SAFRAN Identity and Security MASIGMA13M Access Control Terminal User Manual MorphoAccess Sigma Series Installation Guide

SAFRAN MORPHO Access Control Terminal MorphoAccess Sigma Series Installation Guide

Manual.pdf

     COPYRIGHT© 2013 Morpho Osny, France          MorphoAccess® Sigma Series – Installation Guide  September 2013 SSE-00000XXXXX-01  MorphoAccess® Sigma Series  Installation Guide
  MorphoAccess® Sigma Series - Installation Guide   Warning  2 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Warning COPYRIGHT© 2013 Morpho. All rights reserved. Information  in  this  document  is  subject  to  change  without  notice  and  do  not represent a commitment on the part of  Morpho. No part of  this document may  be reproduced  or  transmitted  in  any  form  or  by  any  means,  electronic  or  mechanical, including  photocopying  or  recording,  for  any  purpose  without  the  express  written permission of Morpho. This legend is applicable to all pages of this document. This  manual  makes  reference  to  names  and  products  that  are  trademarks  of  their respective owners.
 SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 3 September 2013    Revision History The table below contains the history of changes made to the present document. Version Date Description 01 September 2013 Document creation
  MorphoAccess® Sigma Series - Installation Guide   Table of Content  4 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Table of Content  Warning ........................................................................................................................................ 2 Revision History ............................................................................................................................ 3 Section 1 : Introduction ................................................................................................................ 8 MorphoAccess® Sigma Series Terminal .................................................................................... 9 Scope of the document ............................................................................................................ 10 Safety Instructions ................................................................................................................... 11 Wiring Recommendations ................................................................................................... 11 Europe information ............................................................................................................. 12 USA information .................................................................................................................. 12 Recommendations for terminal implementation .................................................................... 13 Section 2 : General Description .................................................................................................. 17 Box opening ............................................................................................................................. 18 Components of the initial package ......................................................................................... 19 Terminal's front view description ............................................................................................ 20 Terminal's rear view description ............................................................................................. 21 MorphoAccess® Sigma Series Technical Characteristics ......................................................... 22 Section 3 : Installation Procedure ............................................................................................... 25 Before proceeding to the installation ..................................................................................... 26 Installation .............................................................................................................................. 27 Required tools (not supplied)............................................................................................... 27 Equipment from the initial package to use ......................................................................... 27 Step by step procedure ........................................................................................................ 28 Section 4 : Electrical Interface .................................................................................................... 32 Wiring overview ...................................................................................................................... 33 Power Supply ........................................................................................................................... 34 External Power supply ......................................................................................................... 34 POE (Power Over Ethernet) ................................................................................................. 34 Output Relay ........................................................................................................................... 35 Nominal characteristics of relay .......................................................................................... 35 Example of connection for electrical door locks .................................................................. 35 Tamper Switch ......................................................................................................................... 36 Operating principle for the switch ....................................................................................... 36
 SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 5 September 2013    Nominal characteristics of switch block .............................................................................. 36 Wiegand input wiring .............................................................................................................. 37 Wiegand output wiring ........................................................................................................... 38 The controller supports neither LED1 nor LED2 signals ....................................................... 38 The controller supports only LED1 signal ............................................................................ 38 The controller supports LED1 and LED2 signals .................................................................. 39 Serial port wiring ..................................................................................................................... 40 DataClock Input ................................................................................................................... 40 DataClock Output ................................................................................................................ 40 RS485 ................................................................................................................................... 41 RS422 ................................................................................................................................... 41 GPIO wiring ............................................................................................................................. 42 Ethernet connection ................................................................................................................ 43 Default Ethernet configuration ........................................................................................... 43 Recommendations for RJ45 wiring ...................................................................................... 43 External USB connection ......................................................................................................... 44 Wifi / 3G dongle installation ................................................................................................... 45 Micro SD connection ............................................................................................................... 46 Section 5 : User Interface ........................................................................................................... 47 Modes for controlling access rights ........................................................................................ 48 Introduction ......................................................................................................................... 48 Identification mode ............................................................................................................. 48 Authentication (verification) mode ..................................................................................... 48 Multi-factor mode ............................................................................................................... 49 Proxy mode .......................................................................................................................... 49 Polling mode ........................................................................................................................ 49 Configuring the terminal ......................................................................................................... 51 MorphoAccess® 500 or J Series legacy mode ...................................................................... 51 Bioscrypt 4G Series legacy mode ......................................................................................... 51 MorphoAccess® Sigma Series native mode ......................................................................... 52 Anti-tamper / anti-pulling switches ........................................................................................ 53 Section 6 : Accessories, Software Licenses and PC Applications ................................................ 54 Compatible Accessories, Licenses and Software ..................................................................... 55 Compatible PC applications .................................................................................................... 56 Section 7 : Recommendations .................................................................................................... 57 Notice................................................................................................................................... 58 General precautions ............................................................................................................ 58
