automation.siemens.com/WW/view/en/22099875) 9.3 Diagnostics Use the diagnostics function to determine the following: ●  Does signal acquisition function without errors on the HMI device? ●  Does the safety-related module of the HMI device work properly? Diagnostic function of the HMI device in STEP 7  The HMI device provides diagnostics conforming to PROFINET IO standard IEC 61784-1, Ed1, CP 3/3 for standard application. The diagnostics function cannot be parameterized. The diagnostics are always enabled and information is provided automatically by the HMI device in STEP 7 in the event of an error. The diagnostic function also passes the "Communication error" message, if at all possible, for the safety-related component.  The communication between the HMI device as an input and output device, and the F-CPU and IO controller is disrupted. This situation can be caused, for example, by an incorrect PROFIsafe address or the lack of a wireless network. Reading diagnostics information  Open the module diagnostics in STEP 7 to determine the cause of the error. For additional information, refer to the online help for STEP 7. You also have the option of reading the diagnostic information using SFB 52 or SFB 54 in the standard user program. For additional information, refer to the "System and Standard Functions" reference manual. PRELIMINARY II 1.7.2010
 Commissioning the plant  9.3 Diagnostics Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  205 Diagnostic information for internal errors  All LEDs of the LED display go out when an internal error of the HMI device causes a failure. When a project is running on the HMI device, the following occurs: ●  The project is closed. ●  The following error code message is displayed on the HMI device: A severe problem has occurred!Date: 2010-04-30 09:18ErrorCode: 000 0008 00006 01506Please report this error code to your technical supporthttp://www.siemens.de/automation/support-request Procedure Proceed as follows: 1. Record the error number – see Error Code. 2. Switch off the HMI device. 3. Restart the HMI device. Contact Technical Support (http://support.automation.siemens.com/WW/llisapi.dll?aktprim=99&lang=en&referer=%2fWW%2f&func=cslib.csinfo2&siteid=csius&extranet=standard&viewreg=WW) if the error persists. Based on the error code, Technical Support can come to a conclusion about the type of internal error. PRELIMINARY II 1.7.2010
Commissioning the plant   9.3 Diagnostics  Wireless Teach Pendant F IWLAN V2 206 Operating Instructions, 08/2010, A5E02453837-01 Error code for discrepancy errors  The following table lists the error codes for discrepancy errors. You may be able to find a remedy for a discrepancy error yourself, depending on the situation. The first six digits of the error code are decisive for the correct identification of the error.  Error code  Error type  Remedy 000 008  Discrepancy error at the EMERGENCY STOP button Release the EMERGENCY STOP button. 000 014  Discrepancy error at the right enabling button, Panic switch position 000 015  Discrepancy error at the left enabling button, Panic switch position Make sure that the button does not become askew when it is pressed.   The terms "left" and "right" enabling buttons refer to your position facing the display of the HMI device. See also Discrepancy error during enabling (Page 258) PRELIMINARY II 1.7.2010
 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  207 Fail-safe operation 1010.1 Organizational measures The HMI device should only be operated in the plant with a main rechargeable battery or in the docking station. You must adhere to the organizational measures described in this section to ensure fail-safe operation of the HMI device.   WARNING  EMERGENCY STOP button out of service when HMI device is removed If the HMI device is not integrated in the safety program of the F-CPU, the EMERGENCY STOP button will be out of service. To avoid confusion between HMI devices with enabled and disabled EMERGENCY STOP buttons, only one integrated HMI device should be freely accessible. If an HMI device is not integrated and not in use, store the HMI device in a location with protected access.  Handling the HMI device during operation   CAUTION  Shutdown or global rampdown may occur with an empty main rechargeable battery An integrated HMI device with an empty main rechargeable battery triggers a communication error. This error results in the following reaction of the F-CPU:  When the HMI device is logged onto a machine – shutdown  When the HMI device is not logged onto a machine – global rampdown Check the charge of the main rechargeable battery at brief intervals using the "BAT" LED.   Note It is prohibited to leave the protection zone without an HMI device while the HMI device is logged onto a machine. Log off the HMI device from the machine before you leave the protection zone.  Pay attention to the LED display of the HMI device – see section "LED display (Page 85)". PRELIMINARY II 1.7.2010
Fail-safe operation   10.2 Switch-off behavior  Wireless Teach Pendant F IWLAN V2 208 Operating Instructions, 08/2010, A5E02453837-01 10.2 Switch-off behavior The shutdown reaction of the plant will vary according to cause and effect.  DANGER  Shutdown  The shutdown response described in the next sections is only triggered in the plant if the F-CPU has been programmed accordingly. Programming the F-CPU accordingly.  The following types of shutdown may occur depending on the operating state of the plant: ●  EMERGENCY STOP ●  Global rampdown ●  Local rampdown ●  Shutdown The following table shows the shutdown reaction depending on the operating state and the cause:   Cause of the shutdown Operating state EMERGENCY STOP button pressed Communication error HMI not integrated  –  – HMI device is in the protection zone EMERGENCY STOP  Shutdown HMI device is logged onto a machine  HMI device is outside the protection zone EMERGENCY STOP  Shutdown HMI integrated HMI device is logged off from the machine EMERGENCY STOP  Global rampdown See also  Terms for fail-safe operation (Page 32) PRELIMINARY II 1.7.2010
 Fail-safe operation  10.3 Integrating the HMI device Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  209 10.3 Integrating the HMI device During fail-safe operation, a safety program runs in the F-CPU. The HMI device is integrated into this safety program. The HMI device and F-CPU communicate via PROFINET IO.  When there is a project for a safety program on the HMI device, it is automatically integrated following the start of the project. The "SAFE" LED lights up to indicate that integration is complete. The EMERGENCY STOP button is enabled as soon as the HMI device is integrated. Requirement ●  WLAN ●  PROFIsafe safety-related bus profile, as of V2.0 ●  The plant has been accepted. ●  The loader is displayed on the HMI device. Procedure  Proceed as follows: 1. Start the project. PROFIsafe communication is established. While the connection is being established, the "Establishing secure connection" dialog is displayed with the following symbol.  The HMI device is integrated in the safety program of the F-CPU.  The "SAFE" LED lights up. The "Test enabling switch" dialog is displayed with the following symbol.  2. Fully press down both enabling buttons. The project start screen appears. PRELIMINARY II 1.7.2010
Fail-safe operation   10.4 Logging onto a machine  Wireless Teach Pendant F IWLAN V2 210 Operating Instructions, 08/2010, A5E02453837-01 10.4 Logging onto a machine The following figure shows the logon of an HMI device to a machine within a protection zone. 352),VDIH ①  Protection zone ②  Machine ③  HMI device ④  RFID tag 1 ⑤  Access monitoring Requirement ●  WLAN connection ●  RFID tags have been commissioned ●  The HMI device is integrated PRELIMINARY II 1.7.2010
 Fail-safe operation  10.4 Logging onto a machine Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  211 Procedure Proceed as follows: 1. Switch to the screen that contains the "Effective range name (RFID)" button labeled "Scan". 6FDQ 2. Bring the HMI device into the effective range of the RFID tag to which you want to log on, for example, "RFID Tag 1". The following table shows how to align the HMI device to the RFID tag.  Alignment      Logon  Possible  Not supported  Not supported 3. Press the button labeled "Scan". During the scan procedure, the button is yellow and displays the text, "Scanning...". 6FDQQLQJ The HMI device reads the ID from the RFID tag. After the data transfer, the name of the effective range will be briefly displayed on the "Effective range name (RFID)" operator control, for example, "Robot 1". 5RERW The "Effective range logon" dialog is then displayed with the following symbol.     Note As soon as the "Effective range logon" dialog is displayed, you can remove the HMI device from the effective range of the RFID tag.  4. Enter the ID of the effective range in the text box. The ID of the effective range is located on the label of the RFID tag. 5. Confirm the entry with "OK". The dialog closes.    Note A message appears if the ID of the effective range is incorrect. The corresponding dialog must be acknowledged. Repeat the logon to the effective range with a valid ID.  PRELIMINARY II 1.7.2010
Fail-safe operation   10.5 Logging off the machine  Wireless Teach Pendant F IWLAN V2 212 Operating Instructions, 08/2010, A5E02453837-01 The "Confirmation of logon" dialog is displayed with the following symbol.  6. Confirm the logon with the enabling button. The successful logon is indicated by the "RNG" LED on the HMI device. Result You are logged onto the machine and the machine can operate within the protection zone in fail-safe mode. The "Effective range name (RFID)" operator control is shown in green and labeled with the name of the effective range.  The following figure shows the "Effective range name (RFID)" object after logon to an effective range with the name "Robot 1". 5RERW 10.5 Logging off the machine You do not need to stand directly in front of the RFID tag to log off the machine you are operating in fail-safe mode. Procedure Proceed as follows: 1. Press the "Effective range name (RFID)" operator control. 5DQJHQDPH The "Effective range logoff" dialog is displayed with the following symbol.  2. Confirm the logoff from the machine with the "OK" button. The "RNG" LED goes out when the logoff is successfully completed. Result ●  The HMI device is logged off the machine. ●  The "Effective range name (RFID)" operator control is shown in white and labeled "Scan". 6FDQ PRELIMINARY II 1.7.2010
 Fail-safe operation  10.6 Removing the HMI device Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  213 10.6 Removing the HMI device You have the following options for removing the HMI device: ●  Close the project. ●  Press and hold the "ON/OFF" button for at least 4 seconds.  WARNING   EMERGENCY STOP button out of service when HMI device is removed If the HMI device is not integrated in the safety program of the F-CPU, the EMERGENCY STOP button will be out of service. To avoid confusion between HMI devices with enabled and disabled EMERGENCY STOP buttons, only one integrated HMI device should be freely accessible. If an HMI device is not integrated and not in use, store the HMI device in a location with protected access.  Requirement ●  The project must be started. ●  The HMI device is integrated into the safety program of the F-CPU. ●  The HMI device is not logged onto a machine. Procedure  Proceed as follows: 1. Close all open dialogs. 2. Close the project using the operator control designed for this purpose or press the "ON/OFF" button for more than 4 seconds. The "Start removal" dialog is displayed with the following symbol.  3. Use the "Yes" button to confirm the removal. The "Confirm removal" dialog opens with the following symbol.  4. Press an enabling button within 60 seconds. PRELIMINARY II 1.7.2010
Fail-safe operation   10.6 Removing the HMI device  Wireless Teach Pendant F IWLAN V2 214 Operating Instructions, 08/2010, A5E02453837-01  NOTICE   Global rampdown A global rampdown will occur, if you do not confirm the "Confirm removal" dialog within 60 seconds with the enabling button. Press an enabling button within 60 seconds.  The "Confirm removal" dialog closes. –  The "SAFE" LED on the HMI device goes out. –  PROFIsafe communication is terminated. –  The HMI device has been successfully removed from the safety program of the F-CPU. –  The project is closed. –  If you have pressed the ON/OFF" button during step 1, the HMI device switches off. PRELIMINARY II 1.7.2010
 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  215 Operating a project 1111.1 Starting the project   Note A project may demand operator actions that require in-depth knowledge of the specific plant on part of the operator. Proceed with caution, for example, when you use jog mode. Refer to your plant documentation for additional information.  Requirement The following requirements have to be met to start the project: ●  The plant has been accepted. ●  The main rechargeable battery is charged and inserted in the HMI device. If no main rechargeable battery is available, place the HMI device in the docking station. ●  The radio signal from the WLAN is sufficiently strong. ●  The PROFIsafe address is configured on the HMI device. ●  The data channel is configured on the HMI device. ●  The project has been transferred to the HMI device. PRELIMINARY II 1.7.2010
Operating a project   11.1 Starting the project  Wireless Teach Pendant F IWLAN V2 216 Operating Instructions, 08/2010, A5E02453837-01 Procedure Proceed as follows: 1. Press the "ON/OFF" button. The HMI device performs the following tasks: –  The HMI device starts. –  The "PWR" LED lights up. –  The "BAT" LED shows the remaining charge of the main rechargeable battery. –  The WLAN connection is established. The "COM" LED flashes while the connection is being established. The "COM" LED lights up when the WLAN connection is established. The project is started. –  PROFIsafe communication is established. The "Establishment of safety connection" dialog is displayed. The HMI device is integrated once the PROFIsafe connection has been successfully established. The "SAFE" LED lights up. The EMERGENCY STOP button is enabled. –  The "Test enabling button" dialog is displayed. 2. Fully press down both enabling buttons. Result The HMI device displays the start screen of the project.  Log onto a machine to enable the enabling button. See also Logging onto a machine (Page 210) PRELIMINARY II 1.7.2010
 Operating a project  11.2 Operator input options Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  217 11.2 Operator input options A project may demand operator actions that require in-depth knowledge of the specific plant on part of the operator. Proceed with caution, for example, when you use jog mode. Refer to your plant documentation for additional information.  CAUTION  Unintentional action  If you press several operator controls at once, you may trigger an unintentional action. Do not carry out several operations simultaneously.  When using the touch screen: Never press more than one operator control on the touch screen at once.  When using an external keyboard: Do not press more than two keys at once  Operator input options  Once the project is transferred to the HMI device, you can operate and monitor active processes during the process control phase. You have the following operating options: ●  Touch screen The operator controls shown in the configured screens are touch-sensitive. Touch objects are operated in the same way as mechanical keys. You trigger an operator control by pressing it with your finger. To double-click an operator control, you tap it twice in quick succession. ●  Membrane keyboard You can use the numeric area of the membrane keyboard to enter numeric values.    Note Read the section "Overview (Page 83)".  ●  USB keyboard  You can operate the Windows CE interface and Control Panel with an external keyboard in the exact same way as you do with the screen keyboard of the HMI device. ●  USB mouse  You can operate the Windows CE interface and Control Panel with an external mouse in the exact same way as you do with the touch screen of the HMI device. PRELIMINARY II 1.7.2010
Operating a project   11.2 Operator input options  Wireless Teach Pendant F IWLAN V2 218 Operating Instructions, 08/2010, A5E02453837-01 Feedback from an operator control  The HMI device provides optical feedback as soon as it detects that an operator controls has been selected. The operator control receives the focus and is selected. The selection is independent of any communication with a PLC. Therefore this selection does not indicate whether the relevant action is actually executed or not. The selection of an operator control can deviate from the standard. Refer to your plant documentation for additional information. The type of optical operation feedback depends on the operator control: ●  Button If the configuration engineer has configured a 3D effect, the button appears differently depending on the "Pressed" and "Not pressed" states: –  "Pressed" state  –  "Not pressed" state  The line width and color of the button are set during the configuration. ●  Invisible button By default, an invisible button is displayed as not pressed when it is selected. There is no optical operation feedback. The configuration engineer may, however, configure invisible buttons so that their outline appears as lines when they are pressed. This lines will remain visible until you press another operator control. ●  I/O field When you select an I/O field, the content of the I/O field is displayed against a colored background. With touch operation, a screen keyboard is displayed for the entering of values. PRELIMINARY II 1.7.2010
 Operating a project  11.3 Direct keys Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  219 11.3 Direct keys A direct key on the HMI device is a direct way to set a bit in the I/O area of the controller. A direct key enables an operation with a fast response time. Fast response time is essential, for example, for jogging mode.  NOTICE  Leaving the WLAN Note that leaving the WLAN area will cause the PROFINET IO device to fail and therefore result in a PLC stop. Determine suitable programming measures in the PLC, in order to prevent a PLC stop. Refer to your plant documentation for additional information. Pressing a direct key If you trigger an operator control with direct key functionality in an active project, the corresponding function is always executed, regardless of the screen display at the time. Avoid pressing a direct key unintentionally.   Note A direct key is enabled when both of the following conditions are satisfied:  The HMI device is in the WLAN with sufficient radio signal.  The HMI device is in "Offline" mode.  The following objects can be configured as a direct key:  ●  Button ●  Screen number ●  Illuminated pushbutton ●  Rotary switch    Note Direct keys result in additional basic load on the HMI device.  Additional information is available in the "WinCC flexible, Communication" system manual. PRELIMINARY II 1.7.2010
Operating a project   11.4 Setting the project language  Wireless Teach Pendant F IWLAN V2 220 Operating Instructions, 08/2010, A5E02453837-01 11.4 Setting the project language The HMI device supports multilingual projects. You must have configured a corresponding operator control which lets you change the language setting on the HMI device during runtime.  The project always starts with the language set in the previous session. Requirement  ●  The required language for the project must be available on the HMI device ●  The language switching function must be logically linked to a configured operator control such as a button Selecting a language You can change project languages at any time. Language-specific objects are immediately output to the screen in the new language when you switch languages. The following options are available for switching the language: ●  A configured operator control switches from one language to the next in a list ●  A configured operator control directly sets the desired language More detailed information is available in your plant documentation. 11.5 Operating the screen keyboard in the project If you do not use an external keyboard, use the screen keyboard to enter numeric and alphanumeric characters. As soon as you touch a text box, a numeric or alphanumeric screen keyboard is displayed, depending on the type of the text box. Display methods for the screen keyboard  You can change the type of display for the screen keyboard and move its position on the screen.  ●  Numerical screen keyboard  PRELIMINARY II 1.7.2010
 Operating a project   11.5 Operating the screen keyboard in the project Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  221 ●  Alphanumerical screen keyboard  The alphanumerical screen keyboard has the following levels. –  Normal level –  Shift level The shift level includes uppercase letters. –  Special character level    Note The ' character (button between ";" and "\") appears only when followed by a space. If the ' character is followed by a letter, then the result will be an accent, such as "á".  ●  Reduced screen keyboard     Note When the screen keyboard is open, PLC job 51, "Select screen" has no function. The screen keyboard display is independent of the configured project language. Language switching in the project has no influence on the alphanumerical screen keyboard. This means you cannot enter Cyrillic or Asian characters.  Procedure for moving the screen keyboard  Proceed as follows: 1. Touch the   symbol and move the screen keyboard on the touch screen. 2. When the desired position is reached, release the icon  . PRELIMINARY II 1.7.2010
Operating a project   11.5 Operating the screen keyboard in the project  Wireless Teach Pendant F IWLAN V2 222 Operating Instructions, 08/2010, A5E02453837-01 Procedure for adjusting the size of the screen keyboard    Note The   icon only appears on the screen keyboard if in the "Siemens HMI InputPanel" dialog you have selected the "Show Resize button" check box.  Proceed as follows: 1. Touch the   symbol and drag the screen keyboard to the appropriate size. 2. When the size you want is reached, release contact with the   icon. Changing the display of the screen keyboard   Key  Function  Switching between the numerical and alphanumerical keyboard  Switching between the normal level and Shift level of the alphanumerical screen keyboard  Switchover to special characters  Switching from full display to reduced display  Switching from reduced display to full display  Closing of reduced display of the screen keyboard Entering data   Key  Function  Delete character left of cursor  Delete character right of cursor  Confirm entry and close the screen keyboard  Cancel input   PRELIMINARY II 1.7.2010
 Operating a project   11.5 Operating the screen keyboard in the project Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  223   Note Data input - numerical text box  Hexadecimal values When you enter a value in hexadecimal format, the alphanumerical screen keyboard opens.  Decimal places The configuration engineer can define the number of decimal places for a numerical text box. The number of decimal places is checked when you enter a value in this type of I/O field. –  Decimal places in excess of the limit are ignored. –  Empty decimal places are filled with "0".  Limits A tag can be configured with limits. If you enter a value outside these limits, it will be rejected. If an alarm view is configured, a system event is triggered and the original value is displayed again.  Data input – date and time When entering the date and time, note that their format is determined by the configured project language.  Opening the Windows CE taskbar You open the Windows CE taskbar with the   key. Displaying infotext  The configuration engineer uses infotext to provide additional information and operating instructions. There may be infotext for HMI screens and operator controls in the project. The infotext for an I/O field may contain, for example, information on the value to be entered.  The screen keyboard appears on the HMI device touch screen when you touch an operator control that requires input. If an infotext was configured for the current operator control, call up the infotext with the   button. If no infotext is available for the current operator control, the infotext for the current HMI screen will be displayed. PRELIMINARY II 1.7.2010