  MorphoAccess® Sigma Series - Installation Guide   Table of Content  6 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Areas containing combustibles ............................................................................................ 58 Specific precautions for terminals equipped with a contactless smartcard reader ............ 58 Ethernet connection ............................................................................................................ 58 Date / Time synchronization ............................................................................................... 59 Cleaning precautions ........................................................................................................... 59 Legacy mode ........................................................................................................................ 59 Lighting conditions for face detection ................................................................................. 59 Main principles ........................................................................................................................ 61 Most useful areas for biometric data...................................................................................... 62 Position of finger ..................................................................................................................... 63 Finger height ........................................................................................................................ 63 Finger angle ......................................................................................................................... 63 Finger inclination ................................................................................................................. 64 Finger rotation ..................................................................................................................... 64 Troubleshooting ...................................................................................................................... 65 How to get the latest versions of documents ......................................................................... 67 Documents concerning the MorphoAccess® terminal ............................................................ 68 Documents about installing the terminal ............................................................................ 68 Documents about administrating / using the terminal ....................................................... 68 Documents for the developer .............................................................................................. 68 Release note ........................................................................................................................ 68 Troubleshooting ...................................................................................................................... 70 The IP address for the terminal is unknown or it is not possible to connect to the terminal ............................................................................................................................................. 70 The sensor is switched off .................................................................................................... 70 The terminal returns erratic responses to Ping commands ................................................ 70 FAQ .......................................................................................................................................... 71 Contacts .................................................................................................................................. 72 Customer service ................................................................................................................. 72 Hotline ................................................................................................................................. 72  Annex 1 : Finger Placement Recommendations ...................................................................... 60 Annex 2 : Bibliography ............................................................................................................. 66 Annex 3 : Support .................................................................................................................... 69
 SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 7 September 2013    Table of Figures Figure 1: Implementation Recommendations ............................................................................. 15 Figure 2: Box Opening .................................................................................................................. 18 Figure 3: Box Content .................................................................................................................. 19 Figure 4: MorphoAccess® Sigma Series ....................................................................................... 20 Figure 5: MorphoAccess® Sigma Series terminal rear view ........................................................ 21 Figure 6: Removing wall frame and screw ................................................................................... 26 Figure 7: Face camera viewing angle ........................................................................................... 28 Figure 8: Drilling template ........................................................................................................... 29 Figure 9: Wall plate preparation for water tightness .................................................................. 30 Figure 10: Wall plate fixing .......................................................................................................... 30 Figure 11: Cabling layout ............................................................................................................. 33 Figure 12: Power supply wiring ................................................................................................... 34 Figure 13: Output relay wiring ..................................................................................................... 35 Figure 14: Example of electric latch connection ......................................................................... 35 Figure 15: Tamper switch wiring ................................................................................................. 36 Figure 16: Wiegand input wiring ................................................................................................. 37 Figure 17: Wiegand output wiring ............................................................................................... 38 Figure 18: Serial port wiring – DataClock .................................................................................... 40 Figure 19: Serial port wiring – DataClock .................................................................................... 40 Figure 20: Serial port wiring – RS485 ........................................................................................... 41 Figure 21: Serial port wiring – RS422 ........................................................................................... 41 Figure 22: GPIO wiring ................................................................................................................. 42 Figure 23: RJ45 wiring .................................................................................................................. 43 Figure 24: External USB connection ............................................................................................ 44 Figure 25: WI-FI™ / 3G dongle installation .................................................................................. 45 Figure 26: WiFi / 3G USB cable connection ................................................................................. 45
  MorphoAccess® Sigma Series - Installation Guide   Section 1 :Introduction  8 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013   Section 1 : Introduction
 MorphoAccess® Sigma Series – Installation Guide  Section 1 : Introduction   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 9 September 2013    MorphoAccess® Sigma Series Terminal Congratulations  for  choosing  a  MorphoAccess®  Sigma  Series  Automatic  Fingerprint Recognition Terminal. MorphoAccess® Sigma Series provides an innovative and effective solution for access control applications using Fingerprint Verification or/and Identification. Among  a  range of alternative biometric technologies,  the  use  of finger imaging has significant  advantages:  each  finger  constitutes  an  unalterable  physical  signature, developed  before  birth  and  preserved  until  death.  Unlike  DNA,  a  finger  image  is unique to each individual - even identical twins. MorphoAccess®  Sigma  Series  integrates  Morpho  image  processing  and  feature matching algorithms. This technology is based on lessons learned during 25 years of experience in the field of biometric identification and the creation of literally millions of individual fingerprint identification records. We believe you will find the MorphoAccess® Sigma Series fast, accurate, easy to use and suitable for physical access control. The MorphoAccess® Sigma Series offers the following advantages:  high quality optical sensor (IQS certified),  supports multiple input/output interfaces used in the physical  access control industry,  Local Area Network interface for easy interaction with other host  systems ; LAN and WLAN possibilities (Wi-Fi™ and 3G as an option),  compact size for easy installation and integration into your  available office space,  intuitive man machine interface with touch panel and display, that is easy to use in both setup and operational modes,  open  architecture,  with  dedicated  applications  implemented  via  MorphoAccess® Sigma Series Software Development Kit. To ensure the most effective use of your MorphoAccess® Sigma Series terminal, we recommend that you read this Installation Guide completely.
  MorphoAccess® Sigma Series - Installation Guide   Section 1 :Introduction  10 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Scope of the document This guide deals with the installation of MorphoAccess® Sigma Series, which is made up of following list of products:   Biometrics Contactless smartcard reader Water Resistant   iClass® Mifare® Desfire® NFC® Prox® MA Sigma Series MA Sigma      MA Sigma WR      MA Sigma iClass      MA Sigma iClass WR      MA Sigma Multi      MA Sigma Multi WR      MA Sigma Prox      MA Sigma Prox WR     
 MorphoAccess® Sigma Series – Installation Guide  Section 1 : Introduction   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 11 September 2013    Safety Instructions The  installation  of  this  product  should  be  made  by  a  qualified  service  Person  and should comply with all local regulations. It is strongly recommended to use a class II power supply at 12V-24V and 1A. min (at 12V) in conformity with Safety Electrical Low Voltage (SELV). The power supply cable length should not exceed 10 meters. This  product  is  intended  to  be  installed  with  a  power  supply  complying  with IEC60950-1, in accordance with the NEC Class 2 requirements; or supplied by a listed IEC60950-1  external  Power  Unit  marked  Class  2,  Limited  Power  source,  or  LPS  and rated 12VDC, 1A minimum or 24VDC, 0,5A minimum. In  case  of  building-to-building  connection  it  is  recommended  to  connect  0V  to ground. Ground cable must be connected with the terminal block Power Ground. Note  that  all  connections  of  the  MorphoAccess®  Sigma  Series  terminal  described hereafter are of SELV (Safety Electrical Low Voltage) type.  Wiring Recommendations Morpho recommends using a gauge AWG20 for 12V power supply when POE supply is not use. For information, this table shows the maximum drop voltage voltage observed on the terminal MorphoAccess® Sigma Series: Gauge AWG Diameter (mm) Maximum drop voltage @ 1m (V) Maximum drop voltage @ 5m (V) Maximum drop voltage @ 10m (V) 20 0.812 0.0333 0.1665 0.333 22 0.644 0.05295 0.26475 0.5295 24 0.511 0.0842 0.421 0.842 26 0.405 0.134 0.67 1.34       Drop voltage = loss of power due to wire resistance and its length V2 = V1 – Drop voltage  V1 V2 L
  MorphoAccess® Sigma Series - Installation Guide   Section 1 :Introduction  12 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Caution with battery usage CAUTION RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS Europe information Morpho  hereby  declares  that  the  MorphoAccess®  Sigma  Series  terminal  has  been tested and found compliant with following listed standards:   Low voltage Directive: 2006/95/CE  EMC Directive 2004/108/CE  R&TTE Directive (1999/5/CE).  ROHS Directive 2011/65 USA information  This device complies  with part 15  of the FCC Rules.  Operation  is subject to the  following  two  conditions:  (1)  this  device  may  not  cause  harmful interference,  and  (2)  this  device  must  accept  any  interference  received, including interference that may cause undesired operation. Changes  or  modifications  not  expressly  approved  by  the  party  responsible  for compliance could void the user's authority to operate the equipment. Responsible Party: SAFRAN Morpho, 11, boulevard Gallieni 92130 Issy-les-Moulineaux – France NOTA :  This  equipment  has  been  tested  and  found  to  comply  with  the  limits for  a  Class  B digital  device,  pursuant  to  Part  15  of  the  FCC  Rules.  These  limits  are  designed  to provide  reasonable  protection  against  harmful  interference  in  a  residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference  to  radio  communications.  However,  there  is  no  guarantee  that interference will not occur in a particular installation. If this equipment  does cause harmful  interference  to  radio  or  television  reception,  which  can  be  determined  by turning  the  equipment  off  and  on,  the  user  is  encouraged  to  try  to  correct  the interference by one of the following measures:  Reorient or relocate the receiving antenna.  Increase the separation between the equipment and receiver.
 MorphoAccess® Sigma Series – Installation Guide  Section 1 : Introduction   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 13 September 2013     Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.  Consult the dealer or an experienced radio/TV technician for help. Shielded cables must be used with this unit to ensure compliance with category B FCC restrictions.  Canada information WARNING  TO  USERS  IN  THE  CANADA  /  ATTENTION  POUR  LES  UTILISATEURS  AU CANADA This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and  (2)  this  device  must  accept  any  interference,  including  interference  that  may cause undesired operation of the device. Under Industry Canada regulations, this radio transmitter may only operate using an antenna  of  a  type  and  maximum  (or  lesser)  gain  approved  for  the  transmitter  by Industry Canada.  To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that  the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication. Le  présent  appareil  est  conforme  aux  CNR  d’Industrie  Canada  applicables  aux appareils  radio  exempts  de  licence.  L’exploitation  est  autorisée  aux  deux  conditions suivantes: (1) il ne doit pas produire de brouillage, et (2) l’utilisateur du dispositif doit être  prêt  a  accepter  tout  brouillage  radioélectrique  reçu,  même  si  ce  brouillage  est susceptible de compromettre le fonctionnement du dispositif. Conformément  à  la  réglementation  d’Industrie  Canada,  le  présent  émetteur  radio peut  fonctionner  avec  une  antenne  d’un  type  et  d’un  gain  maximal  (ou  inférieur) approuvé pour l’émetteur par Industrie Canada.  Dans le but de réduire les risques de brouillage radioélectrique à l’ intention d’autres utilisateurs,  il  faut  choisir  le  type  d’antenne  et  son  gain  de  sorte  que  la  puissance isotrope  rayonnée  équivalente  (p.i.r.e.)  ne  dépasse  pas  l’intensité  nécessaire  à l’établissement d’une communication satisfaisante.