Operating a project   11.6 Device-specific displays  Wireless Teach Pendant F IWLAN V2 224 Operating Instructions, 08/2010, A5E02453837-01   Note If an infotext was configured for the current control object as well as the current HMI screen, you can switch between both infotexts by touching the infotext window.  Close the infotext window with the   button. Depending on the project, infotext can also be called by an operator control configured for this purpose. For additional information, refer to the online help of WinCC flexible. 11.6 Device-specific displays 11.6.1 Overview This section describes the device-specific WinCC flexible objects, which you can use in a project for the Wireless Teach Pendant F IWLAN. For a full description of all WinCC flexible objects, refer to the online help of WinCC flexible.  11.6.2 Showing the battery charge The "Battery" object indicates the remaining charge of the main rechargeable battery.  Charge the main rechargeable battery in time or replace it. Read the information provided in section "Replacing and charging the main rechargeable battery (Page 72)". The amount of charge for the main rechargeable battery is shown by the "Battery" object as follows:  Icon  Color  Meaning   Charge level  Green  The main rechargeable battery is sufficiently charged. > 20 %  Yellow  The charge is low. The main rechargeable battery must be charged or replaced. 6% to 20 %  Red  The charge is very low. The main rechargeable battery must be charged or replaced. < 6 % See also  Displaying the charge status of the batteries (Page 138) PRELIMINARY II 1.7.2010
 Operating a project  11.6 Device-specific displays Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  225 11.6.3 Displaying WLAN quality The "WLAN quality" object indicates the signal strength of the wireless network at the location of the HMI device. The HMI device measures the signal strength and depicts it with the "WLAN quality" object.  The signal strength of wireless network is indicated by the "WLAN quality" object as follows:  Icon  Meaning   Signal strength  No wireless connection  No signal  Very poor wireless connection  ≤ 20%   Poor wireless connection  ≤ 40% > 20%   Wireless connection OK  ≤ 60% > 40%   Good wireless connection  ≤ 80% > 60%   Very good wireless connection  > 80% PRELIMINARY II 1.7.2010
Operating a project   11.7 Project security  Wireless Teach Pendant F IWLAN V2 226 Operating Instructions, 08/2010, A5E02453837-01 11.6.4 Displaying the "Effective range name (RFID)" object The "Effective range name (RFID)" object is only available for an HMI device of the RFID tag system. The "Effective range name (RFID)" object displays the following information:  ●  Logon status ●  "Scan", "Scanning..." or name of the effective range associated with the machine on which the HMI device is logged on The "Effective range name (RFID)" object can show the following operating states:  Icon  Operating state  Logon 6FDQ The HMI device is not logged onto a machine. The enabling button is not enabled. It is not possible to log onto a machine. To log onto a machine, the user must press the operator control and search for effective ranges. 6FDQQLQJ The user has pressed the operator control to search for effective ranges. The HMI device searches for an effective range. The enabling button is not enabled. Logon can only take place when the HMI device has detected an effective range. 5RERW The HMI device has detected the effective range, "Robot 1". The logon to the machine associated with the "Robot 1" effective range is possible. 5RERW The user is logged onto the machine associated with the "Robot 1" effective range. The enabling button is enabled. – 11.7 Project security 11.7.1 Overview Design of the security system  The configuration engineer can protect the operation of a project by implementing a security system. The security system is based on authorizations, user groups and users. If operator controls protected by a password are pressed, the HMI device first requests that you log on. A logon screen is displayed in which you enter your user name and password. After logging on, you can press the operator controls for which you have the necessary authorizations. The logon dialog can be set up by the configuration engineer via an individual operator control. Similarly, an operator control can be configured for logoff. After logging off, objects with password protection can no longer be operated – you need to log on again. Refer to your plant documentation for additional information. PRELIMINARY II 1.7.2010
 Operating a project  11.7 Project security Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  227 Central user administration using SIMATIC Logon  Users, user groups and authorizations can be stored on a central server. If user administration cannot contact the server, an error message is displayed. If this is the case, you can only log on locally. More detailed information is available in your plant documentation. The operation of SIMATIC Logon differs as follows: ●  The simple user display is not supported ●  Users cannot be deleted ●  You cannot change your logout time ●  When changing the password, you must enter it twice for security reasons ●  The domain name is also indicated in the "User" field User groups and authorizations  Project-specific user groups are created by the configuration engineer. The "Administrators" and "PLC User" groups are included in all projects by default. User groups are assigned authorizations. Authorization required for an operation is specifically defined for each individual object and function in the project. Users and passwords  Each user is assigned to exactly one user group.  The following persons are allowed to create users and assign them passwords: ●  The configuration engineer during configuration ●  The administrator on the HMI device ●  A user with user management authorization on the HMI device Irrespective of the user group, each user is allowed to change his own password. Logoff times  A logoff time is specified in the system for each user. If the time between any two user actions, such as entering a value or changing screens, exceeds this logoff time, the user is automatically logged off. The user must then log on again to continue to operate objects assigned password protection. PRELIMINARY II 1.7.2010
Operating a project   11.7 Project security  Wireless Teach Pendant F IWLAN V2 228 Operating Instructions, 08/2010, A5E02453837-01 Backup and restore    Note Backup and restore is not available to central user administration with SIMATIC Logon.  The user data is encrypted and saved on the HMI device to protect it from loss due to power failure. The users, passwords, group assignments and logoff times set up on the HMI device can be backed up and restored. This prevents you having to enter all of the data again on another HMI device.   NOTICE  The currently valid user data is overwritten in the following cases:  Depending on the transfer settings, when the project is transferred again  Upon restore of a backed-up project  Upon import of the user administration via an operator control. More detailed information is available in your plant documentation. The retransferred or restored user data and passwords are valid with immediate effect.  Number of characters for user, password and user view    Number of characters Length of user name, maximum  40 Length of password, minimum  3 Length of password, maximum  24 Entries in user view, maximum  50 11.7.2 User View The user view is used to show user accounts configured on the HMI device.  ●  If you are an administrator or a user with administrator rights, you can see all user accounts configured on the HMI device in the user view. ●  If you are a user without user management rights, you can only see your personal user account. The authorizations of a user after logging on depends on the user group to which the user belongs. More detailed information is available in your plant documentation. A simple or extended user view can be configured in the project. The two user views offer the same functions. The presentation of information differs. PRELIMINARY II 1.7.2010
 Operating a project  11.7 Project security Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  229 Simple user view  If you are not logged onto the HMI device, the only entry contained in the simple user view is "<ENTER>". If you are logged onto the HMI device, the simple user view only displays the user name and user group.  Extended user view  The extended user view displays information about the users.  The extended user view contains the following columns: ●  Users ●  Password ●  Group ●  Logoff time PRELIMINARY II 1.7.2010
Operating a project   11.7 Project security  Wireless Teach Pendant F IWLAN V2 230 Operating Instructions, 08/2010, A5E02453837-01 11.7.3 User logon Use the logon dialog of the HMI device to log onto the security system. Enter your user name and password in the logon dialog.  The logon dialog opens in the following cases: ●  You press an operator control with password protection ●  You press an operator control that was configured for displaying the logon dialog ●  Select the "<ENTER>" entry in the simple user view ●  Select a blank entry in the extended user view ●  The logon dialog will be automatically displayed when the project is started, depending on the configuration More detailed information is available in your plant documentation. Requirement  ●  The logon dialog is open. Procedure Proceed as follows: 1. Enter the user name and password. Touch the corresponding text box. The alphanumerical screen keyboard is displayed.     Note The user name is not case-sensitive.  The password is case-sensitive.   2. Select "OK" to confirm logon. Result  After successful logon to the security system, you can execute password-protected functions on the HMI device for which you have authorizations. If you enter a wrong password, an error message is displayed when an alarm window has been configured.  PRELIMINARY II 1.7.2010
 Operating a project  11.7 Project security Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  231 11.7.4 User logoff Requirement  ●  You have logged into the security system of the HMI device. Procedure You have the following options for logging off: ●  Press an operator control that is configured for logging off the security system. ●  If you do not operate a project and exceed the logoff time, your user account will be locked. Your user account will be automatically logged off if you enter an incorrect password. Result You are no longer logged onto the project. In order to use an operator control in the security system, you need to log on again. 11.7.5 Creating users You create a user with both the simple and enhanced user display. Requirement  ●  A configured screen with user display is shown. ●  You have user management authorization or you are the administrator.    Note The following characters are prohibited in passwords:  Blank  Special characters * ? . % / \ ' "  Procedure – Creating a user in the simple user view Proceed as follows: 1. Touch the "<New User>" entry in the user view. PRELIMINARY II 1.7.2010
Operating a project   11.7 Project security  Wireless Teach Pendant F IWLAN V2 232 Operating Instructions, 08/2010, A5E02453837-01 The following dialog appears:  2. Enter the desired user name and password. Touch the corresponding text box. The alphanumerical screen keyboard is displayed. 3. Touch the "OK" button. The following dialog appears:  4. Assign the user to a group. In order to do so, open the "Group" drop down list box by means of the   button. Select  and   to scroll in the drop down list box. 5. Touch the required entry in the drop down list box. The selected entry is then accepted as input. 6. Touch the text box "Logoff time". The screen keyboard is displayed. 7. Enter a value between 0 and 60 for the logoff time in minutes. The value 0 stands for "no automatic logoff." 8. Touch the "OK" button to confirm your entries. Procedure – Creating a user in the extended user view Proceed as follows: 1. Double-click the desired field in the blank line of the user view. The screen keyboard is displayed. 2. Enter the respective user data in the field: –  Assign the user to one of the groups from the drop down list box. –  Enter a value between 0 and 60 for the logoff time in minutes. The value 0 stands for "no automatic logoff." Result  The new user is created. PRELIMINARY II 1.7.2010
 Operating a project  11.7 Project security Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  233 11.7.6 Changing user data You have opened a screen with a user view. The data you are allowed to change depends on your authorization: Requirement   ●  You are an administrator or a user with user management authorization. In these cases you are allowed to change the data for all the users on the HMI device in the user view: –  User name –  Group assignment –  Password –  Logoff time ●  You are a user without user management authorization. In this case you are only allowed to change your personal user data: –  Password –  Logoff time, if configured    Note You can only change the logoff time and password for the "Admin" user. You can only change the logoff time for the "PLC_User". This user is used for logging on via the PLC  Procedure The procedure applies to simple and extended user view alike. Proceed as follows: 1. In the user view, touch the user whose user data you want to change 2. When entering the data, use exactly the same procedure as for creating a user Result The user data for the user is changed. PRELIMINARY II 1.7.2010
Operating a project   11.7 Project security  Wireless Teach Pendant F IWLAN V2 234 Operating Instructions, 08/2010, A5E02453837-01 11.7.7 Deleting users Requirement  ●  You have opened a screen with a user view. ●  You are an administrator or you have permission for user management. Procedure   Note The "Admin" and "PLC_User" users exist by default. You cannot delete these users.  1. Delete the entered user name. Result The affected user can no longer use the operator controls with permission. PRELIMINARY II 1.7.2010
 Operating a project   11.8 Error cases in the project operation Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  235 11.8 Error cases in the project operation During fail-safe operation, you must be aware that the following error cases may arise: ●  Leaving an HMI device logged onto a machine  CAUTION   Shutdown possible If the HMI device is in a state where it is constantly ready for operation, the main rechargeable battery will lose its charge. A discharged main rechargeable battery causes communication failure. The F-CPU initiates a shutdown. If you do not need the HMI device:  Log off the HMI device from the machine.  Close the active project.  Switch off the HMI device or place it in the docking station.  ●  Internal error  If an internal error occurs on the HMI device, the "SAFE" and "RNG" LEDs go out. and the project is terminated immediately. The HMI device displays the error code message – see section "Diagnostics (Page 204)".  Safety functions are no longer available. Contact the SIEMENS hotline. ●  Communication error If a communication error occurs on the HMI device, the "SAFE" LED goes out. Safety functions are no longer available. The following situations can occur with communication errors: –  When the HMI device is logged onto a machine: The F-CPU initiates a shutdown. The F-CPU stops the plant unit associated with the machine. –  When the HMI device is not logged onto a machine: The F-CPU initiates a global rampdown. –  If communication is reestablished within 60 seconds: The EMERGENCY STOP button is enabled again. The "SAFE" LED lights up again. Acknowledge the communication error. The "RNG" LED lights up when the HMI device is logged onto a machine. –  If communication remains interrupted for more than 60 seconds: The HMI device terminates the project. The "RNG" LED lights up when the HMI device is logged on to a machine. PRELIMINARY II 1.7.2010
Operating a project   11.9 Closing the project  Wireless Teach Pendant F IWLAN V2 236 Operating Instructions, 08/2010, A5E02453837-01 11.9 Closing the project The procedure for closing the active project is identical to the procedure for removing the HMI device. See also Removing the HMI device (Page 213) PRELIMINARY II 1.7.2010
 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  237 Service and maintenance 1212.1 Maintenance and care Read sections "Safety-related operator controls (Page 88)" and "Safety instructions (Page 72)" for information on service and maintenance. Scope of maintenance  The HMI device is designed for maintenance-free operation. Remember to include accessories and peripheral equipment in the maintenance. The scope of maintenance includes: Function test Perform an annual function test for the enabling button and EMERGENCY STOP button. Proceed as follows: 1. Switch on the HMI device. 2. Press both enabling buttons when the "Test Enabling Button" dialog is shown. 3. Press the EMERGENCY STOP button. Storing the main rechargeable battery A lithium-ion rechargeable battery loses more than 50% of its charge capacity within three years . Store rechargeable batteries at 40 to 60% of their capacity to ensure optimal service life. Manufacturers recommend storage at 15° C – which is optimal for aging and self-discharge. Charge the battery every six months to 40 to 60% of its charge capacity. Scope of maintenance  The scope of maintenance includes: ●  Cleaning the touch screen ●  Cleaning the membrane keypad PRELIMINARY II 1.7.2010
Service and maintenance   12.2 Replacing the rechargeable buffer battery  Wireless Teach Pendant F IWLAN V2 238 Operating Instructions, 08/2010, A5E02453837-01 Procedure  CAUTION  Damage possible The use of compressed air, steam cleaners or aggressive solutions or scouring agents will damage the HMI device. Use a cleaning cloth dampened with a cleaning agent to clean the equipment. Only use water with a little liquid soap or a screen cleaning solution.  Proceed as follows: 1. Switch off the HMI device. 2. Spray the cleaning solution onto a cleaning cloth. Do not spray directly onto the HMI device. 3. Clean the HMI device. When cleaning the display, wipe inwards from the edge of screen.  12.2 Replacing the rechargeable buffer battery The capacity of the rechargeable buffer battery is reduced by age. After about five years, the rechargeable buffer battery needs to be replaced. This section describes how to replace the rechargeable buffer battery. Procedure   Note Read sections "Safety instructions (Page 66)", "Opening and closing the terminal compartment (Page 67)" and "Safety instructions (Page 72)".  &RQQHFWLQJFDEOH(QFORVXUH5HFKDUJHDEOHEXIIHUEDWWHU\&RQQHFWRUV PRELIMINARY II 1.7.2010
 Service and maintenance  12.3 Spare parts and repairs Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  239 Proceed as follows: 1. Remove the enclosure. The enclosure is not needed for installation. 2. Open the connection compartment. 3. Pull out the connector. 4. Slide the rechargeable buffer battery out of the guide and put it down. 5. Insert the new rechargeable buffer battery, as shown in the following illustration. 5HFKDUJHDEOHEXIIHUEDWWHU\&RQQHFWLQJFDEOH3OXJDQGVRFNHW3ULQWHGFLUFXLWERDUG 6. Connect the plug. 7. Position the cable so that it cannot be pinched when you close the connection compartment. 8. Close the connection compartment. 12.3 Spare parts and repairs If the unit needs to be repaired, ship the HMI device to the Return Center in Fürth. The address is: Siemens AG Industry Sector Returns Center Siemensstr. 2 90766 Fürth Germany You can find more detailed information on the Internet at Spare parts and repairs (http://support.automation.siemens.com/WW/view/en/16611927).  PRELIMINARY II 1.7.2010
Service and maintenance   12.3 Spare parts and repairs  Wireless Teach Pendant F IWLAN V2 240 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010
 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  241 Technical specifications 1313.1 Dimension drawings 13.1.1 Wireless Teach Pendant F IWLAN ssss$OOGLPHQVLRQVLQPP  PRELIMINARY II 1.7.2010
Technical specifications   13.1 Dimension drawings  Wireless Teach Pendant F IWLAN V2 242 Operating Instructions, 08/2010, A5E02453837-01 13.1.2 Docking station r$OOGLPHQVLRQVLQPP  PRELIMINARY II 1.7.2010
 Technical specifications  13.1 Dimension drawings Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  243 13.1.3 RFID tag Fixing pocket  $OOGLPHQVLRQVLQPP Spacer  $OOH$QJDEHQLQPP You can additional illustrations on the Internet at Image database (http://www.automation.siemens.com/bilddb/index.aspx?att14s=35). PRELIMINARY II 1.7.2010
Technical specifications   13.2 Specifications  Wireless Teach Pendant F IWLAN V2 244 Operating Instructions, 08/2010, A5E02453837-01 13.2 Specifications 13.2.1 Wireless Teach Pendant F IWLAN V2 General information   Weight with battery, without packaging  Approx. 2 kg Drop height with main rechargeable battery, max.  0.5 m Buffer time of internal clock with battery inserted  Approx. 4 days Display   Type  Color TFT LC display Display area, active  132.5 mm x 99.5 mm Resolution  640 x 480 pixels Colors, displayable  65536 colors Brightness control  Yes Backlighting Half Brightness Life Time, typical CCFL 50000 h Pixel error class according to DIN EN ISO 13406-2 II Input unit   Touch screen  Analog, resistive Membrane keyboard  1 Rotary switch  1, with 2 positions Illuminated pushbutton  1 EMERGENCY STOP button  1 Enabling button  2 Memory   Application memory  6 MB SD memory card  2 GB PRELIMINARY II 1.7.2010
 Technical specifications  13.2 Specifications Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  245 Ports   2 x USB   USB host; conforms to USB standard 1.1 Supports low-speed and full-speed USB devices.  Current load per port, max. 100 mA 1 x WLAN  For PROFINET WLAN 1 x RJ45  For LAN WLAN antenna   Antenna type  Dual port patch antenna Polarization  Vertical and horizontal Antenna gain in principle ray direction, max.  2 dBi Impedance  50 Ω Fail-safe operation    Note The safety characteristics in the specifications apply for a proof-test interval of 10 years and a mean repair time of 8 hours.    In accordance with IEC 61508 Hardware architecture  Redundant 1oo2 Hardware error tolerance  1 Safe failure fraction  99.5 % Diagnostic test interval  10 ms Request rate  High demand mode High demand (PFH – probability of a dangerous failure per hour) 8.60e–11h–1 Safety class, maximum achievable (SIL)  3 Useful life  10 years   According to ISO 13849-1 Mean time to failure (MTTFd)  1516 years Meantime to Restoration (MTTR)  8 h Diagnostic coverage  99 % Performance level  e Safety category  4  PRELIMINARY II 1.7.2010
Technical specifications   13.2 Specifications  Wireless Teach Pendant F IWLAN V2 246 Operating Instructions, 08/2010, A5E02453837-01  Other safety-related characteristic values Acknowledgement time  40 ms Response time with no fault, max.  25 ms Discrepancy time – EMERGENCY STOP  500 ms Discrepancy time – enabling button  "Enabling" position  "Panic" position  2 sec 1 sec 13.2.2 Interface description USB  The figure below shows the pin assignment of the USB interface.   Pin  Assignment 1  +5 VDC, out (max. 100 mA) 2  USB-DN 3  USB-DP 4  GND RJ45  The figure below shows the pin assignment of the RJ45 interface.   Pin  Assignment 1  TD+ 2  TD– 3  RD+ 4  n. c. 5  n. c. 6  RD– 7  ICD+ 8  ICD– PRELIMINARY II 1.7.2010
 Technical specifications  13.2 Specifications Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  247 WLAN  Operation of a wireless interface in the frequency bands 2.4 GHz and 5 GHz. The wireless interface is compatible with the following standards: ●  IEEE 802.11a ●  IEEE 802.11h ●  IEEE 802.11b ●  IEEE 802.11g Receiver sensitivity  WLAN standard  Data transfer rate  Receiver sensitivity IEEE 802.11a/h  54 Mbps 48 Mbps 36 Mbps 24 Mbps 18 Mbps 12 Mbps 9 Mbps 6 Mbps -74 dBm -75 dBm -80 dBm -83 dBm -86 dBm -88 dBm -89 dBm -90 dBm IEEE 802.11g  54 Mbps 48 Mbps 36 Mbps 24 Mbps 18 Mbps 12 Mbps 9 Mbps 6 Mbps -76 dBm -77 dBm -82 dBm -85 dBm -88 dBm -91 dBm -92 dBm -93 dBm IEEE 802.11b  11 Mbps 5.5 Mbps 2 Mbps 1 Mbps -90 dBm -92 dBm -94 dBm -98 dBm PRELIMINARY II 1.7.2010
Technical specifications   13.2 Specifications  Wireless Teach Pendant F IWLAN V2 248 Operating Instructions, 08/2010, A5E02453837-01 Transmission power  WLAN standard  Data transfer rate  Receiver sensitivity IEEE 802.11a/h (5.18 ∼ 5.7 GHz) 54 Mbps 48 Mbps 36 Mbps 6-24 Mbps 13.5 dBm 15 dBm 16 dBm 17 dBm IEEE 802.11a/h (4.92 ∼ 5.16 GHz) (5.745 ∼ 5.825 GHz) 54 Mbps 48 Mbps 36 Mbps 6-24 Mbps 11.5 dBm 13 dBm 14 dBm 15 dBm IEEE 802.11g (2.412 ∼ 2.484 GHz) 54 Mbps 48 Mbps 36 Mbps 6-24 Mbps 16 dBm 17 dBm 17 dBm 17 dBm IEEE 802.11b  11 Mbps 5.5 Mbps 2 Mbps 1 Mbps 20 dBm 20 dBm 20 dBm 20 dBm 13.2.3 Rechargeable batteries  Main rechargeable battery    Type  Lithium ion accumulator Operation time in normal mode  Approx. 4 h Operation time in stand-by mode  Approx. 15 days Charging cycles  500 Charging time  Approx. 4 h 1)   Rechargeable buffer battery    Type  Lithium ion accumulator Bridging time  20 sec Charging cycles  500   1)  See section Charging the main rechargeable battery (Page 75), Maintenance and care (Page 237) PRELIMINARY II 1.7.2010
 Technical specifications  13.2 Specifications Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  249 13.2.4 Docking station  Weight without packing  Approx. 1.1 kg Power supply   Nominal voltage  +24 VDC via external power supply Transients, maximum permitted  35 V (500 ms) Time between two transients, minimum  50 s Power consumption with Wireless Teach Pendant F IWLAN  Typical  Constant current, maximum  Power on current surge I2t   Approx. 1.5 A  Approx. 1.8 A  Approx. 1.7 A2s Fuse, internal  Electronic 13.2.5 Charger  Weight without packing  Approx. 1.1 kg Power supply   Nominal voltage  +24 VDC via external power supply unit Transients, maximum permitted  35 V (500 ms) Time between two transients, minimum  50 sec Power consumption with Wireless Teach Pendant F IWLAN  Typical  Constant current, maximum  Power on current surge I2t   Approx. 1.5 A  Approx. 1.8 A  Approx. 1.7 A2s Fuse, internal  Electronic PRELIMINARY II 1.7.2010
Technical specifications   13.2 Specifications  Wireless Teach Pendant F IWLAN V2 250 Operating Instructions, 08/2010, A5E02453837-01 13.2.6 RFID tag  Memory capacity  128 bytes Memory technology  EEPROM Protocol  ISO 15693 Data retention, at +40° C  10 years MTBF, at + 40° C  2 x 106 hours Read cycles   Unlimited Write cycles, typical   200000 Write cycles, minimal  100000 Multitag-capable  Yes Energy supply, inductive  Energy transfer (without battery) Degree of protection in accordance with EN 60529 IP68 Mechanical design  Material  PC Color  White/petrol Dimensions (L x W x H) in mm  85.6 x 54 x 0.9 Ambient temperature  Operation  –25° C to +80° C Storage/transport  –25° C to +80° C 13.2.7 F-FBs and configuration  F-FBs required in safety program F_FB_MP  1 per Wireless Teach Pendant F IWLAN, maximum 126 F_FB_RNG_4  1 per effective range, for which up to 4 HMI devices have logon permission F_FB_RNG_16  1 per effective range, for which up to 16 HMI devices have logon permission DB_STATES  1   Configuration Number of effective ranges in a project, max.  127 Number of RFID tags in a project, max.  127 Number of RDIF tags per effective range, max.  127 Number of HMI devices authorized for logon per effective range, max.  With F_FB_RNG_4: 4  With F_FB_RNG_16: 16  PRELIMINARY II 1.7.2010
 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  251 Appendix AA.1 ESD guideline What does ESD mean? An electronic module is equipped with highly integrated electronic components. Due to their design, electronic components are highly sensitive to overvoltage and thus to the discharge of static electricity. Such electronic components are labeled as electrostatic sensitive devices (ESD). The following abbreviations are commonly used for electrostatic sensitive devices: ●  ESD – Electrostatic Sensitive Device ●  ESD – Electrostatic Sensitive Device (internationally recognized term) Electrostatic charge   CAUTION  Electrostatic charge ESDs may be destroyed by voltages far below the level perceived by human beings. If you are not discharged electrostatically, the voltage that you transfer when touching a component or the contact points of a module can already cause damage. The damage to an ESD caused by overvoltage is usually not recognized immediately. The damage only becomes apparent after a long period of operation. Discharge any electrostatic charge of your body before you touch the ESD.  Anyone who is not connected conductively to their surroundings is subject to electrostatic charge. PRELIMINARY II 1.7.2010
Appendix   A.1 ESD guideline  Wireless Teach Pendant F IWLAN V2 252 Operating Instructions, 08/2010, A5E02453837-01 The following diagram shows the maximum voltage values to which a person can be charged electrostatically. The values depend on the material and humidity. The shown values are in conformity with the specifications of EN 61000-4-2. 9ROWDJH5HODWLYHKXPLGLW\         >@>N9@ ①  Synthetic materials ②  Wool ③  Antistatic materials such as wood or concrete Protective measures against discharge of static electricity   CAUTION  Grounding measures There is no equipotential bonding without grounding. An electrostatic charge is not discharged and may damage the ESD. When working with electrostatic sensitive devices, make sure that the person and the workplace are properly grounded.  Note the following: ●  Only touch the ESD if it is absolutely necessary. ●  When you touch ESD modules, avoid touching the pins or the PCB tracks. This precaution reduces the risk of damaging an ESD. ●  Discharge electrostatic electricity from your body if you are performing measurements on an ESD. To do so, touch a grounded metal object before you carry out the measurement. ●  Always use grounded measuring instruments. PRELIMINARY II 1.7.2010
 Appendix   A.2 Typical operating procedures and potential fault scenarios Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  253 A.2 Typical operating procedures and potential fault scenarios A.2.1 Overview This section describes typical application cases for the HMI device. The following states are graphically represented in the application cases.  ●  LED status ●  Operability of the EMERGENCY STOP button and enabling buttons The used icons have the following meaning: ●  LED display  Icon  Meaning 6$)( 3:5 &20 51* %$7 Status of the LEDs that are displayed on the HMI device during the described situation. All LEDs are on. ●  EMERGENCY STOP button  Icon  Meaning  Pressing the EMERGENCY STOP button triggers an EMERGENCY STOP.  Pressing the EMERGENCY STOP has no effect. ●  Enabling button  Icon  Meaning  The operator can release movements of the assigned machine with the enabling buttons.  Pressing the enabling buttons has no effect. PRELIMINARY II 1.7.2010
Appendix   A.2 Typical operating procedures and potential fault scenarios  Wireless Teach Pendant F IWLAN V2 254 Operating Instructions, 08/2010, A5E02453837-01 A.2.2 Switch on the HMI device. Requirement  ●  The HMI device is switched off. ●  The rechargeable battery is fully charged.  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    Procedure  1. Switch on the HMI device using the ON/OFF button. Communication via WLAN starts up. While the WLAN connection is being established the "COM" LED flashes. Result  ●  WLAN communication is established. ●  The HMI device displays the Windows CE Desktop with the Loader.  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    PRELIMINARY II 1.7.2010
 Appendix   A.2 Typical operating procedures and potential fault scenarios Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  255 A.2.3 Integrating the HMI device Requirement  ●  The HMI device is switched on. ●  WLAN communication is established. ●  The HMI device shows the Windows CE Desktop with the Loader.   LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    Procedure 1. Start the project. –  PROFIsafe communication is established. –  The "Establishment of safety connection" dialog is shown with the following icon.  –  The HMI device is integrated in the safety program of the F CPU. –  The "Test enabling button" dialog opens with the following icon.  2. Press both enabling buttons when prompted until the "Panic" switch position is reached. Result ●  Both enabling buttons have been tested in the "Enable" and "Panic" switch positions. ●  The project start screen appears.  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    PRELIMINARY II 1.7.2010
Appendix   A.2 Typical operating procedures and potential fault scenarios  Wireless Teach Pendant F IWLAN V2 256 Operating Instructions, 08/2010, A5E02453837-01 A.2.4 Communication error for the integrated HMI device Requirement ●  The HMI device is integrated in the safety program of the F-CPU.  ●  The HMI device is not logged onto a machine.  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    Procedure 1. You are leaving the WLAN range with the HMI device. The "COM" LED flashes. The F CPU detects a communication error and initiates a global rampdown. The "SAFE" LED goes out. The user is informed that no safety functions are available. The "No safety connection" dialog is shown with the following symbol.  2. You will return to the WLAN range within 60 seconds. The "Acknowledgment of communication error" dialog opens with the following symbol.  3. Acknowledge the communication error. See Result 1. 4. You remain outside the WLAN. The "Confirm removal" dialog will be displayed after 60 seconds with the following symbol.  See Result 2. Result 1 – Return to the WLAN range ●  The "Global rampdown" signal is canceled. PROFIsafe communication is again possible. ●  The HMI device is fully operable. PRELIMINARY II 1.7.2010
 Appendix   A.2 Typical operating procedures and potential fault scenarios Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  257  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    Result 2 – No return to the WLAN range ●  The project will be closed immediately if you confirm the Confirm removal dialog within 60 seconds. ●  The active project will be closed automatically if you do not confirm the "Confirm removal" dialog within 60 seconds. ●  The Windows CE desktop with the loader is shown on the display.  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    Wireless network communication is reestablished if you later return to the WLAN range with the HMI device. Start the project again. Acknowledge the communication error in the "Acknowledgment of communication error" dialog with the following symbol.  The "Global rampdown" signal is cancelled when you acknowledge the communication error. Test the enabling buttons when the "Test Enabling Button" dialog is shown with the following symbol.  The HMI device is integrated again.   Note Users can react to a fault on the HMI device by resetting the associated F_FB_MP to the "original state" using input "S7_MP_RES." This action sets the relevant HMI device to the "removed" state and the global rampdown signal is canceled.  PRELIMINARY II 1.7.2010
Appendix   A.2 Typical operating procedures and potential fault scenarios  Wireless Teach Pendant F IWLAN V2 258 Operating Instructions, 08/2010, A5E02453837-01 A.2.5 Discrepancy error during enabling The enabling button is two-channel. Both contacts must be closed at the same time to reach the enabled state. A discrepancy error is generated if one of the contacts is open while the other is closed. The following fault scenarios can occur: ●  The enabling button is askew ●  The enabling button is defective. A.2.5.1 The enabling button is askew Requirement The HMI device is integrated.  ●  The HMI device is not logged onto a machine.  LED display  EMERGENCY STOP button Enabling button6$)( 3:5 &20 51* %$7    ●  The HMI device is logged on to a machine.  LED display  EMERGENCY STOP button Enabling button6$)( 3:5 &20 51* %$7    Procedure 1. Press the enabling button. If you press the edge of an enabling button, the pressure point for the contacts is not centered. The signal is therefore transmitted only through one of the two contacts. The controller detects a discrepancy. Result The enabled state is withdrawn when a discrepancy is detected. The "Discrepancy error enabling button" dialog opens with the following symbol when the discrepancy time expires.  PRELIMINARY II 1.7.2010
 Appendix   A.2 Typical operating procedures and potential fault scenarios Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  259 The dialog stays open until this discrepancy is corrected. Additional information on discrepancy time is available in "Wireless Teach Pendant F IWLAN V2 (Page 244)", section "Fail-safe operation". Enabling is made possible by pressing the enabling button again from the zero position. ●  The HMI device is integrated but not logged onto a machine.  LED display  EMERGENCY STOP button Enabling button6$)( 3:5 &20 51* %$7    ●  The HMI device is integrated and logged onto a machine:  LED display  EMERGENCY STOP button Enabling button6$)( 3:5 &20 51* %$7    A.2.5.2 The enabling button is defective. Requirement ●  The HMI device is integrated and logged onto a machine. ●  An enabling button is defective and not pressed. Distinguish between the two scenarios: –  Scenario 1 One channel of the enabling button is opened permanently. –  Scenario 2 One channel of the enabling button is closed permanently. Discrepancy is detected in this situation. The "Discrepancy error enabling button" dialog is displayed with the following symbol.    LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    PRELIMINARY II 1.7.2010
Appendix   A.2 Typical operating procedures and potential fault scenarios  Wireless Teach Pendant F IWLAN V2 260 Operating Instructions, 08/2010, A5E02453837-01 Procedure 1. Press the enabling button. Result – Scenario 1 ●  The enabled state is not activated. The "Discrepancy error enabling button" dialog opens with the following symbol when the discrepancy time expires.  The dialog stays open until the enabling button is released. This step cancels the discrepancy. A discrepancy error is displayed again when the operator presses the enabling button once again . ●  The device must be repaired. See section "Spare parts and repairs (Page 239)". ●  Press the second working enabling button to remove the HMI device. Result – Scenario 2 ●  The "Discrepancy error enabling button" dialog is closed and the discrepancy is cleared. The enable signal remains in deactivated state. The "Discrepancy error enabling button" dialog is displayed with the following symbol when the enabling button is released.  ●  The device must be repaired. See section "Spare parts and repairs (Page 239)". A.2.6 Logging onto a machine Requirement ●  You have the HMI device at a distance of no more than 5 cm in front of an RFID tag. ●  The "Effective range name (RFID)" object is shown in white labeled "Scan". 6FDQ  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    PRELIMINARY II 1.7.2010
 Appendix   A.2 Typical operating procedures and potential fault scenarios Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  261 Procedure  1. Touch the "Effective range name (RFID)" object labeled "Scan". The HMI device searches for RFID tags, the "Effective range name (RFID)" object is shown in yellow labeled "Scanning". 6FDQQLQJ If the "Effective range name (RFID)" object is configured with password protection, enter a valid user name and a valid password. The "Effective range logon" dialog opens with the following symbol.  2. Read the effective range ID from the RFID tag. 3. Enter the effective range ID. 4. Click "Yes". The dialog closes. The "Confirmation of logon" dialog is displayed with the following symbol.  5. Confirm the logon to the RFID tag with the enabling button. Result ●  You have logged on the HMI device to the machine via the RFID tag. ●  The "Effective range name (RFID)" operator control is shown in green and labeled with the name of the effective range. The following figure shows the "Effective range name (RFID)" object after logon to an effective range with the name "Robot 1". 5RERW  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    PRELIMINARY II 1.7.2010
Appendix   A.2 Typical operating procedures and potential fault scenarios  Wireless Teach Pendant F IWLAN V2 262 Operating Instructions, 08/2010, A5E02453837-01 A.2.7 Leaving a protection zone without logging off Requirement ●  A security system is installed for the protection zone, for example, a photoelectric sensor or a contact pressure mat. ●  The HMI device has been logged on to a machine, such as "Robot 1", via an RFID tag. 5RERW  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    Procedure 1. You leave the protection zone with the HMI device through the security system. The HMI device initiates a local rampdown. The "Forced logoff" dialog opens with the following symbol.  2. Close the "Forced logoff" dialog with "OK". Result The HMI device is logged off the machine. The machine is free again for logon.  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    PRELIMINARY II 1.7.2010
 Appendix   A.2 Typical operating procedures and potential fault scenarios Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  263 A.2.8 Communication errors with logged on HMI device Starting situation The HMI device is logged on to a machine.  5DQJHQDPH  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    Fault A communication error occurs. The F-CPU initiates a shutdown and stops the machine. The "SAFE" and "RNG" LEDs are off. The operator is alerted that no safety-related communication is available. Result – Communication will be reestablished within 60 seconds If the communication is reestablished within 60 seconds, the "Acknowledgment of communication error" dialog will open. If the operator acknowledges the communication error, the shutdown signal will be cancelled. PROFIsafe communication is again possible. The machine is free again for logon.  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    Result – Communication remains interrupted for more than 60 seconds If communication remains interrupted for more than 60 seconds, the project will be closed. The HMI device displays the Windows CE Desktop with the loader. Wireless network communication is reestablished if you later return to the WLAN range with the HMI device. Start the project again. Acknowledge the communication error in the "Acknowledgment of communication error" dialog. The shutdown signal is revoked. The HMI device is fully operable. PRELIMINARY II 1.7.2010
Appendix   A.2 Typical operating procedures and potential fault scenarios  Wireless Teach Pendant F IWLAN V2 264 Operating Instructions, 08/2010, A5E02453837-01  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    A.2.9 Logging off the machine Requirement  ●  The HMI device is logged on to a machine.  ●  The "Effective range name" object will be displayed in green. 5DQJHQDPH  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    Procedure  1. Confirm the "Effective range name (RFID)" object. The "Effective range logoff" dialog opens with the following symbol.  2. Confirm the logoff from the machine with the "Yes" button. Result  ●  The HMI device is logged off the machine. ●  The "Effective range name (RFID)" object is shown in white labeled "Scan". 6FDQ  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    PRELIMINARY II 1.7.2010
 Appendix   A.2 Typical operating procedures and potential fault scenarios Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  265 A.2.10 Removing the HMI device Requirement ●  The project must be started. ●  The HMI device is integrated in the safety program of the F-CPU. ●  The HMI device is not logged onto a machine.  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    Procedure 1. To close the project, use the operator control designed for this purpose. The "Start removal" dialog opens with the following symbol.  2. Use the "Yes" button to confirm the removal. The "Confirm removal" dialog opens with the following symbol.  3. Press an enabling button within 60 seconds.  NOTICE   Global rampdown A global rampdown will occur, if you do not confirm the "Confirm removal" dialog within 60 seconds with the enabling button. Press an enabling button within 60 seconds.  Result  ●  Safety-related communication is terminated. ●  The HMI device has been successfully removed from the safety program of the F-CPU. ●  The project is closed. ●  The HMI device shows the Windows CE Desktop with the loader. PRELIMINARY II 1.7.2010
Appendix   A.2 Typical operating procedures and potential fault scenarios  Wireless Teach Pendant F IWLAN V2 266 Operating Instructions, 08/2010, A5E02453837-01  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    A.2.11 Switching off the HMI device Requirement  ●  The project must be started. ●  The HMI device is integrated in the safety program of the F-CPU.  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    Procedure  1. Close all open dialogs. 2. Press and hold the "ON/OFF" button for at least 4 seconds. The "Start removal" dialog opens with the following symbol.  3. Use the "Yes" button to confirm the removal. The "Confirm removal" dialog opens with the following symbol.  4. Press an enabling button within 60 seconds.  NOTICE   Global rampdown A global rampdown will occur, if you do not confirm the "Confirm removal" dialog within 60 seconds with the enabling button. Press an enabling button within 60 seconds.  PRELIMINARY II 1.7.2010
 Appendix  A.3 Example of an application Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  267 Result ●  Safety-related communication is terminated. ●  The HMI device has been successfully removed from the safety program of the F-CPU. ●  The project is closed. ●  The HMI device will be switched off.  LED display  EMERGENCY STOP button Enabling button 6$)( 3:5 &20 51* %$7    A.3 Example of an application A.3.1 Configuration and operation This application example shows one possible application with the safety features of the HMI device.   Note In this example, the HMI device is logged onto a machine via an RFID tag within a protection zone. The security system of the protection zone consists of a wire mesh fence with a door and a contact pressure mat.  WARNING  Read the documentation for S7 Distributed Safety An incorrectly configured or programmed system can result in death or serious injuries. We highly recommend that you read the information on S7 Distributed Safety in Programming and operation manual "S7 Distributed Safety - Configuring and Programming" (http://support.automation.siemens.com/WW/view/en/22099875) and in the online help of S7 Distributed Safety.  PRELIMINARY II 1.7.2010
Appendix   A.3 Example of an application  Wireless Teach Pendant F IWLAN V2 268 Operating Instructions, 08/2010, A5E02453837-01 Configuration example The following example configuration shows a robot cell which is secured by a wire mesh fence with a contact pressure mat.  ($$$ 352),VDIH ①  Access point ②  Fail-safe controller ③  Robot ④  Signal lamp ⑤  F-I/O, PROFINET IO device ⑥  HMI device ⑦  RFID tag ⑧  Contact pressure mat The following signals are used:  PRELIMINARY II 1.7.2010
 Appendix  A.3 Example of an application Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  269 Function Symbolic name  Signal  Explanation Contact pressure mat "Contact_Mats" I11.0  "0": Step on contact pressure mat "1": Do not step on contact mat  "Key1" button, configured as direct key on the HMI device: E0.0  "0": Button not pressed "1": Button pressed Enabling button  ENABLE (F_FB_RNG_4) "0": No enable "1": Enable Power ON-OFF robot "E_Stop_Robot" O11.0  "0": EMERGENCY STOP triggered. "1": Normal operation of plant. Actuator to robot  O11.1  "0": The robot is not operated with Key1 and the enabling buttons "1": The robot is operated with Key1 and the enabling buttons Signal lamp  O 11.2  "0": Robot is not in use; the signal lamp is off "1": Robot is in use; the signal lamp is on Flowchart The following flowchart shows the operation sequence in the example.  StartLog on to the machine?YesNoOperation in the protection zone is possibleContact with pressure mat?Forced logoffYesNoOperation in the protection zone not possible PRELIMINARY II 1.7.2010
Appendix   A.3 Example of an application  Wireless Teach Pendant F IWLAN V2 270 Operating Instructions, 08/2010, A5E02453837-01 A.3.2 Configuring the controller and HMI device in STEP 7 This section describes the most important parameters you need to set in "HW Config" for the F-CPU and for the HMI device.  WARNING  Safety category Any changes to parameters may result in the loss of the safety category. Set the parameters as described. The parameters will contribute to meeting safety category 4 PL e/SIL 3.   Requirement  The software for fail-safe operation has been installed, see section "Required software (Page 22)". Procedure – Configuring CPU 317F-2 PN/DP Proceed as follows: 1. Create a STEP 7 project in SIMATIC Manager. 2. Open the "HW Config" hardware configuration and insert the desired F-CPU and a PROFINET connection, as shown in the following figure:  3. Open the settings by double-clicking the F-CPU in "HW Config". The table below shows the most important settings: PRELIMINARY II 1.7.2010
 Appendix  A.3 Example of an application Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  271  Setting  Explanation  This is where you set the cycle time for OB35. Note If the cycle time for OB35 is set lower than the PBIO update time, the message frame may be lost and the evaluation of the "E-STOP" output of F_FB_RNG_4 or F_FB_RNG_16 may be delayed. Set the cycle time of OB35 to a value higher than the PNIO update time.  Assign a password for the safety program. Set the "CPU contains safety program" check box. This setting is required to generate all the necessary F-FBs for safe operation of the fail-safe modules during compilation of "HW Config" by STEP 7. PRELIMINARY II 1.7.2010