  MorphoAccess® Sigma Series - Installation Guide   Section 1 :Introduction  14 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Recommendations for terminal implementation Every  installation  is  unique.  Sometimes  the  issues  are  well  defined  and  can  be handled in a standard fashion; sometimes the issues are very specific and may not be immediately recognizable. Morpho recommends following these steps for a successful installation:  Plan the installation - Choose the type of hardware required, decide if a network is required, and decide on the location and number of required devices.  Unpack all items - Unpack all items and check against the packing list.  Install  network  hardware  components  -  Install  the  cabling  and  components needed to run the system.  Install software - Install the software needed to set up the devices.  Pre-configure  device  -  Connect  the  device  to  the  Ethernet,  supply  power  to  the device, and pre-configure the device.  Mount devices - Mount the devices in their final locations  Power distribution and device hook up -  Connect the  device wiring  via the back panel.  Power-up procedure - Check the power connections, verify if battery is attached and  then  start  the  system  safely.  First  Boot  Assistant  screen  is  displayed,  where you can perform fundamental configuration.
 MorphoAccess® Sigma Series – Installation Guide  Section 1 : Introduction   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 15 September 2013    To  secure  properly  an  access,  Morpho  recommends  installing  the  MorphoAccess® Sigma Series terminal as a part of the typical Access Control environment, described in the figure below.  Figure 1: Implementation Recommendations This environment comprises: The MorphoAccess® Sigma Series terminal itself Its  role  is  to  perform  one-to-many  biometric  identification  or  one-to-one  biometric verification, i.e. to identify the individual who is presenting his finger on the terminal sensor by comparing his biometric data with the references previously stored in the terminal database (in the form of biometric templates) or to verify his identity using the reference stored in a contactless card presented to the terminal. An Access Controller (3rd party product) The Controller is the element which controls the access rights of the individuals to the secured area. For that reason, it must be located in the secured area. ACCESS CONTROLSYSTEM(*) OR EQUIVALENTNON SECUREDAREAACCESS CONTROLLERTCP/IP, Wiegand, Dataclock, RS485 or RS422ELECTRICLATCH (*)SECUREDAREADry ContactMorphoAccess® Sigma TerminalDry ContactALARM
  MorphoAccess® Sigma Series - Installation Guide   Section 1 :Introduction  16 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  The  individuals  who  are  authorized  to  access  the  secured  area  have  their  User  ID listed in a so-called "White List" (in contrast with a black list). The  MorphoAccess®  Sigma  Series  terminal  and  the  Controller  are  communicating according to one of the TCP/IP, Wiegand, Dataclock or RS485 protocols:  The MorphoAccess® Sigma Series terminal sends User ID to the Controller  The  Controller  sends  its  decision  to  the  MorphoAccess®  Sigma  Series  terminal (which displays GREEN light if access is granted or RED light if denied)  The MorphoAccess® Sigma Series terminal sends an alarm signal to the Controller as soon as a malicious operation (terminal pulled  out from the wall or having  its bottom  cover  opened  out  of  maintenance  operations)  is  detected;  refer  the paragraph  dealing  with  anti-pulling  and  anti-tamper  switches  for  more explanations. The Controller is part of the global Access Control System of the secured area, which for instance can administrate the White List of the Controller and receive diaries of the decisions taken by the Controller. An Alarm (3rd party product) This element is connected to the MorphoAccess® Sigma Series terminal through a dry contact. The MorphoAccess® Sigma Series terminal sends the command to activate the Alarm as  soon  as  a  malicious  operation  (terminal  pulled  out  from  the  wall  or  having  its bottom  cover  opened  out  of  maintenance  operations)  is  detected;  refer  the paragraph dealing with anti-pulling and anti-tamper switches for more explanations. A Door Electric Latch or equivalent (3rd party product) This element once activated opens the access. The Controller is the one which sends the command to activate the latch if access is granted (i.e. if the individual's User ID is listed in the Controller White List). Connection between these two elements is done through a dry contact.
 MorphoAccess® Sigma Series – Installation Guide  Section 2 :  General Description   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 17 September 2013     Section 2 :  General Description
  MorphoAccess® Sigma Series - Installation Guide   Section 2 : General Description  18 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Box opening At  the  box  opening,  components  shall  be  extracted  from  the  protection  casing  as depicted in the pictures below. Extract the wall plate (which is not screwed to the terminal) and keep it separate until the installation of the terminal is completed. The screwing of the product to the wall plate is the last stage of the installation. The protection accessory provided is optional : recommended for outside installation (to protect biometric module against water)        Figure 2: Box Opening    2 1
 MorphoAccess® Sigma Series – Installation Guide  Section 2 :  General Description   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 19 September 2013    Components of the initial package          Figure 3: Box Content  1. One (1) MASigma Terminal 2. One (1) wall frame 3. One (1) Battery 4. One (1) protection accessory (for WR products only, which usage is optional)   +                    +
  MorphoAccess® Sigma Series - Installation Guide   Section 2 : General Description  20 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Terminal's front view description                     Figure 4: MorphoAccess® Sigma Series    Contactless card area  Logo on cover when available  Camera Speaker Biometrical sensor (optical) USB port (for configuration and settings with a USB mass storage key or a computer) Sensor protection cap (optional, WR only) Micro LCD Touch panel