Appendix   A.3 Example of an application  Wireless Teach Pendant F IWLAN V2 272 Operating Instructions, 08/2010, A5E02453837-01 Procedure – Configuring Wireless Teach Pendant F IWLAN Proceed as follows: 1. Insert the Wireless Teach Pendant F IWLAN in "HW Config" as shown in the following figure.  2. Open the properties dialog of the HMI device by double-clicking the "WTPfiwlan" icon. 3. Enter the device name of the HMI device in the properties dialog. 4. Open the properties dialog of the "WTPFailsafe_IO" module by double-clicking the "WTPFailsafe_IO" entry in the detailed view of the HMI device. 5. Change to the "PROFIsafe" tab. PRELIMINARY II 1.7.2010
 Appendix  A.3 Example of an application Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  273 The table below shows the most important settings:  Setting  Explanation Device name Here you assign a device name to the HMI device, which is unique in the local Ethernet network segment. This name must match the name defined in the Control Panel of the HMI device under "PROFINET" in the text box "Device name:". Additional information is available in the section: "Specifying the computer name of the HMI device (Page 145)". Inputs This is where you specify the start address of the inputs and the process image associated with this address area (PII). Outputs Here you specify the start address of the outputs and the process image associated with this address area (PIQ). F_Dest_Add PROFIsafe address of the Wireless Teach Pendant F IWLAN. This address must match the address on the HMI device. F_WD_Time Monitoring time in the fail-safe IO device. A valid current safety message frame must reach the F-CPU and be returned to the HMI device within the monitoring time period. This ensures that failures and errors are detected and appropriate responses are triggered to keep the fail-safe system in a safe state or transfer it to a safe state. The monitoring time selected must be long enough that message frame delays will be tolerated by the communication system, but also that the fault reaction function responds quickly enough in the event of a fault (e.g. interruption in the communication connection). PRELIMINARY II 1.7.2010
Appendix   A.3 Example of an application  Wireless Teach Pendant F IWLAN V2 274 Operating Instructions, 08/2010, A5E02453837-01 A.3.3 Safety program S7 Distributed Safety In the safety program of the S7-CPU, the operation sequence of the application example is implemented by the following programming:  ●  Once the HMI device is logged on to a machine, the signal lamp and the "Override" mode are enabled. ●  In the protection zone, the operator can operate the robot with the "Key1" button and the enabling button. ●  If the operator leaves the protection zone over the contact pressure mat, the safety program responds as follows: –  The signal lamp goes out. –  "Override" mode is deactivated. –  The HMI device is logged off the machine. ●  After an EMERGENCY STOP, the plant only restarts when the operator performs an acknowledgment. ●  Reactions specific to a plant are initiated when a rampdown or shutdown occurs. Safety program  The safety program is structured as follows: )% )B)%B03))%)B)%B51*))%)B(6723))%)&DOO)& Symbolic names The following symbolic names are used in the networks of the sample programs  Symbolic name  Meaning F00256_WTPFailsafe_IO  Fail-safe I/O DB of HMI device MP1_FB_S7_MP_RE  Input which is set when a reset of the HMI device is performed from the F-CPU. MP1_FB_S7_ACK_ERR  Input which is set when a communication error is acknowledged from the F-CPU. MP1_F_DATA_PII  Word 1 of the PII of the HMI device MP1_F_RANGE_PII  Word 2 of the PII of the HMI device MP1_F_DATA_PIQ  Word 1 of the PIQ of the HMI device MP1_F_RANGE_PIQ  Word 2 of the PIQ of the HMI device Interface_DB  F-DB for the data transfer of user data F_DB_States  F-DB for the transfer of data between the F_FB_MP of the HMI device and the F_FB_RNG_n of the effective range PRELIMINARY II 1.7.2010
 Appendix  A.3 Example of an application Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  275 F-CALL (FC 1) F-CALL (FC1) is the F-run-time group and is called from the cyclic interrupt OB (OB35). F-CALL (FC1) calls the F-program block (in this case: FB1). FB1 For reasons of program modularity, all other F-FBs are called from this FB. In FB 1, you have to call the F-FBs in the following order. 1. Network 1 )B:73)DLOVDIHB,2ಯ$&.B5(,03B)B'$7$B3,4ಯ03B)B51*B3,4,QWHUIDFHB'%03B)%B',$*'%(14%$'$&.B5(46B03B5(66B$&.B(5503B'$7$03B51*03B67$7$&.B5(,03B'$7$B403B51*B4',$*(12)B)%B03)B:73)DLOVDIHB,24%$')B:73)DLOVDIHB,2$&.B5(403B)%B6B03B5(03B)%B6B$&.B(5503B)B'$7$B3,,03B)B51*B3,,)B'%B67$7(603BB6WDWXV The controller uses this F-FB to monitor the PROFIsafe communication of the HMI device. The following diagnostics information is indicated at the "DIAG" output: –  Status of the HMI device: integrated or removed –  A communication error has occurred. –  Communication error must be acknowledged Additional information is available in F_FB_MP (Page 171). PRELIMINARY II 1.7.2010
Appendix   A.3 Example of an application  Wireless Teach Pendant F IWLAN V2 276 Operating Instructions, 08/2010, A5E02453837-01 2. Network 2 (GJHB&RQWDFWB0DWV1(*0B%,7 4&RQWDFWB0DWV )B)%B51*B'%(151*B,'29(55,'(03B'$7$03B51*03B)B.(<03B'$7$03B51*03B)B.(<03B'$7$03B51*03B)B.(<03B'$7$03B51*03B)B.(<03B67$703B67$703B67$703B67$7(B6723*/2%B5'/2&B5'6+87'2:1(1$%/()B.(<651*B%86<',$*(12,QWHUIDFHB'%(5B(B6723,QWHUIDFHB'%(5B*/2%B5',QWHUIDFHB'%(5B/2&B5',QWHUIDFHB'%(5B6+87'2:1,QWHUIDFHB'%(5B(1$%/(,QWHUIDFHB'%(5B51*B%86<,QWHUIDFHB'%(5B)%B',$*03B)B'$7$B3,,03B)B51*B3,,)B'%B67$7(603BB6WDWXV,QWHUIDFHB'%(5B51*B%86< The activation of the "override" mode is controlled in this network. "OVERRIDE" is set as soon as the operator has logged the HMI device on to the machine via the RFID tag. (RNG_BUSY). "OVERRIDE" is reset by a negative edge on the contact pressure mat, in other words I11.0 = "0". This is the case when the operator leaves the protection zone. At the same time, F_FB_RNG monitors the signals "EMERGENCY STOP", "Global rampdown", "Local rampdown" and "Shutdown". They are scanned in networks 3 to 6. PRELIMINARY II 1.7.2010
 Appendix  A.3 Example of an application Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  277 3. Network 3 )B(6723'%,QWHUIDFHB'%(5B(B6723(B6WRSB5RERW(1(B6723$&.B1(&$&.7,0(B'(/44B'(/$<$&.B5(4',$*(12 In network 3, the EMERGENCY STOP signal of the HMI device is monitored via F_ESTOP1 from the F-library of S7 Distributed Safety. F_ESTOP1 ensures that the plant is only able to restart following an EMERGENCY STOP after acknowledgment by the operator via the input "ACK".    Note Read also the information on FB215 in the online help for F-FBs and in the manual "SIMATIC S7-Distributed Safety, Configuring and Programming", section "FB215 "F_ESTOP1:" Emergency STOP up to Stop Category 1".  4. Networks 4, 5 and 6    *OREDOB5DPSGRZQ/RFDOB5DPSGRZQ6KXWGRZQ,QWHUIDFHB'%(5B*/2%B5',QWHUIDFHB'%(5B/2&B5',QWHUIDFHB'%(5B6+87'2:1 In network 4, 5 and 6 the signals for a global and a local rampdown and shutdown are processed further. As the configuration of the monitored plant determines which responses have to occur following occurrence of a particular safety state, these networks are not explained in detail in this example. PRELIMINARY II 1.7.2010
Appendix   A.3 Example of an application  Wireless Teach Pendant F IWLAN V2 278 Operating Instructions, 08/2010, A5E02453837-01 5. Network 7  ($,QWHUIDFHB'%(5B(QDEOH If the operator simultaneously presses the Key1 key and the enabling button, the robot is activated via the output Q11.1. 6. Network 8  ,QWHUIDFHB'%(5B51*B%86<$  If the "RNG_BUSY" signal is set in F_FB_RNG, output Q11.2 is used to control the signal lamp that indicates whether or not the machine is in use. PRELIMINARY II 1.7.2010
 Appendix  A.4 Safety-related messages Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  279 A.4 Safety-related messages The following safety-related messages are displayed in fail-safe mode depending on the operating situation. In contrast to system alarms, no message window needs to be configured for safety-related messages.  Dialog  Reaction  Situation Establishment of safety connection No safe connection available.  Reason:  Connection not yet completed  PROFIsafe address error  Internal configuration error  Communication error (timeout)  Communication error (CRC)  CPU in STOP  PROFIsafe CRC configuration error Should the Panel be switched off? "Yes" button  The following is reported in the warning message depending on the operating situation:  Connection not yet completed The safe connection is not yet established after the project has been started. Wait until the connection has been established. The dialog is closed on completion.  A communication error occurred after the HMI device was successfully integrated. Correct the cause of the error described by "Reason". Start removal  The removal cannot be interrupted once it has started. Do you want to start the removal? "Yes" button "No" button The "Start removal" dialog opens in the following cases:  The operator has pressed the "ON/OFF" button for more than 4 seconds.  The operator has pressed the operator control for closing the project. Confirm removal  Please confirm the removal with the enabling button. Press an enabling button until the "Enable" switch position is reached. The removal starts, in other word, the user has pressed the "Yes" button in the "Start removal" dialog. PRELIMINARY II 1.7.2010
Appendix   A.4 Safety-related messages  Wireless Teach Pendant F IWLAN V2 280 Operating Instructions, 08/2010, A5E02453837-01 Dialog  Reaction  Situation Effective range logon  Do you want to logon to the following effective range?  Effective range <<EFFECTIVE RANGE NAME>> Please enter the effective range ID: "Yes" button "No" button The HMI device is located directly in front of an RFID tag and is not yet logged on to the corresponding machine.  The operator has activated the "Scan" object to log on. 6FDQ Effective range logoff  Do you want to log off from the following effective range? Effective range <<EFFECTIVE RANGE NAME>> "Yes" button "No" button The HMI device is logged on to a machine. The operator has activated the "Effective range name (RFID)" object to log off. Effective range logoff (shutdown)  The Panel cannot be switched off. You first have to log off from the effective range. Do you want to logoff from the following effective range? Effective range <<EFFECTIVE RANGE NAME>> "Yes" button "No" button The HMI device is logged on to a machine. The operator has attempted to:  Shut down the HMI device.  Close the project with the corresponding operator control. Acknowledgment of communication error  A safe connection is possible again. Please confirm the communication error. "OK" button  Communication was recovered after a short communication error. The operator must confirm this state.  Causes:  The operator has briefly left the WLAN range and then returned.  PROFIsafe communication was briefly interrupted. PRELIMINARY II 1.7.2010
 Appendix  A.4 Safety-related messages Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  281 Dialog  Reaction  Situation Forced logoff  You are automatically logged off from the effective range. A local rampdown has been triggered! Confirm the logoff from the effective range. "OK" button  The operator has left the protection zone with a logged-on HMI device via the safety system. Low battery alarm Battery charge is less than 20 percent. "OK" button  The remaining charge of the main rechargeable battery is less than 20%. An additional system alarm is output after the charge of the main rechargeable battery has dropped to less than 6%. Test enabling button  Both enabling buttons must be tested to ensure they are operational. Fully press both enabling buttons until the panic position is reached. Press both enabling buttons until the "Panic" switch position is reached. The operator has started the project.  Perform a function test for the enabling button.  Error during effective range logon  Error during effective range logon. The enabling button remains deactivated. "OK" button  An error occurred during logon of the HMI device to a machine. The operator cannot use the enable switches to control the production process. Possible causes:  You are already logged on to the machine with your HMI device or the logon is currently in progress.  Another HMI device is already logged on to the machine.  RFID tag is defective.  RFID module in the HMI device is defective.  No ID has been assigned to the RFID tag.  The operator has entered an incorrect RFID tag ID for the logon.  F_FB_RNG missing in the STEP7 configuration.  F_FB_RNG is wired incorrectly in STEP7. PRELIMINARY II 1.7.2010
Appendix   A.4 Safety-related messages  Wireless Teach Pendant F IWLAN V2 282 Operating Instructions, 08/2010, A5E02453837-01 Dialog  Reaction  Situation Enabling switch discrepancy error  Please release the enabling button. Release both enabling buttons. The HMI device detects a discrepancy at one of the two enabling buttons in switch position "Enable". See also Communication error for the integrated HMI device (Page 256) PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  283 A.5 System alarms Introduction System alarms on the HMI device provide information about internal states of the HMI device and PLC. The following overview shows the causes of system alarms and how to eliminate the cause of error. Some of the system alarms described in this section are relevant to individual HMI devices based on their range of features.   Note System alarms are only indicated if an alarm window was configured. System alarms are output in the language currently set on your HMI device. System alarm parameters  System alarms may contain encrypted parameters which are relevant to troubleshooting because they provide a reference to the source code of the runtime software. These parameters are output after the text "Error code:" Displaying the "System alarms" editor  You can find the text content of the system alarm in WinCC flexible. The "System alarms" editor is not displayed by default in WinCC flexible. 1. Enable the "System alarms" editor under "Options > Setting... > Workbench > Settings for Project Window" with "Display all entries". 2. Select the "System alarms" editor under "Alarms" in the project view. The system alarms are sorted numerically in the "System alarms" editor.  Configuring events for system alarms You can configure the "Incoming" event for the following system alarm in the "System alarms" editor.  System alarms 10000  10000 to 10006 150000  150000  150001 230300  230300 to 230308 20000  20000 to 20015 160000  160000  160001  160010 to 160014 240000  240000 to 240005 30000  30010 to 20012 170000  170000 to 170004  170007 250000  250000 to 250003 PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 284 Operating Instructions, 08/2010, A5E02453837-01 System alarms 40000  40010  40011 180000  180000 to 180002 260000  260000 to 260009  260012 to 260014  260028  260030  260033 to 260045 50000  50000  50001 190000  190000 to 190002  190004 to 190013 270000  270000 to 270003 60000  60010 to 60011 190100  190100 to 190102 280000  280000 to 280004 70000  70010 to 70044 200000  200000 to 200005 290000  290000 to 290008  290010 to 290014  290020 to 290027  290040 to 290042  290044  290050 to 290065  290070 to 290073  290075 80000  80001 to 80035  80044 to 80050 200100  200100 to 200105 300000  300000  300001 90000  90024 to 90026  90029 to 90033  90040  90041  90044 210000  210000 to 210006 310000  310000  310001 110000  110000 to 110006 220000  220000 to 220008 600000  600000 120000  120000 to 120002 230000  230000  230002  200003  200005 620000  620000 130000  130000 to 130012 230100  230100  140000  140000 to 140020 230200  230200 to 230203  PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  285 10000 - Printer alarms   Number  Effect/cause  Remedy 10000  The print job could not be started or was canceled due to an unknown error. Faulty printer setup. Or: No authorization is available for accessing the network printer. Power supply failure during data transfer. Check the printer settings, cable connections and the power supply. Set up the printer once again. Obtain a network printer authorization. If the error persists, contact the Hotline! 10001  No printer is installed or a default printer has not been set up. Install a printer and/or select it as the default printer. 10002  Overflow of the graphics buffer for printing. Up to two graphics are buffered. Allow sufficient intervals between successive print jobs.10003  Graphics can now be buffered again.  -- 10004  Overflow of the buffer for printing lines in text mode (e.g. alarms). Up to 1000 lines are buffered. Allow sufficient intervals between successive print jobs.10005  Text lines can now be buffered again.  -- 10006  The Windows printing system reports an error. Refer to the output text and the error ID to determine the possible causes. Nothing is printed or the print is faulty. Repeat the action if necessary.  20000 - Global script alarms  Number  Effect/causes  Remedy 20010  An error has occurred in the specified script line. Execution of the script was therefore aborted. Note the system alarm that may have occurred prior to this. Select the specified script line in the configuration. Ensure that the tags used are of the allowed types. Check system functions for the correct number and types of parameters. 20011  An error has occurred in a script that was called by the specified script.  Execution of the script was therefore aborted in the called script.  Note the system alarm that may have occurred prior to this.  In the configuration, select the script that has been called directly or indirectly by the specified script.  Ensure that the tags used are of the allowed types.  Check system functions for the correct number and types of parameters. 20012  The configuration data is inconsistent. The script could therefore not be generated. Recompile the configuration. 20013  The scripting component of WinCC flexible Runtime is not correctly installed. Therefore, no scripts can be executed. Reinstall WinCC flexible Runtime on your PC.  Rebuild your project with "Project > Compiler > Generate" and transfer the project to the HMI device. 20014  The system function returns a value that is not written in any return tag. Select the specified script in the configuration. Check whether the script name has been assigned a value. 20015  Too many successive scripts have been triggered in short intervals. When more than 20 scripts are queued for processing, any subsequent scripts are rejected. In this case, the script indicated in the alarm is not executed. Find what is triggering the scripts. Extend the times, e.g. the polling time of the tags which trigger the scripts. PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 286 Operating Instructions, 08/2010, A5E02453837-01 30000 - Alarms for IFwSetValue: SetValue()  Number  Effect/causes  Remedy 30010  The tag could not accept the function result, e.g. when it has exceeded the value range. Check the tag type of the system function parameter. 30011  A system function could not be executed because the function was assigned an invalid value or type in the parameter. Check the parameter value and tag type of the invalid parameter. If a tag is used as a parameter, check its value. 30012  A system function could not be executed because the function was assigned an invalid value or type in the parameter. Check the parameter value and tag type of the invalid parameter. If a tag is used as a parameter, check its value. 40000 - Linear scaling alarms  Number  Effect/causes  Remedy 40010  The system function could not be executed since the parameters could not be converted to a common tag type. Check the parameter types in the configuration. 40011  The system function could not be executed since the parameters could not be converted to a common tag type. Check the parameter types in the configuration. 50000 - Data server alarms   Number  Effect/causes  Remedy 50000  The HMI device is receiving data faster than it is capable of processing. Therefore, no further data is accepted until all current data have been processed. Data exchange then resumes. -- 50001  Data exchange has been resumed.  -- 60000 - Win32 function alarms   Number  Effect/causes  Remedy 60000  This alarm is generated by the “DisplaySystemAlarms” function. The text to be displayed is transferred to the function as a parameter. -- 60010  The file could not be copied in the direction defined because one of the two files is currently open or the source/target path is not available. It is possible that the Windows user has no access rights to one of the two files. Restart the system function or check the paths of the source/target files. Using Windows NT/XP: The user running WinCC flexible Runtime must be granted access rights to the files. 60011  An attempt was made to copy a file to itself. It is possible that the Windows user has no access rights to one of the two files. Check the path of the source/target file. Using Windows NT/XP with NTFS: The user running WinCC flexible Runtime must be granted access rights to the files. PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  287 70000 - Win32 function alarms   Number  Effect/causes  Remedy 70010  The application could not be started because it could not be found in the path specified or there is insufficient memory space. Check whether the application exists in the specified path or close other applications. 70011  The system time could not be modified. The error alarm only appears in connection with area pointer "Date/time PLC". Possible causes:  An invalid time was transferred in the job mailbox.  The Windows user has no right to modify the system time. If the first parameter in the system alarm is displayed with the value 13, the second parameter indicates the byte containing the incorrect value. Check the time which is to be set. Using Windows NT/XP: Users running WinCC flexible Runtime must be granted the right to modify the system time of the operating system. 70012  An error occurred when executing the function "StopRuntime" with the option "Runtime and operating system". Windows and WinCC flexible Runtime are not closed.One possible cause is that other programs cannot be closed. Close all programs currently running. Then close Windows. 70013  The system time could not be modified because an invalid value was entered. Incorrect separators may have been used. Check the time which is to be set. 70014  The system time could not be modified. Possible causes:  An invalid time was transferred.  The Windows user has no right to modify the system time. Windows rejects the setting request. Check the time which is to be set. Using Windows NT/XP: Users running WinCC flexible Runtime must be granted the right to modify the system time of the operating system. 70015  The system time could not be read because Windows rejects the reading function. -- 70016  An attempt was made to select a screen by means of a system function or job. This is not possible because the screen number specified does not exist. Or: A screen could not be generated due to insufficient system memory. Or: The screen is blocked. Or: Screen call has not been executed correctly. Check the screen number in the function or job with the screen numbers configured. Assign the number to a screen if necessary. Check the details for the screen call and whether the screen is blocked for specific users. 70017  Date/time is not read from the area pointer because the address set in the PLC is either not available or has not been set up. Change the address or set up the address in the PLC. 70018  Acknowledgment that the password list has been successfully imported. -- 70019  Acknowledgment that the password list has been successfully exported. -- 70020  Acknowledgment for activation of alarm reporting.  -- 70021  Acknowledgment for deactivation of alarm reporting.  -- 70022  Acknowledgment to starting the Import Password List action. -- PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 288 Operating Instructions, 08/2010, A5E02453837-01 Number  Effect/causes  Remedy 70023  Acknowledgment to starting the Export Password List action. -- 70024  The range of values of the tag was exceeded in the system function. No calculation of the system function. Check and correct the calculation. 70025  The range of values of the tag was exceeded in the system function. No calculation of the system function. Check and correct the calculation. 70026  No other screens are stored in the internal screen memory. No other screens can be selected. -- 70027  The backup of the RAM file system has been started.  -- 70028  The files from the RAM have been copied in the Flash memory. The files from the RAM have been copied in the Flash memory. Following a restart, these saved files are copied back to the RAM file system. -- 70029  Backup of the RAM file system has failed. No backup copy of the RAM file system has been made. Check the settings in the "Control Panel > OP" dialog and save the RAM file system using the "Save Files" button in the "Persistent Storage" tab. 70030  The parameters configured for the system function are faulty. The connection to the new PLC was not established. Compare the parameters configured for the system function with the parameters configured for the PLCs and correct them as necessary. 70031  The PLC configured in the system function is not an S7 PLC. The connection to the new PLC was not established. Compare the S7 PLC name parameter configured for the system function with the parameters configured for the PLC and correct them as necessary. 70032  The object configured with this number in the tab order is not available in the selected screen. The screen changes but the focus is set to the first object. Check the number of the tab order and correct it if necessary. 70033  An e-mail cannot be sent because a TCP/IP connection to the SMTP server no longer exists. This system alarm is generated only at the first attempt. All subsequent unsuccessful attempts to send an e-mail will no longer generate a system alarm. The event is regenerated when an e-mail has been successfully sent in the meantime. The central e-mail component in WinCC flexible Runtime attempts, in regular intervals (1 minute), to establish the connection to the SMTP server and to send the remaining e-mails. Check the network connection to the SMTP server and re-establish it if necessary. 70034  Following a disruption, the TCP/IP connection to the SMTP server could be re-established. The queued e-mails are then sent. -- 70036  No SMTP server for sending e-mails is configured. An attempt to connect to an SMTP server has failed and it is not possible to send e-mails. WinCC flexible Runtime generates the system alarm after the first attempt to send an e-mail. Configure an SMTP server: In WinCC flexible Engineering System using "Device settings > Device settings" In the Windows CE operating system using "Control Panel > Internet Settings > E-mail > SMTP Server" PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  289 Number  Effect/causes  Remedy 70037  An e-mail cannot be sent for unknown reasons. The contents of the e-mail are lost. Check the e-mail parameters (recipient etc.). 70038  The SMTP server has rejected sending or forwarding an e-mail because the domain of the recipient is unknown to the server or because the SMTP server requires authentication. The contents of the e-mail are lost. Check the domain of the recipient address or disable the authentication on the SMTP server if possible. SMTP authentication is currently not used in WinCC flexible Runtime. 70039  The syntax of the e-mail address is incorrect or contains illegal characters. The contents of the e-mail are discarded. Check the e-mail address of the recipient. 70040  The syntax of the e-mail address is incorrect or contains illegal characters. -- 70041  The import of the user management was aborted due to an error. Nothing was imported. Check your user management or transfer it again to the panel. 70042  The range of values of the tag was exceeded while executing the system function. The system function was not calculated. Check and correct the calculation. 70043  The range of values of the tag was exceeded while executing the system function. The system function was not calculated. Check and correct the calculation. 70044  An error occurred while sending the e-mails. The e-mails were not sent.  Check the SMTP settings and the error message in the system alarm. 70045  Cannot load a file required for encrypting the e-mail.  Update the operating system and Runtime. 70046  The server does not support encryption.  Select an SMTP server that supports encryption. 70047  The SSL versions of the HMI device and SMTP server may not be compatible. Contact your network administrator or the operator of the SMTP server. 80000 - Log alarms   Number  Effect/causes  Remedy 80001  The log specified is filled to the size defined (in percent) and must be stored elsewhere. Store the file or table by executing a ‘move’ or ‘copy’ function. 80002  A line is missing in the specified log.  -- 80003  The copying process for logging was not successful. In this case, it is advisable to check any subsequent system alarms, too. -- 80006  Since logging is not possible, this causes a permanent loss of the functionality. In the case of databases, check whether the corresponding data source exists and start up the system again. 80009  A copying action has been completed successfully.  -- 80010  Since the storage location was incorrectly entered in WinCC flexible, this causes a permanent loss of the functionality. Configure the storage location for the respective log again and restart the system when the full functionality is required. PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 290 Operating Instructions, 08/2010, A5E02453837-01 Number  Effect/causes  Remedy 80012  Log entries are stored in a buffer. If the values are read to the buffer faster than they can be physically written (using a hard disk, for example), overloading may occur and recording is then stopped. Archive fewer values. Or: Increase the logging cycle. 80013  The overload status no longer applies. Archiving resumes the recording of all values. -- 80014  The same action was triggered twice in quick succession. Since the process is already in operation, the action is only carried out once. -- 80015  This system alarm is used to report DOS or database errors to the user. -- 80016  The logs are separated by the system function "CloseAllLogs" and the incoming entries exceed the defined buffer size. All entries in the buffer are deleted. Reconnect the logs. 80017  The number of incoming events cause a buffer overflow. This can be caused, for example, by several copying actions being activated at the same time. All copy jobs in the buffer are deleted. Stop the copy action.  80019  The connection between WinCC flexible and all logs were closed, for example, after executing the system function "CloseAllLogs". Entries are written to the buffer and are then written to the logs when a connection is re-established. There is no connection to the storage location and the storage medium may be replaced, for example. -- 80020  The maximum number of simultaneously copy operations has been exceeded. Copying is not executed. Wait until the current copying actions have been completed, then restart the last copy action. 80021  An attempt was made to delete a log which is still busy with a copy action. Deletion has not been executed. Wait until the current copying actions have been completed, then restart the last action. 80022  An attempt was made to use the system function "StartSequenceLog" to start a sequence log for a log which is not configured as a sequence log. No sequence log file is created. In the project, check  if the "StartSequenceLog" system function was properly configured.  if the tag parameters are properly provided with data on the HMI device. 80023  An attempt was made to copy a log to itself. The log is not copied. In the project, check  if the "CopyLog" system function was properly configured.  if the tag parameters are properly provided with data on the HMI device. 80024  The "CopyLog" system function does not allow copying when the target log already contains data ("Mode" parameter). The log is not copied. Edit the "CopyLog" system function in the project if necessary. Before you initiate the system function, delete the destination log file. 80025  You have canceled the copy operation. Data written up to this point are retained. The destination log file (if configured) is not deleted. The cancellation is reported by an error entry $RT_ERR$ at the end of the destination log. -- PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  291 Number  Effect/causes  Remedy 80026  This alarm is output after all logs are initialized. Values are written to the logs from then on. Prior to this, no entries are written to the logs, irrespective whether WinCC flexible Runtime is active or not. -- 80027  The internal Flash memory has been specified as the storage location for a log. This is not permissible. No values are written to this log and the log file is not created. Configure "Storage Card" or a network path as the storage location. 80028  The alarm returns a status report indicating that the logs are currently being initialized. No values are logged until the alarm 80026 is output. -- 80029  The number of logs specified in the alarm could not be initialized. The logs are initialized.  The faulty log files are not available for logging jobs. Evaluate the additional system alarms related to this alarm. Check the configuration, the ODBC (Open Database Connectivity) and the specified drive. 80030  The structure of the existing log file does not match the expected structure. Logging is stopped for this log. Delete the existing log data manually, in advance. 80031  The log in CSV format is corrupted. The log cannot be used. Delete the faulty file. 80032  Logs can be assigned events. These are triggered as soon as the log is full. WinCC flexible Runtime is started and the log is already full, the event is not triggered. The log specified no longer logs data because it is full.Close WinCC flexible Runtime delete the log, then restart WinCC flexible Runtime. Or: Configure a button which contains the same actions as the event and press it. 80033  "System Defined" is set in the data log file as the data source name. This causes an error. No data is written to the database logs, whereas the logging to the CSV logs works. Reinstall SQL Sever 2005 Express. 80034  An error has occurred in the initialization of the logs. An attempt has been made to create the tables as a backup. This action was successful. A backup has been made of the tables of the corrupted log file and the cleared log was restarted. No action is necessary. However, it is recommended to save the backup files or delete them in order to make the space available again. 80035  An error has occurred in the initialization of the logs. An attempt has been made to create backups of the tables and this has failed. No logging or backup has been performed. It is recommended to save the backups or to delete them in order to release memory. 80044  The export of a log was interrupted because Runtime was closed or due to a power failure. It was detected that the export needed to be resume when Runtime restarted. The export resumes automatically. 80045  The export of a log was interrupted due to an error in the connection to the server or at the server itself. The export is repeated automatically. Check:  The connection to the server.  If the server is running.  If there is enough free space on the server. 80046  The destination file could not be written while exporting the log. Check whether there is enough space on the server and it you have permission to create the log file. 80047  The log could not be read while exporting it.  Check whether the storage medium is correctly inserted. PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 292 Operating Instructions, 08/2010, A5E02453837-01 Number  Effect/causes  Remedy 80049  The log could not be renamed while preparing to export it.  The job can not be completed." Check whether the storage medium is correctly inserted and if there is sufficient space on the medium. 80050  The log which shall be exported is not closed.  The job can not be completed. Make sure the "CloseAllLogs" system function is called before using the "ExportLog" system function. Change the configuration as required. 80051  The log to be copied contains an invalid checksum. The log was not copied. Select a log with a valid checksum. The selected log may have been manipulated. 80052  The log cannot be read.   Check the log and the specified path. 80053  The closed log cannot be read.  Open the log. 90000 - FDA alarms   Number  Effect/causes  Remedy 90024  No operator actions can be logged due to lack of space on the storage medium for log. The operator action will therefore not be executed. Make more space available by inserting an empty storage medium or swapping out the log files on the server using "ExportLog". 90025  No user actions can be logged because of error state of the archive. Therefore the user action will not be executed. Check whether the storage medium is correctly inserted. 90026  No operator actions can be logged because the log is closed. The operator action will therefore not be executed. Before further operator actions are carried out, the log must be opened again using the system function "OpenAllLogs". Change the configuration as required. 90028  The password you entered is incorrect.  Enter the correct password. 90029  Runtime was closed during ongoing operation (perhaps due to a power failure) or a storage medium in use is incompatible with Audit Trail. An Audit Trail is not suitable if it belongs to another project or has already been logged. Ensure that you are using the correct storage medium. 90030  Runtime was closed during ongoing operation (perhaps due to a power failure). -- 90031  Runtime was closed during ongoing operation (perhaps due to a power failure). -- 90032  Running out of space on the storage medium for log.  Make more space available by inserting an empty storage medium or swapping out the log files on the server using "ExportLog". 90033  No more space on the storage medium for log. As of now, no more operator actions requiring logging will be executed. Make more space available by inserting an empty storage medium or swapping out the log files on the server using "ExportLog". 90039  You do not have the necessary authorization to perform this action.  Adapt or upgrade your authorizations. 90040  Audit Trail is switched off because of a forced user action. Activate the "Audit Trail" again using the system function "StartLog". 90041  A user action which has to be logged has been executed without a logged on user. A user action requiring logging should only be possible with permission. Change the configuration by setting a required authorization for the input object. 90044  A user action which has to be confirmed was blocked, because there is another user action pending. Repeat the user action if necessary. PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  293 Number  Effect/causes  Remedy 90048  The Audit Trail cannot be printed while data relevant to the audit is being logged. Stop logging using the system function "StopLogging". 90049  Access to required file is not possible.  Check the network connection or the storage medium. 90056  The recipe was not imported because the file contains no checksum. Select a file with a checksum. As an alternative, disable verification of the checksum by using the system function "ImportDataRecords". 90057  The recipe was not imported because the file contains an invalid checksum. The selected file may have been manipulated. Select a file with a valid checksum. 110000 - Offline function alarms   Number  Effect/causes  Remedy 110000  The operating mode was changed. "Offline" mode is now set. -- 110001  The operating mode was changed. "Online" mode is now set. -- 110002  The operating mode was not changed.  Check the connection to the PLCs. Check whether the address area for the area pointer 88 “Coordination" in the PLC is available. 110003  The operating mode of the specified PLC was changed by the system function "SetConnectionMode". The operating mode is now "offline". -- 110004  The operating mode of the specified PLC has been changed by the system function "SetConnectionMode". The operating mode is now "online". -- 110005  An attempt was made to use the system function SetConnectionMode to switch the specified PLC to "online" mode, although the entire system is in "offline" mode. This changeover is not allowed. The PLC remains in "offline" mode. Switch the complete system to "online" mode, then execute the system function again. 110006  The content of the "project version" area pointer does not match the user version configured in WinCC flexible. WinCC flexible Runtime is therefore closed. Check the following:  The project ID entered on the PLC.  The project ID entered in WinCC flexible. 120000 - Trend alarms   Number  Effect/causes  Remedy 120000  The trend is not displayed because you configured an incorrect axis to the trend or an incorrect trend. Change the configuration. 120001  The trend is not displayed because you configured an incorrect axis to the trend or an incorrect trend. Change the configuration. 120002  The trend is not displayed because the tag assigned attempts to access an invalid PLC address. Check whether the data area for the tag exists in the PLC, the configured address is correct and the value range for the tag is correct. PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 294 Operating Instructions, 08/2010, A5E02453837-01 130000 - System information alarms   Number  Effect/causes  Remedy 130000  The action was not executed.  Close all other programs. Delete files no longer required from the hard disk. 130001  The action was not executed.  Delete files no longer required from the hard disk. 130002  The action was not executed.  Close all other programs. Delete files no longer required from the hard disk. 130003  No data medium found. The operation is canceled.  Check, for example, if  The correct data medium is being accessed  The data medium is inserted 130004  The data medium is write-protected. The operation is canceled. Check whether access has been made to the correct data carrier. Remove the write protection. 130005  The file is read only. The operation is canceled.  Check whether access has been made to the correct file. Edit the file attributes if necessary. 130006  Access to file failed. The operation is canceled.  Check, for example, if  The correct file is being accessed  The file exists  Another action is preventing simultaneous access to the file. 130007  The network connection is interrupted. Records cannot be saved or read over the network connection. Check the network connection and eliminate the cause of error. 130008  The storage card is not available. The specified data records cannot be saved to / read from the storage card. Insert the storage card. 130009  The specified folder does not exist on the storage card. Any files saved to this directory are not backed up when you switch off the HMI device. Insert the storage card. 130010  The maximum nesting depth can be exhausted when, for example, a value change in a script results in the call of another script and the second script in turn has a value change that results in the call of yet a further script etc.  The configured functionality is not supported. Check the configuration. 130013  The storage card is not available. The specified data records cannot be saved to / read from the storage card. Insert the storage card. PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  295 140000 - Connection alarms chns7: Connection + device   Number  Effect/causes  Remedy 140000  An online connection to the PLC is established.  -- 140001  The online connection to the PLC was shut down.  -- 140003  No tag updating or writing is executed.  Check the connection and if the PLC is switched on. Check the parameter definitions in the Control Panel using "Set PG/PC interface". Restart the system. 140004  No tag update or write operations are executed because the access point or the module configuration is faulty. Verify the connection and check whether the PLC is switched on. Check the access point or the module configuration (MPI, PPI, PROFIBUS) in the Control Panel with "Set PG/PC interface". Restart the system. 140005  No tag updating or writing is executed because the HMI device address is incorrect (possibly too high). Use a different HMI device address. Verify the connection and check whether the PLC is switched on. Check the parameter definitions in the Control Panel using "Set PG/PC interface". Restart the system. 140006  No tag updating or writing is executed because the baud rate is incorrect. Select a different baud rate in WinCC flexible (according to module, profile, communication peer, etc.). 140007  Tags are not updated or written because the bus profile is incorrect (see %1). The following parameters could not be written to the registry: 1:  Tslot 2:  Tqui 3:  Tset 4:  MinTsdr 5:  MaxTsdr 6:  Trdy 7:  Tid1 8:  Tid2 9:  Gap Factor 10: Retry Limit Check the user-defined bus profile. Check the connection and if the PLC is switched on. Check the parameter definitions in the Control Panel using "Set PG/PC interface". Restart the system. 140008  No tag updating or writing is executed because baud rate is incorrect. The following parameters could not be written to the registry:  0:  General error 1:  Wrong version 2:  Profile cannot be written to the registry. 3:  The subnet type cannot be written to the registry. 4:  The target rotation time cannot be written to the registry. 5:  Faulty highest address (HSA). Check the connection and if the PLC is switched on. Check the parameter definitions in the Control Panel using "Set PG/PC interface". Restart the system. 140009  Tags are not updated or written because the module for S7 communication was not found. Reinstall the module in the Control Panel using "Set PG/PC interface". PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 296 Operating Instructions, 08/2010, A5E02453837-01 Number  Effect/causes  Remedy 140010  No S7 communication partner found because the PLC is shut down. DP/T: The option “PG/PC is the only master” is not set in the Control Panel under “Set PG/PC interface.” Switch the PLC on. DP/T: If only one master is connected to the network, disable "PG/PC is the only master" in "Set PG/PC interface". If several masters are connected to the network, enable these. Do not change any settings, for this will cause bus errors. 140011  No tag updating or writing is executed because communication is down. Check the connection and that the communication partner is switched on. 140012  There is an initialization problem (e.g. when WinCC flexible Runtime was closed in Task Manager). Or: Another application (e.g.STEP7) with different bus parameters is active and the driver cannot be started with the new bus parameters (transmission rate, for example). Restart the HMI device. Or: Run WinCC flexible Runtime, then start your other applications. 140013  The MPI cable is disconnected and, thus, there is no power supply. Check the connections. 140014  The configured bus address is in already in use by another application. Edit the HMI device address in the PLC configuration. 140015  Wrong transmission rate Or:  Faulty bus parameters (e.g. HSA) Or: OP address > HSA or: Wrong interrupt vector (interrupt does not arrive at the driver) Correct the relevant parameters. 140016  The hardware does not support the configured interrupt. Change the interrupt number. 140017  The set interrupt is in use by another driver.  Change the interrupt number. 140018  The consistency check was disabled by SIMOTION Scout. Only a corresponding note appears. Enable the consistency check with SIMOTION Scout and once again download the project to the PLC. 140019  SIMOTION Scout is downloading a new project to the PLC. Connection to the PLC is canceled. Wait until the end of the reconfiguration. 140020  The version in the PLC and that of the project (FWX file) do not match. Connection to the PLC is canceled. The following remedies are available: Download the current version to the PLC using SIMOTION Scout. Regenerate the project using WinCC flexible ES, close WinCC flexible Runtime and restart with a new configuration. PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  297 150000 - Connection alarms chnAS511: Connection  Number  Effect/causes  Remedy 150000  No more data is read or written. Possible causes:  The cable is defective.  The PLC does not respond, is defective, etc.  The wrong port is used for the connection.  System overload Ensure that the cable is plugged in, the PLC is operational, the correct port is being used. Restart the system if the system alarm persists. 150001  Connection is up because the cause of the interruption has been eliminated. -- 160000 - Connection alarms IVar (WinLC) / OPC: Connection  Number  Effect/causes  Remedy 160000  No more data is read or written. Possible causes:  The cable is defective.  The PLC does not respond, is defective, etc.  The wrong port is used for the connection.  