 MorphoAccess® Sigma Series – Installation Guide  Section 2 :  General Description   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 21 September 2013    Terminal's rear view description          Figure 5: MorphoAccess® Sigma Series terminal rear view   Battery installation Terminal blocks USB port (for configuration and settings with a USB mass storage key, or for installation of a Wi-Fi™ USB dongle) Anti-tamper  /  Anti-pulling switches RJ 45 Reset button POE (Optional – supplied separatly) µSD card slot Battery
  MorphoAccess® Sigma Series - Installation Guide   Section 2 : General Description  22 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  MorphoAccess® Sigma Series Technical Characteristics Item Description Access control modes Identification (search for fingerprint in a local database) Authentication with contactless card, with or without fingerprint check (only if terminal equipped with a smartcard reader) Multi-factor: identification or authentication (only if equipped with a smartcard reader) Proxy: the access control check is fully driven by a remote system Man Machine Interface 5” WVGA color Touch-screen VGA camera Loudspeaker & Microphone Biometrics Morpho Compact Biometric Module inside: 500dpi, 256 gray levels optical sensor. FBI PIV IQS certified sensor. False Acceptance Rate (FAR) adjustable from 10-2 down to 10-8 Database capacity: 3,000 users (standard) and up to 100 000 users (with specific license). Log capacity 100 000 records (standard) and up to 1 000 000 (with specific license) LAN/WLAN connection For terminal configuration and data transfer: Ethernet 10/100 Base T Or Wi-Fi™ Wireless LAN (option), WEP and WPA encryption available Either TCP, SSL or TLS protocol RFID cards (depending on product version) MIFARE® 4k DESFire® 2k, 4k, 8k Serial port The serial port supports WIEGAND, DATACLOCK ISO2, RS422 and RS485 protocols Output relay switches Access granted: 1 switch (either "open" or "close" in
 MorphoAccess® Sigma Series – Installation Guide  Section 2 :  General Description   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 23 September 2013    default state) USB host port External port for terminal configuration through a USB mass storage key Internal port to connect an external Wi-Fi™ USB dongle using an adapter cable. Input signals LED1/LED2 to activate the access granted relay Power supply Power Over Ethernet RJ45 connector Or 12 to 24 V DC power supply (1A min @12V) Security of the terminal Anti-tamper-pulling switches. Tamper-pulling detection: one relay switch ("open" in default state). Size and weight W x H x D: 152 mm x 154 mm x 59 mm (5.98” x6.06” x2.32”)  Weight : 580g Environmental conditions Operating temperature -10 °C to + 55 °C (14°F to 131°F) Operating humidity 10 % < RH < 80 % (non condensing) Storage temperature -25 °C to + 70 °C (-13°F to 158°F) Storage humidity 5% < RH < 95 % IP65 rated for outdoor use (once wall-mounted)  The terminal should be installed in controlled lighting conditions. Avoid direct exposure to sunlight or to UV lights. Certifications CE, CB, FCC, IC, RoHS, REACh, WEEE
  MorphoAccess® Sigma Series - Installation Guide   Section 2 : General Description  24 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013
 MorphoAccess® Sigma Series – Installation Guide  Section 3 :  Installation Procedure   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 25 September 2013     Section 3 :  Installation Procedure
  MorphoAccess® Sigma Series - Installation Guide   Section 3 : Installation Procedure  26 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Before proceeding to the installation  Make  sure  that  you  have  all  the  components  described  in  “Components  of  the initial package” section at your disposal.  Remove the wall plate. Keep this element at hand.  Remove the screw at the bottom of the product. Keep this element at hand.                 Figure 6: Removing wall frame and screw It is then possible to fix the terminal on the wall. The recommended height for fixing of the terminal is 1.40m (camera height).   For  an  optimal  use  the  terminal  must  be  installed  in  an  area  where  the  lighting conditions are controlled. Avoid direct exposure of the sensor to the sun light and ensure good ambient lighting for face detection if used.   1 2
 MorphoAccess® Sigma Series – Installation Guide  Section 3 :  Installation Procedure   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 27 September 2013    Installation Required tools (not supplied)  Four (4) raw plugs + four (4) ø 3.5mm max and length 30mm screws.  One (1) screwdriver adapted to screws above.  One (1) Drill (with a drill bit diameter adapted to raw plugs above).  One (1) hole saw ø 67mm (depending on installation case).  One (1) Flat tip screwdriver (0.4x2.0) for block connector cable removal.  A (1) Torx T10 screwdriver   Deadbolt/door strike  Snubber  diode  required  to  protect  regulated  DC  power  supply  from  inductive kickback (1N4007 diode or equivalent recommended)  Separate  power  supply  for  the  deadbolt/door  strike  based  on  supplier's recommendations.  External relay (if required)  Networking cable  Equipment from the initial package to use  One (1) MA Sigma terminal  One (1) wall plate.
  MorphoAccess® Sigma Series - Installation Guide   Section 3 : Installation Procedure  28 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Step by step procedure  Figure 7: Face camera viewing angle  The recommended height for fixing of the terminal is 1.40m (camera height).   For  an  optimal  use  the  terminal  must  be  installed  in  an  area  where  the  lighting conditions are controlled. Avoid direct exposure of the sensor to the sun light and ensure good ambient lighting for face detection if used.  Power  supply  from  electrical  source  shall  be  switched  off  before  starting  the installation.  The  strength of the  attachment  depends on  the  solidity of  the  wall  on  which the terminal is mounted.  To ensure water tightness, the wall plate has to be sealed with a silicone bead (refer to corresponding picture for process).