System overload Ensure that the cable is plugged in, the PLC is operational, the correct port is being used. Restart the system if the system alarm persists. 160001  Connection is up because the cause of the interruption has been eliminated. -- 160010  No connection to the server because the server identification (CLS-ID) cannot be determined. Values cannot be read or written. Check access rights. 160011  No connection to the server because the server identification (CLS-ID) cannot be determined. Values cannot be read or written. Check, for example, if  The server name is correct.  The computer name is correct.  The server is registered. 160012  No connection to the server because the server identification (CLS-ID) cannot be determined. Values cannot be read or written. Check, for example, if  The server name is correct.  The computer name is correct.  The server is registered. Note for advanced users: Interpret the value from HRESULT.  160013  The specified server was started as InProc server. This has not been released and may possibly lead to incorrect behavior because the server is running in the same process area as the WinCC flexible Runtime software. Configure the server as OutProc Server or Local Server. 160014  Only one OPC server project can be started on a PC/MP. An alarm is output when an attempt is made to start a second project. The second project has no OPC server functionality and cannot be located as an OPC server by external sources. Do not start a second project with OPC server functionality on the computer. PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 298 Operating Instructions, 08/2010, A5E02453837-01 170000 - S7 dialog alarms   Number  Effect/causes  Remedy 170000  S7 diagnostics events are not indicated because it is not possible to log on to the S7 diagnostics functions at this device. The service is not supported. -- 170001  The S7 diagnostics buffer cannot be viewed because communication with the PLC is shut down. Set the PLC to online mode. 170002  The S7 diagnostics buffer cannot be viewed because reading of the diagnostics buffer (SSL) was canceled with error. -- 170003  An S7 diagnostics event cannot be visualized. The system returns internal error %2. -- 170004  An S7 diagnostics event cannot be visualized. The system returns an internal error of error class %2, error number %3. -- 170007  It is not possible to read the S7 diagnostics buffer (SSL) because this operation was canceled with an internal error of class %2 and error code %3. -- 180000 - Misc/common alarms  Number  Effect/causes  Remedy 180000  A component/OCX received configuration data with a version ID which is not supported. Install a newer component. 180001  System overload because too many actions running in parallel. Not all the actions can be executed, some are rejected. Several remedies are available:  Generate the alarms at a slower rate (polling).  Initiate scripts and functions at greater intervals. If the alarm appears more frequently: Restart the HMI device.  180002  The screen keyboard could not be activated. Possible causes: "TouchInputPC.exe" was not registered due to a faulty Setup. Install WinCC flexible Runtime again. PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  299 190000 - Tag alarms   Number  Effect/causes  Remedy 190000  It is possible that the tag is not updated.  -- 190001  The tag is updated after the cause of the last error state has been eliminated (return to normal operation). -- 190002  The tag is not updated because communication with the PLC is down. Select the system function "SetOnline" to go online. 190004  The tag is not updated because the configured tag address does not exist. Check the configuration. 190005  The tag is not updated because the configured PLC type does not exist for this tag. Check the configuration. 190006  The tag is not updated because it is not possible to map the PLC type in the data type of the tag. Check the configuration. 190007  The tag value is not modified because the connection to the PLC is interrupted or the tag is offline. Set online mode or reconnect to the PLC. 190008  The threshold values configured for the tag have been violated, for example, by  A value entered  A system function  A script Observe the configured or current threshold values of the tag. 190009  An attempt has been made to assign the tag a value which is outside the permitted range of values for this data type. For example, a value of 260 was entered for a byte tag or a value of -3 for an unsigned word tag. Observe the range of values for the data type of the tags. 190010  Too many values are written to the tag (for example, in a loop triggered by a script). Values are lost because only up to 100 actions are saved to the buffer. The following remedies are available:  Increase the time interval between multiple write actions.  Do not use an array tag longer than 6 words when you configure an acknowledgment on the HMI device using "Acknowledgment HMI". 190011  Possible cause 1: The value entered could not be written to the configured PLC tag because the high or low limit was exceeded. The system discards the entry and restores the original value. Possible cause 2: The connection to the PLC was interrupted.  Make sure that the value entered lies within the range of values of the control tags.     Check the connection to the PLC. 190012  It is not possible to convert a value from a source format to a target format, for example: An attempt is being made to assign a value to a counter that is outside the valid, PLC-specific value range. A tag of the type Integer should be assigned a value of the type String. Check the range of values or the data type of the tags. 190013  The user has entered a string that is longer than the tag. The string is automatically shortened to the permitted length. Only enter strings that do not exceed the permitted tag length. PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 300 Operating Instructions, 08/2010, A5E02453837-01 190100 - Area pointer alarms  Number  Effect/causes  Remedy 190100  The area pointer is not updated because the address configured for this pointer does not exist. Type 1  Warnings 2  Errors 3  PLC acknowledgment 4  HMI device acknowledgment 5  LED mapping 6  Trend request 7  Trend transfer 1 8  Trend transfer 2 No.: Consecutive number displayed in WinCC flexible ES. Check the configuration. 190101  The area pointer is not updated because it is not possible to map the PLC type to the area pointer type. Parameter type and no.: see alarm 190100 -- 190102  The area pointer is updated after the cause of the last error state has been eliminated (return to normal operation). Parameter type and no.: See alarm 190100. -- 200000 - PLC coordination alarms  Number  Effect/causes  Remedy 200000  Coordination is not executed because the address configured in the PLC does not exist/is not set. Change the address or set up the address in the PLC. 200001  Coordination is canceled because the write access to the address configured in the PLC is not possible. Change the address or set the address in the PLC at an area which allows write access. 200002  Coordination is not carried out at the moment because the address format of the area pointer does not match the internal storage format. Internal error 200003  Coordination can be executed again because the last error state is eliminated (return to normal operation). -- 200004  The coordination may not be executed.  -- 200005  No more data is read or written. Possible causes:  The cable is defective.  The PLC does not respond, is defective, etc.  System overload Ensure that the cable is plugged in and the PLC is operational. Restart the system if the system alarm persists. PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  301 210000 - PLC job alarms  Number  Effect/causes  Remedy 210000  Jobs are not processed because the address configured in the PLC does not exist/has not been set up. Change the address or set up the address in the PLC. 210001  Jobs are not processed because read/write access to the address configured in the PLC is not possible. Change the address or set up the address in the PLC in an area which allows read/write access. 210002  Jobs are not executed because the address format of the area pointer does not match the internal storage format. Internal error 210003  The job buffer is processed again because the last error status has been eliminated (return to normal operation). -- 210004  It is possible that the job buffer will not be processed.  -- 210005  A control request with an illegal number was initiated.  Check the PLC program. 210006  An error occurred while attempting to execute the control request. As a result, the control request is not executed. Observe the next/previous system alarms. Check the parameters of the control request. Recompile the configuration. 220000 - WinCC channel adapter alarms  Number  Effect/causes  Remedy 220001  The tag is not downloaded because the associated communication driver / HMI device does not support the download of Boolean/discrete data types. Change the configuration. 220002  The tag is not downloaded because the associated communication driver / HMI device does not support write access to the data type BYTE. Change the configuration. 220003  The communication driver cannot be loaded. The driver may not be installed. Install the driver by reinstalling WinCC flexible Runtime. 220004  Communication is down and no update data is transferred because the cable is not connected or defective etc. Check the connection. 220005  Communication is up.  -- 220006  The connection between the specified PLC and the specified port is active. -- 220007  The connection to the specified PLC is interrupted at the specified port. Check whether  The cable is plugged in  The PLC is OK  The correct port is used  Your configuration is OK (port parameters, protocol settings, PLC address). Restart the system if the system alarm persists. 220008  The communication driver cannot access or open the specified port. The port may be in use by another application or the port used is not available on the destination device. There is no communication with the PLC. Close all the applications which access this port and restart the computer. Use another port of the system. PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 302 Operating Instructions, 08/2010, A5E02453837-01 230000 - View alarms  Number  Effect/causes  Remedy 230000  The value entered could not be accepted. The system discards the entry and restores the previous value.  Either   The value range has been exceeded  Illegal characters have been entered  The maximum permitted number of users has been exceeded. Enter a practical value or delete any unneeded users. 230002  The currently logged in user has not the required authorization. The system therefore discards the input and restored the previous value. Log on as a user with appropriate authorization. 230003  Changeover to the specified screen failed because the screen is not available/configured. The current screen remains selected. Configure the screen and check the screen selection function. 230005  The value range of the tag has been exceeded in the I/O field. The original value of the tag is retained. Observe the range of values for the tag when entering a value. 230100  During navigation in the web browser, the system returned a message which may be of interest to the user. The web browser continues to run but may not (fully) show the new page. Navigate to another page. 230200  The connection to the HTTP channel was interrupted due to an error. This error is explained in detail by another system alarm. Data is no longer exchanged. Check the network connection. Check the server configuration. 230201  The connection to HTTP channel was established. Data is exchanged. -- PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  303 Number  Effect/causes  Remedy 230202  WININET.DLL has detected an error. This error is usually generated if it is not possible to connect to the server or if the server denies access because the client could not authenticate itself. A rejected server certificate could also cause a communication error in secure SSL connections. For details, refer to the error text in the alarm. This text is always output in the language of your Windows installation, as it is returned by the Windows operating system. Process values are not exchanged. The part of the alarm which is returned by the Windows operating system may not be displayed, for example "An error has occurred." WININET.DLL returns the following error: Number: 12055 Text:HTTP: <no error text available>." Depending on the cause: When an attempt to connect fails or a timeout error occurs:  Check the network connection and the network.  Check the server address.  Check whether the WebServer is actually running on the destination station. Faulty authorization:  The configured user name and/or password do not match those on the server. Establish consistency When the server certificate is rejected: Certificate signed by an unknown CA ( ):  Either ignore this item in your project, or  Install a certificate that has been signed with a root certificate known to the client computer. The date of the certificate is invalid:  Either ignore this item in your project, or  Install a certificate with a valid date on the server. Invalid CN (Common Name or Computer Name):  Either ignore this item in your project, or  Install a certificate with a name that corresponds to that of the server address. 230203  Although a connection can be made to the server, the HTTP server refuses to connect because  WinCC flexible Runtime is not running on the server or  The HTTP channel is not supported (503 Service unavailable). Other errors can only occur if the Webserver does not support the HTTP channel. The language of the alarm text depends on the Webserver. Data is not exchanged. Error 503 Service unavailable: Check if WinCC flexible Runtime is running on the server and if the HTTP channel is supported. 230301  An internal error has occurred. An English text explains the error in more detail. This may be caused by insufficient memory. OCX does not work. -- 230302  The name of the remote server cannot be resolved. The attempt to connect failed. Check the configured server address. Check whether the DNS service is available on the network. 230303  The remote server is not running on the addressed computer. Wrong server address. The attempt to connect failed. Check the configured server address. Check whether the remote server is running on the target computer. 230304  The remote server on the addressed computer is incompatible with VNCOCX. The attempt to connect failed. Use a compatible remote server. 230305  The authentication has failed because the password is incorrect. The attempt to connect failed. Configure the correct password. PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 304 Operating Instructions, 08/2010, A5E02453837-01 Number  Effect/causes  Remedy 230306  Error in the connection to the remote server. This may occur as a result of network problems. The attempt to connect failed. Check whether  The bus cable is plugged in  There are network problems. 230307  The connection to the remote server was shut down because  The remote server was shut down, or  The user instructed the server to close all connections. The connection is closed. -- 230308  This alarm provides information on the connection status. An attempt is made to connect. -- 240000 - Authorization alarms  Number  Effect/causes  Remedy 240000  WinCC flexible Runtime is operating in demo mode. You have no authorization or your authorization is corrupted. Install the authorization. 240001  WinCC flexible Runtime is operating in demo mode. Too many tags are configured for the installed version. Load an adequate authorization / power pack. 240002  WinCC flexible Runtime is operating with a time-limited emergency authorization. Restore the full authorization. 240004  Error while reading the emergency authorization. WinCC flexible Runtime is operating in demo mode. Restart WinCC flexible Runtime, install the authorization or repair the authorization (see Commissioning Instructions Software Protection). 240005  The Automation License Manager has detected an internal system fault.  Possible causes:  A corrupt file  A defective installation  No free space for the Automation License Manager etc. Reboot the HMI device or PC. If this does not solve the problem, remove the Automation License Manager and install it again. 250000 - S7 Force alarms  Number  Effect/causes  Remedy 250000  The tag in the specified line in "Status Force" is not updated because the address configured for this tag is not available. Check the set address and then verify that the address is set up in the PLC. 250001  The tag in the specified line in "Status Force" is not updated because the PLC type configured for this tag does not exist. Check the set address. PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  305 Number  Effect/causes  Remedy 250002  The tag in the specified line in "Status Force" is not updated because it is not possible to map the PLC type in the tag type. Check the set address. 250003  An attempt to connect to the PLC failed. The tags are not updated. Check the connection to the PLC. Check that the PLC is switched on and is online. 260000 - Password system alarms   Number  Effect/causes  Remedy 260000  An unknown user or an unknown password has been entered in the system. The current user is logged off from the system. Log on to the system as a user with a valid password. 260001  The logged in user does not have sufficient authorization to execute the protected functions on the system. Log on to the system as a user with sufficient authorization. 260002  This alarm is triggered by the system function "TrackUserChange". -- 260003  The user has logged off from the system.  -- 260004  The user name entered into the user view already exists in the user management. Select another user name because user names have to be unique in the user management. 260005  The entry is discarded.  Enter a shorter user name. 260006  The entry is discarded.  Use a shorter or longer password. 260007  The logon timeout value entered is outside the valid range of 0 to 60 minutes. The new value is discarded and the original value is retained. Enter a logon timeout value between 0 and 60 minutes. 260008  An attempt was made to read a PTProRun.pwl file created with ProTool V 6.0 in WinCC flexible. Reading the file was canceled due to incompatibility of the format. -- 260009  You have attempted to delete the user "Admin" or "PLC User". These users are fixed components of the user management and cannot be deleted. If you need to delete a user, because perhaps you have exceeded the maximum number permitted, delete another user. 260012  The passwords entered in the "Change Password" dialog and the confirmation field are not identical. The password has not been changed. User will be logged off. You have to log on to the system again. Then enter the identical password twice to be able to change the password. 260013  The password entered in the "Change Password" dialog is invalid because it is already in use. The password has not been changed. User will be logged off. You have to log on to the system again. Then enter a new password that has not been used before. 260014  You have tried unsuccessfully to log on three times in succession. You will be locked out and assigned to group no. 0. You can log on to the system with your correct password. Only an administrator can change the assignment to a group. 260024  The password you entered does not meet the necessary security guidelines. Enter a password that contains at least one number. 260025  The password you entered does not meet the necessary security guidelines. Enter a password that contains at least one special character. PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 306 Operating Instructions, 08/2010, A5E02453837-01 Number  Effect/causes  Remedy 260028  Upon system start-up, an attempt to log on, or when trying to change the password of a SIMATIC log-on user, the system attempts to access the SIMATIC Logon Server. If attempting to log on, the new user is not logged in. If a different user was logged on before, then this user is logged off. Check the connection to the SIMATIC Logon Server and its configuration; for example: 1. Port number 2. IP address 3. Server name 4. Functional transfer cable Or use a local user. 260030  The SIMATIC Logon user could not change his password on the SIMATIC Logon Server. The new password may not comply with the password regulations on the server or the user does not have the right to change his password. The old password remains and the user is logged off. Log in again and choose a different password. Check the password rules on the SIMATIC Logon Server. 260033  The action change password or log on user could not be carried out. Check the connection to the SIMATIC Logon Server and its configuration; for example: 1. Port number 2. IP address 3. Server name 4. Functional transfer cable Or use a local user. 260034  The last logon operation has not yet ended. A user action or a logon dialog can therefore not be called. The logon dialog is not opened. The user action is not executed. Wait until the logon operation is complete. 260035  The last attempt to change the password was not completed. A user action or a logon dialog can therefore not be called. The logon dialog is not opened. The user action is not executed. Wait until the procedure is complete. 260036  There are insufficient licenses on the SIMATIC Logon Sever. The logon is not authorized. Check the licensing on the SIMATIC Logon Server. 260037  There is no license on the SIMATIC Logon Sever. A logon is not possible. It is not possible to log on via the SIMATIC Logon Server, only via a local user. Check the licensing on the SIMATIC Logon Server. 260040  The system attempts to access the SIMATIC Logon Server upon system start-up or when trying to change the password. If attempting to log on, the new user is not logged in. If a different user was logged on before, then this user is logged off. Check connection to the domain and its configuration in the Runtime security settings editor. Or use a local user. 260043  It was not possible to log the user on to the SIMATIC Logon Server. The user name or the password could be incorrect or the user does not have sufficient rights to log on. The new user is not logged in. If a different user was logged on before, then this user is logged off. Try again. If necessary, check the password data on the SIMATIC Logon Server. PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  307 Number  Effect/causes  Remedy 260044  It was not possible to log the user on to the SIMATIC Logon Server as his account is blocked. The new user is not logged in. If a different user was logged on before, then this user is logged off. Check the user data on the SIMATIC Logon Server. 260045  The SIMATIC Logon user is not associated to any or several groups. The new user is not logged in. If a different user was logged on before, then this user is logged off. Check the user data on the SIMATIC Logon Server and the configuration in your WinCC flexible project. A user may only be assigned to one group. 270000 - System alarms  Number  Effect/causes  Remedy 270000  A tag is not indicated in the alarm because it attempts to access an invalid address in the PLC. Check whether the data area for the tag exists in the PLC, the configured address is correct and the value range for the tag is correct. 270001  There is a device-specific limit as to how many alarms may be queued for output (see the operating instructions). This limit has been exceeded. The view no longer contains all the alarms. However, all alarms are written to the alarm buffer. -- 270002  The view shows alarms of a log for which there is no data in the current project. Wildcards are output for the alarms. Delete older log data if necessary. 270003  The service cannot be set up because too many devices want to use this service. A maximum of four devices may execute this action. Reduce the number of HMI devices which want to use the service. 270004  Access to persistent buffer is not possible. Alarms cannot be restored or saved. If the problems persist at the next startup, contact Customer Support (delete Flash). 270005  Persistent buffer damaged: Alarms cannot be restored.  If the problems persist at the next startup, contact Customer Support (delete Flash). 270006  Project modified: Alarms cannot be restored from the persistent buffer. The project was generated and transferred new to the HMI device; The error should no longer occur when the device starts again. 