 MorphoAccess® Sigma Series – Installation Guide  Section 3 :  Installation Procedure   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 29 September 2013    Drilling the mounting holes  Figure 8: Drilling template If not present, drill in the wall a hole with a diameter of 67mm (see Figure 8: Drilling template. This template can be found in the Quick Installation Guide). Confirm  the  presence  inside  the  hole  of  all  the  cables  needed  for  the  electrical installation (see Electrical Interface) Drill in the wall 4 holes with a diameter adapted to screws and fit them with the raw plugs (see Figure 8: Drilling template).   88.0078.0021.00 59.0010.5053.00
  MorphoAccess® Sigma Series - Installation Guide   Section 3 : Installation Procedure  30 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Preparing wall plate  Figure 9: Wall plate preparation for water tightness Create a silicone bead all along the notch. The silicone bead shall be reduced to avoid overflow on the upper part of the wall plate (risk to prevent product mounting). Fixing  Figure 10: Wall plate fixing Place the wall plate against the wall, opposite the two holes pierced in the wall (see Figure 10: Wall plate fixing).         SiliconeIP65       Silicone
 MorphoAccess® Sigma Series – Installation Guide  Section 3 :  Installation Procedure   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 31 September 2013    Cabling Cable for wiring shall be AWG 20 to 26, length shall be 12 cm to 15 cm (stripped on 0,6mm). Prefer rigid cable to flexible cable (easier to connect)  Connection details: Characteristics min max Conductor cross section solid 0.14 mm² 0.5 mm² Conductor cross section stranded 0.2 mm² 0.5 mm² Conductor  cross  section  stranded,  with  ferrule  without  plastic sleeve 0.25 mm² 0.5 mm² Conductor cross section AWG/kcmil 24 20 AWG according to UL/CUL  26 20  Closing Don’t forget to insert battery before closing product, but power has to be set up just after closing it. If product has to be stored, don’t forget to remove the battery. Lock the product with the lower screw.   Battery  lifetime  is  limited when  power  is off :  at  least 250  hours  at 25°C  and 150 hours at -10°C. Don’t forget to change battery after long power cut or after several short power cut.
  MorphoAccess® Sigma Series - Installation Guide   Section 4 : Electrical Interface  32 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013   Section 4 :  Electrical Interface
 MorphoAccess® Sigma Series – Installation Guide  Section 4 :  Electrical Interface   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 33 September 2013    Wiring overview  Before proceeding, make sure that the person in charge of installation and connections is properly connected to earth, in order to prevent Electrostatic Discharges (ESD).  In case of several digital signals use, digital grounds shall all be wired together outside the product. Example : schematic to be included… Note  that  all  connections  of  the  MA  Sigma  described  hereafter  are  of  SELV  (Safety Electrical Low Voltage) type.  Figure 11: Cabling layout To connect wire to block connector, insert cable in the round hole of the connector. To remove wire, insert a flat screw driver (0.4x2.0max) in the rectangular hole of the connector and pull the corresponding wire.  BatteryReset buttonRJ45POEµSDUSBSAM1 Power supply 12V2 Power ground3 Switch 24 Switch 15 Digital ground6 Digital ground1 Wiegand IN 02 Wiegand IN 13 Wiegand OUT 04 Wiegand OUT 15 Wiegand LED 16 Wiegand LED 21 Digital Input 12 Digital Input 23 Digital Input 34 Digital Output 15 Digital Output 26 Digital Output 31 Relay 12 Relay 23 RS422 RX-4 RS422 RX+5 RS422/485 TX+6 RS422/485 TX-16161616
  MorphoAccess® Sigma Series - Installation Guide   Section 4 : Electrical Interface  34 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Power Supply POE and external power supply are not used at the same time: if both power supplies are used, priority is given to external power supply. If external power supply is shut down, switch to POE without reboot is not guarantee. External Power supply   Figure 12: Power supply wiring A 1 Power Supply 12V In Positive 12 Volts, power supply 2 Power ground In Ground power supply  External power supply  Must comply with CEE/EEC EN60950 standard.  12V to 24V (regulated) 1 Amp min at 12V.   Could be provided by a 12 Volts Wiegand power supply, which complies with the Security Industry Association's Wiegand standard March 1995.  Compliant with IEC60950-1, in accordance with the NEC Class 2 requirements; or supplied by a listed IEC60950-1 external Power Unit marked Class 2, Limited Power source, or LPS and rated 12VDC, 1A minimum or 24VDC, 0,5A minimum.  POE (Power Over Ethernet) MorphoAccess®  Sigma  Series  terminal's  power  supply  can  also  be  provided  by  the Ethernet using RJ45 connection (Power Over Ethernet mode). 16161616A B C D