270007  A configuration problem is preventing the restore (a DLL is missing, a directory is unknown, etc.). Update the operating system and then transfer your project again to the HMI device. PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 308 Operating Instructions, 08/2010, A5E02453837-01 280000 - DPHMI alarms Connection  Number  Effect/causes  Remedy 280000  Connection is up because the cause of the interruption has been eliminated. -- 280001  No more data is read or written. Possible causes:  The cable is defective  The PLC does not respond, is defective, etc.  The wrong port is used for the connection  System overload Check whether  The cable is plugged in  The PLC is OK  The correct port is used. Restart the system if the system alarm persists. 280002  The connection used requires a function block in the PLC.  The function block has responded. Communication is now enabled. -- 280003  The connection used requires a function block in the PLC.  The function block has not responded. Check whether  The cable is plugged in  The PLC is OK  The correct port is used. Restart the system if the system alarm persists. Remedy depends on the error code: 1:  The function block must set the COM bit in the response container. 2:  The function block must not set the ERROR bit in the response container. 3:  The function block must respond within the specified time (timeout). 4:  Go online to the PLC. 280004  The connection to the PLC is interrupted. There is no data exchange at present. Check the connection parameters in WinCC flexible.Ensure that the cable is plugged in, the PLC is operational, the correct port is being used. Restart the system if the system alarm persists. PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  309 290000 - Recipe system alarms  Number  Effect/causes  Remedy 290000  The recipe tag could not be read or written. It is assigned the start value. The alarm can be entered in the alarm buffer for up to four more failed tags if necessary. After that, alarm 290003 is output. Check in the configuration that the address has been set up in the PLC. 290001  An attempt has been made to assign a value to a recipe tag which is outside the value range permitted for this type. The alarm can be entered in the alarm buffer for up to four more failed tags if necessary. After that, alarm 290004 is output. Observe the value range for the tag type. 290002  It is not possible to convert a value from a source format to a target format. The alarm can be entered in the alarm buffer for up to four more failed recipe tags if necessary. After that, alarm 290005 is output. Check the value range or type of the tag. 290003  This alarm is output when alarm number 290000 is triggered more than five times. In this case, no further separate alarms are generated. Check in the configuration that the tag addresses have been set up in the PLC. 290004  This alarm is output when alarm number 290001 is triggered more than five times. In this case, no further separate alarms are generated. Observe the value range for the tag type. 290005  This alarm is output when alarm number 290002 is triggered more than five times. In this case, no further separate alarms are generated. Check the value range or type of the tag. 290006  The threshold values configured for the tag have been violated by values entered. Observe the configured or current threshold values of the tag. 290007  There is a difference between the source and target structure of the recipe currently being processed. The target structure contains an additional data recipe tag which is not available in the source structure. The data recipe tag specified is assigned its start value. Insert the specified data recipe tag in the source structure. 290008  There is a difference between the source and target structure of the recipe currently being processed. The source structure contains an additional data recipe tag which is not available in the target structure and therefore cannot be assigned. The value is rejected. Remove the specified data recipe tag in the specified recipe from the project. 290010  The storage location configured for the recipe is not permitted. Possible causes: Illegal characters, write protection, data carrier out of space or does not exist. Check the configured storage location. 290011  The record with the specified number does not exist. Check the source for the number (constant or tag value).290012  The recipe with the specified number does not exist.  Check the source for the number (constant or tag value).PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 310 Operating Instructions, 08/2010, A5E02453837-01 Number  Effect/causes  Remedy 290013  An attempt was made to save a record under a record number which already exists. The action is not executed. The following remedies are available:  Check the source for the number (constant or tag value).  First, delete the record.  Change the "Overwrite" function parameter. 290014  The file specified to be imported could not be found.  Check:  The file name  Ensure that the file is in the specified directory. 290020  Alarm reporting that the download of records from the HMI device to the PLC has started.  -- 290021  Alarm reporting that the download of records from the HMI device to the PLC was completed. -- 290022  Alarm reporting that the download of records from the HMI device to the PLC was canceled due to an error. Check in the configuration whether:  The tag addresses are configured in the PLC  The recipe number exists  The record number exists  The "Overwrite" function parameter is set 290023  Alarm reporting that the download of records from the PLC to the HMI device has started. -- 290024  Alarm reporting that the download of records from the PLC to the HMI device was completed. --- 290025  Alarm reporting that the download of records from the PLC to the HMI device was canceled due to an error. Check in the configuration whether:  The tag addresses are configured in the PLC  The recipe number exists  The record number exists  The "Overwrite" function parameter is set 290026  An attempt has been made to read/write a record although the record is not free at present. This error may occur in the case of recipes for which downloading with synchronization has been configured. Set the record status to zero. 290027  Unable to connect to the PLC at present. As a result, the record can neither be read nor written. Possible causes: No physical connection to the PLC (no cable plugged in, cable is defect) or the PLC is switched off. Check the connection to the PLC. 290030  This alarm is output after you selected screen which contains a recipe view in which a record is already selected. Reload the record from the storage location or retain the current values. 290031  While saving, it was detected that a record with the specified number already exists. Overwrite the record or cancel the action. 290032  While exporting records it was detected that a file with the specified name already exists. Overwrite the file or cancel the process. 290033  Confirmation request before deleting records.  -- PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  311 Number  Effect/causes  Remedy 290040  A record error with error code %1 that cannot be described in more detail occurred. The action is canceled. It is possible that the record was not installed correctly on the PLC. Check the storage location, the record, the "Data record" area pointer and if necessary, the connection to the PLC. Restart the action after a short time. If the error persists, contact Customer Support. Forward the relevant error code to Customer Support. 290041  A record or file cannot be saved because the storage location is full. Delete files no longer required. 290042  An attempt was made to execute several recipe actions simultaneously. The last action was not executed. Trigger the action again after waiting a short period. 290043  Confirmation request before storing records.  -- 290044  The data store for the recipe has been destroyed and is deleted. -- 290050  Alarm reporting that the export of records has started. -- 290051  Alarm reporting that the export of records was completed. -- 290052  Alarm reporting that the export of records was canceled due to an error. Ensure that the structure of the records at the storage location and the current recipe structure on the HMI device are identical. 290053  Alarm reporting that the import of records has started. -- 290054  Alarm reporting that the import of records was completed. -- 290055  Alarm reporting that the import of records was canceled due to an error. Ensure that the structure of the records at the storage location and the current recipe structure on the HMI device are identical. 290056  Error when reading/writing the value in the specified line/column. The action was canceled. Check the specified line/column. 290057  The tags of the recipe specified were toggled from "offline" to "online" mode. Each change of a tag in this recipe is now immediately downloaded to the PLC. -- 290058  The tags of the specified recipe were toggled from "offline" to "online" mode. Modifications to tags in this recipe are no longer immediately transferred to the PLC but must be transferred there explicitly by downloading a record. -- 290059  Alarm reporting that the specified record was saved.  -- 290060  Alarm reporting that the specified record memory was cleared. -- 290061  Alarm reporting that clearing of record memory was canceled due to an error. -- 290062  The record number is above the maximum of 65536.This record cannot be created. Select another number. PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 312 Operating Instructions, 08/2010, A5E02453837-01 Number  Effect/causes  Remedy 290063  This occurs with the system function "ExportDataRecords" when the parameter "Overwrite" is set to No.  An attempt has been made to save a recipe under a file name which already exists. The export is canceled. Check the "ExportDataRecords" system function. 290064  Alarm reporting that the deletion of records has started. -- 290065  Alarm reporting that the deletion of records has successfully completed. -- 290066  Confirmation request before deleting records.  -- 290068  Security request to confirm if all records in the recipe should be deleted. -- 290069  Security request to confirm if all records in the recipe should be deleted. -- 290070  The record specified is not in the import file.  Check the source of the record number or record name (constant or tag value). 290071  During the editing of record values, a value was entered which exceeded the low limit of the recipe tag. The entry is discarded. Enter a value within the limits of the recipe tag. 290072  When editing record values, a value was entered which exceeds the high limit of the recipe tag. The entry is discarded. Enter a value within the limits of the recipe tag. 290073  An action (e.g. saving a record) failed due to an unknown error. The error corresponds to the status alarm IDS_OUT_CMD_EXE_ERR in the large recipe view. -- 290074  While saving, it was detected that a record with the specified number already exists but under another name. Overwrite the record, change the record number or cancel the action. 290075  A record with this name already exists. The record is not saved. Please select a different record name. 290110  The default values could not be set due to an error.  -- 290111  The Recipes subsystem cannot be used. Recipe views have no content and recipe-specific functions will not be performed. Possible causes:  An error occurred while transferring the recipes.  The recipe structure was changed in ES. When the project was downloaded again, the recipes were not transferred with it. This means that the new configuration data is not being transferred to the old recipes on the device. Transfer the project to the device again, together with the recipes (the corresponding check box in the Transfer dialog must be checked). PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  313 300000 - Alarm_S alarms  Number  Effect/causes  Remedy 300000  Faulty configuration of process monitoring (e.g. using PDiag or S7 Graph): More alarms are queued than specified in the specifications of the CPU. No further ALARM_S alarms can be managed by the PLC and reported to the HMI devices. Change the PLC configuration. 300001  ALARM_S is not registered on this PLC.  Select a controller that supports the ALARM_S service. 310000 - Report system alarms  Number  Effect/causes  Remedy 310000  An attempt is being made to print too many reports in parallel. Only one log file can be output to the printer at a given time; the print job is therefore rejected. Wait until the previous active log was printed. Repeat the print job if necessary. 310001  An error occurred on triggering the printer. The report is either not printed or printed with errors. Evaluate the additional system alarms related to this alarm. Repeat the print job if necessary. PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 314 Operating Instructions, 08/2010, A5E02453837-01 320000 - Alarms  Number  Effect/causes  Remedy 320000  The movements have already been indicated by another device. The movements can no longer be controlled. Deselect the movements on the other display units and select the motion control screen on the required display unit. 320001  The network is too complex. The faulty addresses cannot be indicated. View the network in STL. 320002  No diagnosable alarm message (error) selected. The unit associated with the alarm message could not be selected. Select a diagnostics alarm from the ZP_ALARM alarm screen. 320003  No alarm message (error) exists for the selected unit. The detail view cannot visualize any networks. Select the defective unit from the overview screen. 320004  The required signal states could not be read by the PLC. The faulty addresses cannot be found. Check the consistency between the configuration on the display unit and the PLC program. 320005  The project contains ProAgent elements which are not installed. ProAgent diagnostic functions cannot be performed In order to run the project, install the optional ProAgent package. 320006  You have attempted to execute a function which is not supported in the current constellation. Check the type of the selected unit. 320007  No error-triggering addresses were found on the networks. ProAgent cannot indicate any faulty addresses. Switch the detail screen to STL layout mode and check the status of the addresses and exclusion addresses. 320008  The diagnostic data stored in the configuration are not synchronized with those in the PLC. ProAgent can only indicate the diagnostic units. Transfer the project to the HMI device again. 320009  The diagnostic data stored in the configuration are not synchronized with those in the PLC. The diagnostic screens can be operated as usual.  ProAgent may be unable to show all diagnostic texts. Transfer the project to the HMI device again. 320010  The diagnostic data stored in the configuration are not synchronized with those in STEP7. The ProAgent diagnostics data is not up-to-date. Transfer the project to the HMI device again. 320011  A unit with the corresponding DB number and FB number does not exist. The function cannot be executed. Check the parameters of the "SelectUnit" function and the units selected in the project. 320012  The "Step sequence mode" dialog is no longer supported. Use the ZP_STEP step sequence screen from the corresponding standard project for your project. Instead of calling the Overview_Step_Sequence_Mode function, call the "FixedScreenSelection" function using ZP_STEP as the screen name. 320014  The selected PLC cannot be evaluated for ProAgent. The Alarm view assigned to the "EvaluateAlarmDisplayFault" system function could not be found. Check the parameters of the "EvaluateAlarmDisplayFault" system function. PRELIMINARY II 1.7.2010
 Appendix  A.5 System alarms Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  315 330000 - GUI alarms  Number  Effect/causes  Remedy 330022  Too many dialogs are open on the HMI device.  Close all dialogs you do not require on the HMI device. 330026  The password will expire after the number of days shown. Enter a new password. 350000 - GUI alarms  Number  Effect/causes  Remedy 350000  PROFIsafe packages have not arrived within the necessary period. There is a communication problem with the F-CPU.  RT is terminated. Check the WLAN connection. 350001  PROFIsafe packages have not arrived within the necessary period. There is a communication problem with the F-CPU. The PROFIsafe connection is re-established. Check the WLAN connection. 350002  An internal error has occurred. Runtime is terminated. Internal error 350003  Feedback concerning the connection established with the F-CPU. The Emergency-Off buttons are active immediately. -- 350004  PROFIsafe communication was set and the connection was cleared. The Runtime can be terminated. The Emergency-Off buttons are deactivated immediately. -- 350005  Incorrect address configured for the F-slave. No PROFIsafe connection. Check and modify the address of the F slave in WinCC flexible ES. 350006  The project has started. At the start of the project, the enabling buttons must be checked for functionality.  Press the two enabling buttons one after another in the "Enable" and "Panic" positions. 350008  The wrong number of fail-safe buttons was configured. No PROFIsafe connection. Change the number of fail-safe buttons in the project. 350009  The device is in Override mode.  It may no longer be possible to detect the location because transponder detection fails. Exit Override mode. 350010  Internal error: The device has no fail-safe buttons.  Send the device back. Worldwide contact person     PRELIMINARY II 1.7.2010
Appendix   A.5 System alarms  Wireless Teach Pendant F IWLAN V2 316 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010
 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  317 Abbreviations B  CPU  Central Processing Unit CRC  Cyclic redundancy check CSV  Comma Separated Values DC  Direct Current DHCP  Dynamic Host Configuration Protocol DNS   Domain Name System DP  Distributed I/O IO  Input and Output EAP  Extensible Authentication Protocol ESD  Components and modules endangered by electrostatic discharge EMC  Electromagnetic Compatibility EN  European standard ES  Engineering System ESD  Components and modules endangered by electrostatic discharge F-CPU  Fail-safe Central Processing Unit (fail-safe PLC) GND  Ground HF  High Frequency HMI  Human Machine Interface IEC  International Electronic Commission  IEEE  Institute of Electrical and Electronics Engineers IP  Internet Protocol IWLAN  Industrial Wireless Local Area Network LAN  Local Area Network LED  Light Emitting Diode MAC  Media Access Control MPI  Multipoint Interface (SIMATIC S7) MS  Microsoft MTBF  Mean Time Between Failures n. c.  Not connected OP  Operator Panel PC  Personal Computer PG  Programming device PELV  Protective Extra Low Voltage PPI  Point-to-Point Interface (SIMATIC S7) RAM  Random Access Memory RJ45  Registered Jack Type 45 PRELIMINARY II 1.7.2010
Abbreviations      Wireless Teach Pendant F IWLAN V2 318 Operating Instructions, 08/2010, A5E02453837-01 SAR  Specific absorption rate SD  Security Digital SIL  Safety Integrity Level SP  Service Pack PLC  Programmable Logic Controller SSID  Service set identifier TAB  Tabulator TCP/IP  Transmission Control Protocol/Internet Protocol TFT  Thin Film Transistor TIA  Totally Integrated Automation TLS  Transport Layer Security UL  Underwriter’s Laboratory USB  Universal Serial Bus WAP  Wireless Access Point WLAN  Wireless Local Area Network WINS  Windows Internet Naming Service PRELIMINARY II 1.7.2010
 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  319 Glossary "Transfer" mode "Transfer" is an operating mode of the HMI device in which an executable project is transferred from the configuration PC to an HMI device. Access point See Wireless access point. Ad hoc network An ad hoc network in information technology refers to a wireless network between two or more mobile devices, for which no fixed infrastructure is necessary. This technique is used with Bluetooth, for example, to spontaneously link mobile phones. Ad hoc mode is also possible for WLAN. Alarm logging Output of user-specific alarms to a printer, in parallel to their output to the HMI device screen. Alarm, acknowledging an Acknowledgment of an alarm confirms that it has been noted. Alarm, coming in Moment at which an alarm is triggered by the PLC or HMI device. Alarm, going out Moment at which the initiation of an alarm is reset by the PLC. Alarm, user-specific An alarm is configurable object. A user-specific alarm designates a certain operating status of the plant connected to the HMI device via the PLC. Automation system An automation system is a controller of the SIMATIC S7 series, such as a SIMATIC S7-300. PRELIMINARY II 1.7.2010
Glossary      Wireless Teach Pendant F IWLAN V2 320 Operating Instructions, 08/2010, A5E02453837-01 Bootloader Used to start the operating system. Automatically started when the HMI device is switched on. After the operating system has been loaded, the Loader opens. Configuration PC A configuration PC is a programming device or PC on which HMI projects are created for a plant with a configuration software. CRC Test values contained in a safety message frame can be backed up as follows: ●  The validity of the process values contained in the safety message frame ●  The accuracy of the assigned address relationships ●  The safety-related parameters Display duration Defines whether a system alarm is displayed on the HMI device and the duration of the display. Engineering software Use the configuration software to create a project for process visualization. WinCC flexible, for example, is such a configuration software. Event An event is configurable object. Functions are triggered by defined incoming events. Events which can be assigned to a button include "Press" and "Release", for example. Fail-safe Ability of a technical system to remain in a safe operating state or switch to another safe operating state immediately after certain failures occur. Fail-safe operation Operating mode of the HMI device in which safety-related communication can be performed via safety message frames. Fail-safe system, F system A fail-safe system is used to control production processes by achieving a safe operating state immediately after shutdown. In other words, fail-safe systems control processes in which an immediate shutdown does not endanger people or the environment. Fail-safe systems are used in plants requiring higher levels of safety. PRELIMINARY II 1.7.2010
 Glossary   Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  321 Field array A field is configurable object. A reserved area is used for the input and output of values. Flash memory Non-volatile memory with EEPROM chips, used as mobile storage medium or as memory module installed permanently on the motherboard. Half Brightness Life Time Time period after which the brightness reaches 50% of the original value. The specified value is dependent on the operating temperature. HMI device An HMI device is used for operation and monitoring of production processes. The operating states of the plant are visually depicted on the HMI device. Operator controls on the HMI device enable intervention in the production process of the plant.  HMI device image An HMI device image is a file that can be transferred from the configuration PC to the HMI device. An HMI device image contains the operating system for a specific HMI device and the runtime components required for the executable project file. HMI screen The HMI screens on the HMI device visualize the production process. The HMI screens are configured with WinCC flexible and will be available on the HMI device once the project has been transferred to the HMI device. Infotext Infotext is configurable object. It displays information about other objects within a project. Infotext for an alarm, for example, may contain information on the cause of the fault and troubleshooting routines. Infrastructure mode An infrastructure network is a wireless LAN, which enables communication among the various devices through a central wireless access point. The terminal devices must log on with their MAC address to the wireless access point and get an IP address assigned, if a DHCP server responds to the requesting device. PRELIMINARY II 1.7.2010
Glossary      Wireless Teach Pendant F IWLAN V2 322 Operating Instructions, 08/2010, A5E02453837-01 IO field An IO field is configurable object. It enables values to be entered on the HMI device and transferred to the controller, and values to be output from the controller. IO field, symbolic A symbolic IO field is configurable object. It enables values to be entered on the HMI device and transferred to the controller, and values to be output from the controller. Contains a list of default entries from which one can be selected. IT system This is a particular type of ground connection in a distribution system in electrical engineering for increased resistance to isolation errors. Object An object is a configuration component of a project, for example, a screen, alarm or IO field. Operating element Component of a project used to enter values and trigger functions. A operator control is a button, for example. PLC A PLC is a general term for devices and systems with which the HMI device communicates, for example SIMATIC S7. PLC job A PLC job triggers a function for the PLC at the HMI device. Process image The process image is a memory area in the controller which the HMI device and controller access together. At the beginning of the cyclic control program the signal states of the inputs of the HMI device are transferred to the controller via the process input images, PII. At the end of the cyclic program the process image of the outputs, PIQ is transferred as a signal state to the HMI device. Process visualization Visualization of technical processes by means of text and graphic elements. Configured plant screens allow operator intervention in active production processes by means of the input and output of data. PRELIMINARY II 1.7.2010
 Glossary   Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  323 PROFINET Within the framework of Totally Integrated Automation, PROFINET represents an enhancement of the following bus systems:  ●  PROFIBUS DP as well-established fieldbus ●  Industrial Ethernet as the communication bus on the device level The experience gained from both systems has been and continues to be integrated in PROFINET. PROFINET as an Ethernet-based automation standard from PROFIBUS International defines a vendor-independent communications and engineering model. PROFINET IO controller Device used to address the connected IO devices. This means the IO controller exchanges input and output signals with assigned field devices. The IO controller is often a PLC.  PROFINET IO device A distributed field device that is assigned to one of the IO controllers (e.g. remote IO, valve terminals, frequency converters, switches) PROFINET IO As part of PROFINET, PROFINET IO is a communication solution that is used to implement modular, distributed applications.  PROFINET IO allows you to create automation solutions of the type with which you are familiar from PROFIBUS. PROFINET IO is implemented by the PROFINET standard for automation devices on the one hand, and on the other hand by the STEP 7 engineering software. This means that you have the same application view in STEP 7 regardless of whether you configure PROFINET or PROFIBUS devices. The programming in the user program is similar for PROFINET IO and PROFIBUS DP, provided you use the expanded blocks and system status lists for PROFINET IO. PROFIsafe A fail-safe bus profile from PROFINET for communication between the safety program and the F-I/O in a fail-safe system. PROFIsafe address Every F-I/O has a PROFIsafe address. The F-I/O uses this address to receive safety message frames from the F-CPU or send safety message frames to the F-CPU. PRELIMINARY II 1.7.2010
Glossary      Wireless Teach Pendant F IWLAN V2 324 Operating Instructions, 08/2010, A5E02453837-01 Project A project is the result of a configuration using an configuration software. The project normally contains several HMI screens, in which plant-specific objects are embedded. If it has been configured in WinCC flexible, the project is saved in a project file with the file name extension, "hmi". You need to distinguish between the project on the configuration PC and the runtime project on an HMI device. A project on the configuration PC may have more languages than can be managed on the HMI device. The project on the configuration PC can also be set up for different HMI devices. Only the runtime project that has been generated for the respective HMI device can be transferred to it. Project file File generated from the runtime project file for use on the HMI device. The project file is usually not transferred and remains on the configuration PC.  The file name extension of a project file is *.hmi. Project file, compressed Compressed format of the project file. The compressed project file can be transferred together with the runtime project file to the respective HMI device. Backtransfer must be enabled on the configuration PC for this purpose. The compressed project file is usually saved to an external storage medium. The file extension of a compressed project file is *.pdz. Proof-test interval A period after which a component must be set to a safe state. Either the component is replaced by an unused component or full, error-free operation must be demonstrated. Recipe A recipe is a configurable component of a project. A recipe assembles variables in a fixed data structure. The corresponding data structure can be filled with data in the configuration software or on an HMI device. Using a recipe ensures that all assigned data is transferred to the PLC synchronously during the transfer of a data record. Runtime You need the Runtime software to run a project you have created with WinCC flexible on a PC or HMI device. PRELIMINARY II 1.7.2010
 Glossary   Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  325 Runtime project file A runtime project file is a file that is generated from the finished project file for a specific HMI device based on the configuration. It can therefore only be run on a particular HMI device type. The runtime project file is transferred to the corresponding HMI device and used there to operate and monitor a production process. The file extension of a runtime project file is "fwx". Safe operating state An operating state of a visualization unit which achieves safety. This is define by the absence of safety-related failures. It is defined by the acceptably low risk achieved with the protective measures taken against potential safety-related failures. The basic principle of the safety concept in a fail-safe system is the existence of a safe operating state for all process variables. Safety function A safety system integrated in F-I/Os and F-CPUs, enabling them to be used in fail-safe systems. According to IEC 61508, a safety function is implemented by a safety mechanism to ensure that the plant is kept in a safe operating state or brought into a safe operating state in the event of a fault (user safety function). Safety Integrity Level Safety Integrity Level (safety class) according to IEC 61508 and prEN 50129.  The higher the safety integrity level, the greater the measures required for fail-safe operation in order to avoid systematic errors and bring systematic errors and random equipment failure under control. Safety-related communication Communication used for fail-safe data communication. Screen See HMI screen. Screen object A screen object is a configurable object used to display or operate the plant, for example, a rectangle, I/O field or alarm view. STEP 7 STEP 7 is the programming software for SIMATIC S7, SIMATIC C7 and SIMATIC WinAC PLCs. PRELIMINARY II 1.7.2010
Glossary      Wireless Teach Pendant F IWLAN V2 326 Operating Instructions, 08/2010, A5E02453837-01 System alarm A system alarm is assigned to the "System" alarm class. A system alarm refers to internal states on the HMI device and the PLC.  Tab sequence The tab order is the configured order of the objects that are accessed by successively pressing the "TAB" key. Tag Defined memory location to which values can be written to and read from. This can be done from the PLC or the HMI device. Based on whether the tag is interconnected with the PLC or not, we distinguish between "external" tags (process tags) and "internal" tags. Transfer Transfer of a runtime project from the configuration PC to the HMI device. Transponder A transponder is a – usually wireless – communication, display or control device that receives incoming signals and automatically responds to them. The term transponder is derived from transmitter and responder. Transponders can be passive or active. Wireless access point A wireless access point is an electronic device that acts as an interface for wireless communication devices. Terminal devices provide a wireless connection to the wireless access point via wireless adapter, which in turn is connected by cable to an installed communication network. PRELIMINARY II 1.7.2010
 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  327 Index A Acceptance, 203 F-CPU, 203 F-I/O, 203 Plant, 203 Safety program, 204 Acoustics Feedback, 132 Ad hoc network, 51 Adapting Project, 181 Address assignment TCP/IP network, 146 Admin, 233, 234 Alarm Functional scope, 23 Alarm buffer Functional scope, 23 ALARM_S, 23 Ambient condition climatic RFID tag, 50 Climatic, docking station, 50 Climatic, HMI device, 49 Mechanical, HMI device, 49 Application case Communication errors with integrated HMI device, 256 Communication errors with logged on HMI device, 263 Enabling button askew, 258 Enabling button defective, 259 Integrating the HMI device, 255 Logging off the machine, 264 Logon, 261 Switch on the HMI device., 254 Approvals Australia, 37 CE, 36 UL approval, 37 Wireless approval, 37 Authentication, 61 Authorization, 227 Automation system Fail-safe, 32 B Backlighting Reducing, 128 Backtransfer, 184, 185 Backup, 156, 157, 182, 187, 188, 190, 228 Registry information, 133 Temporary files, 133 To external storage device, 156 With ProSave, 190 With WinCC flexible, 188 Band 5 GHz, 58 Battery Used, 5 Bit assignment Direct key, 94 Booting, 113 Brightness Changing, 108 Byte assignment Direct keys, 94 C Calibrating Touch screen, 111 Cancel Transfer, 81 Care, 237 Carrying strap, 14 CE approval, 36 Certificate Requesting, 37 Certificates Stores, 154 Changing Brightness, 108 User data, 233 Character repeat Screen keyboard, 109 Charge Electrostatic, 251 Charge level Rechargeable battery, 138 Charger Connecting, 75 PRELIMINARY II 1.7.2010
Index    Wireless Teach Pendant F IWLAN V2 328 Operating Instructions, 08/2010, A5E02453837-01 Specifications, 249 Checklist Configuration, 167 Fail-safe, 162 Information security, 60 Clearance Docking station, 57 Climatic Transport conditions, 46 COM LED, 85 Commissioning, 183, 199 Communication HMI device and controller, 163 Communication error, 256 Application case, 263 Communication link with controller Number, 22 Compatibility conflict, 187, 191 Computer name For network operation, 145 Unique, 145 Computers Addressing, 144 Condensation, 46 Configuration Checklist, 167 Configuration example, 268 Configuration graphic Configuration PC, 78 PLC to Teach Pendant, 77 Configuration PC, 26 Configuration graphic, 78 Connecting, 78 Configuration phase, 26 Configure Screen keyboard, 107 Connecting Charger, 75 Configuration PC, 78 PLC, 77 Power supply unit, 65 USB device, 80 Connection compartment, 68 Contact person, 5 Control Panel Open, 102 Operating, 100 Password protection, 98 Screen keyboard,  Convention Style, 4 Term, 4 Cookie, 153 Creating Users, 231 D Data channel Enabling, 142 Locking, 142 Parameter assignment, 142 Date Setting, 125 Synchronizing, 126 Date format, 127 Date/time properties, 125 Declarations of Conformity, 37 Default Gateway, 147 Degree of protection, 51 Delay time Setting, 131 Delete Certificate, 154 Users, 234 DHCP, 146 Diagnostics HMI device, 204 Internal error, 205 Reading information, 204 Direct key, 94 Bit assignment, 94 Byte assignment, 94 Configuring, 219 Functional scope, 25 Disabling SecureMode, 101 Discrepancy error Enabling button askew, 258 Enabling button defective, 259 Display HMI device, 244 Displaying Displaying information about the HMI device, 135 Infotext, 223 Memory information, 134 System information, 134 Disposal, 5 Disturbance variable Pulse-shaped, 44 Sinusoidal, 45 DNS, 147 Server,  PRELIMINARY II 1.7.2010
 Index   Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  329 Docking station Clearance, 57 EMC-compliant installation, 44 Main dimensions, 242 Mounting location, 56 Mounting position, 64 Documentation SIMATIC complete, 5 Double-click Setting, 110 E EC Declaration of Conformity, 37 Editor System alarms, 283 Effective range RFID tag, 54 Specifications, 250 Electrostatic charge, 251 EMC Guideline, 36 EMERGENCY STOP, 33 EMERGENCY STOP button Not active, 41 Not available, 41 Operating, 41, 89 Out of service, 41 Release, 90 Requirements, 41 Emission, 40, 45 Enabling SecureMode, 101 Enabling button, 258 Panic activation, 92 Switch settings, 92 Enabling device, 42 Encryption protocol, 153 Entering data, 222 Error Internal, 235 Error code Discrepancy error, 206 Error code message, 235 Internal error, 205 Error message Error code message, 235 Ethernet settings IP address, 146 Evaluation Operator control, 93 Example of an application Components, 270 Flowchart, 269 HW Config, 270 Safety program, 274 Extended user view, 229 F F_Block_ID, 165 F_Dest_Add, 165 F_FB_MP, 171 F_FB_RGN_n, 174 F_FB_RNG_n, 175 F_Par_Version, 165 F_SIL, 165 F_Source_Add, 165 F_WD_Time, 165 Factory setting, 194 Restoring, 79 With ProSave, 197 With WinCC flexible, 195 Fail-safe Automation system, 32 Checklist, 162 Operation, 245 Fail-safe block, 166, 168 Fail-safe operation, 22, 32, 207, 253 F-application block, 168 FB Interconnect, 170 F-CPU Acceptance, 203 Feedback Acoustic, 132 Optical, 218 F-FB, 166 F-I/O Acceptance, 203 Firmware, 137 Fixing pocket Main dimensions, 243 Front view, 14 Function Additional, 25 Testing, 92 Functional scope Alarm buffer, 23 ALARM_S, 23 Alarms, 23 Device-specific, 25 Graphics list, 23 Infotext, 25 PRELIMINARY II 1.7.2010
Index    Wireless Teach Pendant F IWLAN V2 330 Operating Instructions, 08/2010, A5E02453837-01 Limit value monitoring, 23 Log, 24 Recipe, 24 RFID tag system, 26 Safety, 25 Scaling, 23 Screen, 24 Tag, 23 Text list, 23 G Global rampdown, 33 Graphics list Functional scope, 23 Grip strap, 14 GSDML file, 163 H Hidden SSID, 60 High frequency radiation, 36 HMI device Displaying information, 135 During operation, 207 Enabling button, 91 Holding, 95, 96 Integrating, 209, 209 LED display, 85 Logoff, 32 Logon, 32 Operating, 95 Ports, 68 Remove, 213 Restart, 113 Switch off, 82 Switching on, 81 Usage, 40 HMI device antenna, 245 HMI Input Panel Options, 107 Homepage Internet, 151 HW Config HMI device display, 163 I I/O F_FB_MP, 172 F_FB_RNG_n, 176 I/O DB, 170 Identification, 148 Illuminated pushbutton Operating, 93 Illustration, 4 Importing Certificate, 154 Industry Portal, 5 Information For the HMI device, 135 Information security, 60 Checklist, 60 Infotext Displaying, 223 Functional scope, 25 Input F_FB_MP, 172 F_FB_RNG_n, 176 Input unit HMI device, 244 Installation EMC-compatible, 44 RFID tag, 64 Installation according to the instructions, 35 insulation resistance, 50 Integrating, 255 Application case, 255 Internal error, 205 Diagnostics, 205 Internet E-mail, 149 Homepage, 151 Internet browser, 151 Internet Explorer, 99 Internet options Advanced, 153 Connection, 152 General, 151 Privacy, 153 IP address Ethernet, 146 iPCF, 29 iPCF-MC, 29 iWLAN, 27 K Keyboard External, 100, 217 Knowledge Required, 3 PRELIMINARY II 1.7.2010
 Index   Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  331 L Language change Functional scope, 25 LED BAT, 86 COM, 85 Meaning, 85 PWR, 85 RNG, 85 SAFE, 85 LED display HMI device, 85 Main rechargeable battery, 76 License information, 137 Limit value monitoring Functional scope, 23 Loader Buttons, 98 Local rampdown, 33 Log Functional scope, 24 Logoff Application case, 264 Automatic, 32 Forced, 32 HMI device, 32 Users, 231 Logoff time, 227 Logon Application case, 261 HMI device, 32 Users, 230 Logon data, 148 M MAC address, 139 Main dimensions Docking station, 242 Fixing pocket, 243 Spacer, 243 Wireless Teach Pendant F IWLAN, 241 Main rechargeable battery, 76 Charge level, 138 Insert, 74 Removing, 74, 76 Replacing, 73 Temperature, 138 Maintenance, 237 Manual Scope, 3 Transfer, 184 Measures Organizational, 207 Mechanical Transport conditions, 46 Membrane keyboard, 100 Function, 83 Memory HMI device, 244 Memory card, 16 First time use, 70 Inserting, 69 Unplug, 70 Memory information Displaying, 134 Memory management, 136 Module diagnostics, 204 moisture protection, 51 Monitoring time, 164 Mounting Intended, 35 Mounting location Docking station, 56 Selecting, 54 Signal lamp, 57 Mounting position Docking station, 64 Mouse External, 100, 217 Multi-key operation, 217 N Name server, 147 Nameplate, 15 Network ID, 148 Network operation Computer name, 145 Network parameters Setting, 146 Network&Dial-Up Connections, 146 Notice of protected rights, 4 Number format, 127 Number of characters For password, 228 For user, 228 For user view, 228 O Object PRELIMINARY II 1.7.2010
Index    Wireless Teach Pendant F IWLAN V2 332 Operating Instructions, 08/2010, A5E02453837-01 Battery, 224 Effective range (RFID) name, 226 WLAN quality, 225 Office location, 5 Offline Operating mode, 181 testing, 186 Online Operating mode, 182 testing, 187 OP properties Battery, 138 Device, 113, 135 Firmware, 137 License, 137 Memory monitoring, 136 Persistent storage, 133 Touch, 111 Opening Battery compartment, 76 Operating Control Panel, 100 EMERGENCY STOP button, 41, 89 Feedback, 218 Illuminated pushbutton, 93 Project, 217 Operating instructions Purpose, 3 Operating mode Changing, 182 Offline, 181 Online, 182 Transfer, 81, 182 Operating safety Standards, 40 Operating state Safe, 32 Operating system Parameter assignment, 98 Updating, 182, 191 Updating using ProSave, 193 Updating with WinCC flexible, 192 Operation Fail-safe, 32, 207, 253 Operation feedback, 218 Operator control Evaluation, 93 Selection, 93 Optical feedback, 218 Output F_FB_MP, 173 F_FB_RNG_n, 177 Override Input, 177 P Panic activation Enabling button, 92 Parameter assignment Data channel, 142 Operating system, 98 Password, 98 Backup, 228 Number of characters, 228 Removing, 115 Restoring, 228 Setting up, 115 Password list, 227 Password properties, 114 Password protection, 98 Setting up, 114 PII Start address, 164, 174, 179 Pin assignment RJ45 socket, 246 USB socket, 246 PIQ Start address, 164, 174, 179 Planning Number of RFID tags, 55 Plant Acceptance, 203 PLC, 77 Configuration graphic, 77 Connecting, 77 Number, 22 PLC_User, 233, 234 Ports, 68 HMI device, 245 Possible application Wireless Teach Pendant F IWLAN, 13 Power failure, 187 Power management Levels, 87 Power Save 1, 87, 127 Power Save 2, 87, 127 Power supply Charger, 249 Docking station, 249 Power supply unit Connecting, 65 PROFINET Addressing computers, 144 PRELIMINARY II 1.7.2010
 Index   Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  333 PROFINET IO Disabling direct keys, 139 Enabling direct keys, 139 PROFIsafe, 22 Loading the address, 140 Parameter, 164 Project Adapting, 181 Offline testing, 186 Operating, 217 Reuse, 181 Screen keyboard, 220 Testing online, 187 Transferring, 182, 183 Project file Compressed, 184 Protected trademark, 4 Protection against ingress of solid foreign bodies, 51 Protection class HMI device, 50 Protection zone, 29 Planning, 53 Setting up, 52 Protective foil, 16 Protective measure Static electricity, 252 Protocol, 22 Proxy server HMI device, 152 Internet Explorer, 99 PWR LED, 85 R Radiation High frequency, 36 Radio interference, 40 Emission, 45 Radio network, 51 Rampdown Global, 33 Local, 33 Reading Diagnostic information, 204 Rear view, 15 Rechargeable battery Used, 5 Rechargeable buffer battery Charge level, 138 Temperature, 138 Recipe Functional scope, 24 Recommissioning, 183, 199 Recycling, 5 Regional and language settings, 127 Regional setting, 127 Registered trademark, 4 Registry information Backup, 133 Remove, 213 Removing, 74, 76 Password, 115 Replacing the main rechargeable battery Blockage of USB port, 80 Reset button, 68 Response time, 164 Restoring, 79 From external storage device, 157 With ProSave, 190 With WinCC flexible, 189 Restoring factory settings, 182 RFID tag Installation, 64 planning the mapping, 55 Planning the number, 55 Testing, 141 RFID tag system, 26 Risk analysis, 40 Risk evaluation Special mode, 42 RNG LED, 85 S S7 Distributed Safety, 166 SAFE LED, 85 Safety Functional scope, 25 Standards, 40 Safety program, 204 Interconnecting FBs, 170 Scaling Functional scope, 23 Scope Manual, 3 Scope of delivery, 13, 63 Screen Functional scope, 24 Screen keyboard Adjust size, 106, 222 Change layout, 106, 222 PRELIMINARY II 1.7.2010
Index    Wireless Teach Pendant F IWLAN V2 334 Operating Instructions, 08/2010, A5E02453837-01 Character repeat, 109 Configure, 107 Entering data, 222 For Control Panel, 105 For project, 220 Move, 105, 221 Representation types, 105, 220 Screen saver, 128 Setting, 128 SecureMode Disabling, 101 Enabling, 101 Security system, 29, 226 Suitable, 53 Selecting Mounting location, 54 Selection Operator control, 93 Service, 5 Setting Date, 125 Date format, 127 Delay time, 131 Double-click, 110 Language, 220 Network parameters, 146 Number format, 127 Regional data, 127 Screen saver, 128 SMTP server, 149 Storage location, 130 Time, 125 Time format, 127 Setting language, 220 Setting up Password, 115 Password protection, 114 Protection zone, 52 Shock, 48 Shutdown, 33 Shutdown response, 208 Side view, 14 Signal lamp Mounting location, 57 SIMATIC Logon, 227 SIMATIC S7, 22 Simple user view, 229 SMTP server, 149 Setting, 149 Software Fail-safe operation, 161 For fail-safe mode, 22 Spacer Main dimensions, 243 Special mode Risk evaluation, 42 Specifications Charger, 249 Display, 244 Docking station, 249 Effective range, 250 Fail-safe operation, 245 HMI device antenna, 245 Input unit, 244 Main rechargeable battery, 248 Memory, 244 Ports, 245 Rechargeable buffer battery, 248 SSID Hidden, 60 Standard EMC testing, 38 TÜV, 39 Start HMI device, 113 Static electricity Protective measures, 252 STEP 7 HW Config, 163 Stop Category 0, 41 Category 1, 41 Storage location Setting, 130 Storage medium Restoring from external, 157 Saving to external, 156 Subnet Mask, 147 Support Technical, 5 Support Request, 5 Switch off HMI device, 82 Switch setting Enabling button, 92 Switching on Application case, 254 HMI device, 81 Synchronizing Date and time, 126 System alarm Configuring events, 283 PRELIMINARY II 1.7.2010
 Index   Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01  335 Meaning, 285, 286, 286, 289, 292, 293, 294, 295, 297, 298, 299, 300, 300, 301, 302, 304, 304, 307, 308, 309, 313, 314, 315, 315 Parameters, 283 System alarms Display, 283 System function, 93 System information Displaying, 134 System properties Device name, 145 General, 134 Memory, 134 T Tag, 23 Functional scope, 23 Task planner Functional scope, 25 TCP/IP address, 146 Technical support, 5 Technical Support, 5 Temperature Rechargeable battery, 138 Temporary files Backup, 133 Test For ambient conditions, 49 Testing Function, 92 RFID tag, 141 Text list Functional scope, 23 Time Setting, 125 Synchronizing, 126 Time format, 127 Time zone Setting, 125 Touch screen, 111 Calibrating, 111 Trademark, 4 Training center, 5 Transfer, 81 Cancel, 81 Manual, 184 Transfer settings, 142 Directories, 130, 131 Transfer Settings Channel, 142 Transferring Project, 182, 183 Transport conditions, 46 Transport damage, 63 Trends Functional scope, 25 U UL approval, 37 Unintentional action, 217 Updating Operating system, 191 With ProSave, 193 With WinCC flexible, 192 Updating the operating system, 182 Usage In industry, 40 In residential areas, 40 With protective measures, 48 USB Connection sequence, 79 Flash drive, 16 Keyboard, 100, 217 Memory stick, 16 Mouse, 100, 217 Pin assignment, 246 USB connection sequence, 79 USB device Connecting, 80 USB host-to-host cable, 79 USB port Lockout, 80 User data Backup, 228 Changing, 233 Restoring, 228 User group, 227 User name, 148 User view, 229 Extended, 229 Number of characters, 228 Simple, 229 Users, 231 Admin, 233, 234 Creating, 231 Delete, 234 Logoff, 231 Logon, 230 Number of characters, 228 PLC_User, 233, 234 PRELIMINARY II 1.7.2010
Index    Wireless Teach Pendant F IWLAN V2 336 Operating Instructions, 08/2010, A5E02453837-01 V VBScript Functional scope, 25 Vibration, 48 Volume, 132 Volume & Sounds Properties Volume, 132 W Weight HMI device, 244 WinCC flexible ES Configuration, 179 WinCC flexible Internet settings E-mail, 149 Windows CE taskbar, 98 Password protection, 98 WINS, 147 Server, 144 Wireless approval, 37 Wireless Teach Pendant F IWLAN Front view, 14 Main dimensions, 241 Possible application, 13 Rear view, 15 Scope of delivery, 13 Side view, 14 WirelessHART, 58 WLAN, 241 Configuring the connection, 117 Interface, 247 Receiver sensitivity, 247 Standards, 247 Transmission power, 248 WLAN quality, 225 WTPFailsafe_IO, 163 WTPfiwlanv2, 163 WTPStandard-IO, 163 Z ZigBee, 58  PRELIMINARY II 1.7.2010

Navigation menu