 MorphoAccess® Sigma Series – Installation Guide  Section 4 :  Electrical Interface   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 35 September 2013    Output Relay   Figure 13: Output relay wiring D 1 Relay 1  Contact relay (normally open) 2 Relay 2  Contact relay strip Nominal characteristics of relay  Load characteristics:  1  A  max  @  30  VDC  (according  to  the  safety  extra  low  voltage  requirements independently of the power supply),  Resistive  load  or inductive load;  see  warning  information  hereafter  for  inductive load.   Inductive  load  management  requires  a  parallel  diode  for  a  better  contact lifetime. Example of connection for electrical door locks  Figure 14: Example of electric latch connection 16161616A B C D+VCC <30VImax < 2AElectricdoor lockOverswingdiodeMorphoAccess® SIGMA Terminal Button on otherside of the doorRelay Pin 1Relay Pin 2
  MorphoAccess® Sigma Series - Installation Guide   Section 4 : Electrical Interface  36 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Tamper Switch   Figure 15: Tamper switch wiring A 3 Switch 1  Tamper switch contact 4 Switch 2  Strip on tamper switch Operating principle for the switch  Product installed on the wall plate: switch enabled (contact closed).  Product opened (rear connectors accessible): switch disabled (contact open). Nominal characteristics of switch block 50 mA at 20 VDC max according to the safety extra low voltage standard.  This  MorphoAccess®  Sigma  Series  terminal  is  part  of  security  system;  it  is customer’s responsibility to connect the tamper switch (contact) to physical access controller, in order to prevent the access to the connector blocks.  16161616A B C D
 MorphoAccess® Sigma Series – Installation Guide  Section 4 :  Electrical Interface   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 37 September 2013    Wiegand input wiring   Figure 16: Wiegand input wiring A 5 Digital ground  Ground for Wiegand (connect pin 5 or 6) 6 Digital ground  Ground for Wiegand (connect pin 5 or 6) B 1 D0_IN In Wiegand IN D0 2 D1_IN In Wiegand IN D1 C 4 LED0 Out Wiegand LED OUT 1 (option) :    16161616A B C D
  MorphoAccess® Sigma Series - Installation Guide   Section 4 : Electrical Interface  38 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Wiegand output wiring The following figure shows how to cable the wires of the serial port of the terminal for the Wiegand protocol   Figure 17: Wiegand output wiring A 5 Digital ground  Ground for Wiegand (connect pin 5 or 6) 6 Digital ground  Ground for Wiegand (connect pin 5 or 6) B 3 D0_OUT Out Wiegand OUT D0 4 D1_OUT Out Wiegand OUT D1 5 LED1 In Wiegand LED IN 1 (option) : panel feedback 6 LED2 In Wiegand LED IN 2 (option) : panel feedback  The use of LED1 and LED2 wires is described in the paragraphs below. The controller supports neither LED1 nor LED2 signals When  the  access  controller  has  no  relay  contact  to  provide  an  answer  to  the MorphoAccess® terminal, then the decision to emit either the “access granted” signal or the “access denied” signal is taken by another way. It is either the MorphoAccess® terminal  itself  that  decide,  or  it  waits for  the  access  controller  answer  through  the local area network (TCP), or on the serial port in (RS422). It is strongly recommended to disable the LED IN feature, to avoid any interference on MorphoAccess terminal behavior. The controller supports only LED1 signal When  the  access  controller  has  only  one  relay  contact  which  is  dedicated  to  the “access  granted”  answer,  this  one  must  be  connected  between  the  LED1  and  GND wires. The LED1 wire is set to the low level by closing the contact between the LED1 and the GND wires), and it means “access granted". 16161616A B C D
 MorphoAccess® Sigma Series – Installation Guide  Section 4 :  Electrical Interface   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 39 September 2013    The MorphoAccess® terminal uses the timeout of the wait for a low level on the on LED1 wire or LED2 wire as "access denied” answer. To  minimize  at  most  the  waiting  time  of  the  user,  the  MorphoAccess®  terminal timeout value, must be adjusted to a value a little bit higher than the maximal value of the controller response time. Warning: if the LED2 wire is connected, it must be constantly maintained in the high state. The controller supports LED1 and LED2 signals When  the  controller  supports  one  relay  contact  for  each  of  the  possible  answers then:  The « access granted » contact must be connected between the LED1 and the GND wires of the terminal  The « access denied » contact must be connected between the LED2 et the GND wires of the terminal.   The MorphoAccess® terminal considers that:  The  answer  of  the  controller  is  "access  granted",  when  the  controller  puts  the LED1 wire to the low state (by closing a contact between the LED1  and the GND wires), and leaves the LED 2 wire to the high state.  The answer of the controller is "access denied", when the controller puts the LED2 wire to the low state (by closing a contact between the LED2 and the GND wires), whatever is the state of the LED 1 wire. The  MorphoAccess®  terminal  also  considers  that  the  answer  of  the  controller  is "access denied" in case of time-out while expecting for a closure between LED1 and GND wires, or between LED2 and GND wires.
  MorphoAccess® Sigma Series - Installation Guide   Section 4 : Electrical Interface  40 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Serial port wiring DataClock Input   Figure 18: Serial port wiring – DataClock A 5 Digital ground  Ground for Wiegand (connect pin 5 or 6) 6 Digital ground  Ground for Wiegand (connect pin 5 or 6) B 1 D0_IN In Data  ( 5V TTL ) 2 D1_IN In Clock ( 5V TTL ) C 4 Digital Output 0 Out Card present signal DataClock Output   Figure 19: Serial port wiring – DataClock A 5 Digital ground  Ground for Wiegand (connect pin 5 or 6) 6 Digital ground  Ground for Wiegand (connect pin 5 or 6) B 3 D0_OUT Out Data  ( 5V TTL ) 4 D1_OUT Out Clock ( 5V TTL ) 16161616A B C D16161616A B C D
 MorphoAccess® Sigma Series – Installation Guide  Section 4 :  Electrical Interface   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 41 September 2013    RS485   Figure 20: Serial port wiring – RS485 A 5 Digital ground  Ground for Wiegand (connect pin 5 or 6) 6 Digital ground  Ground for Wiegand (connect pin 5 or 6) D 5 RS485 TX / RX + Out RS485 non inverting signal 6 RS485 TX / RX - Out RS485 inverting signal RS485 implementation is limited to half-duplex communication. So only Tx+, Tx- and ground reference signals are necessary. Depending on the RS485 network, an impedance adaptation may be required. For  farthest  terminal,  a  120-Ohms  resistor  termination  may  be  added  outside  the terminal between TX+ and TX-. RS422   Figure 21: Serial port wiring – RS422 A 5 Digital ground  Ground for Wiegand (connect pin 5 or 6) 6 Digital ground  Ground for Wiegand (connect pin 5 or 6) D 3 RS422 RX- In RS422 inverting Receive 4 RS422 RX+ In RS422 non inverting Receive 5 RS422TX+ Out RS422 non inverting Transmit 6 RS422TX- Out RS422 inverting Transmit RS422 interface is a full duplex communication. 16161616A B C D16161616A B C D
  MorphoAccess® Sigma Series - Installation Guide   Section 4 : Electrical Interface  42 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  GPIO wiring   Figure 22: GPIO wiring A 5 Digital ground  Ground for Wiegand (connect pin 5 or 6) 6 Digital ground  Ground for Wiegand (connect pin 5 or 6) C 1 Digital Input 1 In Digital Input (3.3 V) 2 Digital Input 2 In  3 Digital Input 3 In  4 Digital Output 1 Out Digital Output (open drain) 5 Digital Output 2 Out  6 Digital Output 3 Out    16161616A B C D
 MorphoAccess® Sigma Series – Installation Guide  Section 4 :  Electrical Interface   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 43 September 2013    Ethernet connection Ethernet  interface can be  used  to power the  MorphoAccess®  Sigma  Series  terminal through POE (Power Over Ethernet) mode. According to the POE standard two modes are available: power on data pins and power on dedicated pins. Use  either  one  of  these  modes  depending  on  POE  implementation  on  your  local Ethernet network.  Wifi or 3G dongle cannot be used with POE power supply  Ethernet cable shall be shielded Default Ethernet configuration By default, MorphoAccess® Sigma Series terminal is configured in DHCP mode Recommendations for RJ45 wiring Pin 1 2 3 4 5 6 7 8 Signals TX(+) TX(-) RX(+) NC/POE pin dedicated (+) NC/POE pin dedicated (+) RX(-) Ground/ pin dedicated (-) NC/POE pin dedicated (-) EIA / TIA T568B Colors White orange Orange White green Blue White blue Green White brown Brown EIA / TIA T568A Colors White green White green White green White green White green White green White green White green Corel L120 Colors Grey White Pink Orange Yellow Blue Purple Brown  Figure 23: RJ45 wiring RJ45 plug pinout is compliant with 10/100 base T, IEEE802.3 Specification.
  MorphoAccess® Sigma Series - Installation Guide   Section 4 : Electrical Interface  44 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  External USB connection   Figure 24: External USB connection  The  external  Micro  USB  can  be  used  for  administration  only  to  connect  a  USB  key (with  a  standard  female  USB  A  /  USB  Micro  A  adapter)  or  to  connect  a  PC  (with  a standard Male USB A / USB Micro B adapter). These cables can be found in Morpho catalogue with ref XXX and YYY.  Report to User Guide for more information.   USB  connection  is limited to  PC  connection or  USB  key (power  consumption shall not exceed 200mA)
 MorphoAccess® Sigma Series – Installation Guide  Section 4 :  Electrical Interface   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 45 September 2013    Wifi / 3G dongle installation Wifi  /  3G  dongle  shall  be  installed  outside  the  product  (separate  area  shall  be reserved in the wall) and connected to the internal USB Mini B using  Morpho cable ref XXX. Wifi  / 3G dongle  shall not be  exposed to temperature  exceeding 50°C (don’t forget thermal dissipation) WI-FI™  and  3G  features  shall  be  available  only  if  the  product  is  powered  from  an external AC/DC 12V to 24V power supply (no enough power from the POE output for Wifi or 3G) Only  WI-FI  or  3G  USB  dongle  delivered  by  Morpho  (Reference  XXXXXXXX  or XXXXXXXX)  may  be  installed  with  the  terminal  for  WLAN  (Wireless  Local  Area Network) operation. Cable has to be plugged on the upward USB connector, as on the following image: USB extension cord (Reference XXXXXXXXX is necessary)  Figure 25: WI-FI™ / 3G dongle installation              Figure 26: WiFi / 3G USB cable connection   WI-FI™  or 3G  USB dongle  (to be installed outside  the product USB extension cord
  MorphoAccess® Sigma Series - Installation Guide   Section 4 : Electrical Interface  46 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Micro SD connection Micro SD card shall be used for the following functions :  Database extension (license is necessary)  Logs extension (license is necessary)  Picture logs (photo taking or face detection)  Dynamic messages µSD card class shall be 10, lower class may reduce performances Following µSD card shall be chosen in the following list :  XXX
 MorphoAccess® Sigma Series – Installation Guide  Section 5 : User Interface   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 47 September 2013     Section 5 : User Interface
  MorphoAccess® Sigma Series - Installation Guide   Section 5 :User Interface  48 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Modes for controlling access rights Introduction The  MorphoAccess®  Sigma  Series  terminal  offers  several  methods  for  controlling access rights: it needs to be configured in one of the following four modes:  Identification mode,  Authentication mode (requires a contactless smartcard reader in the terminal),  Multi-factor mode (requires a contactless smartcard reader in the terminal),  Proxy mode Refer  to  MorphoAccess®  Sigma  Series  Administrator  /  User  Guide  for  more information on Access Control. Identification mode The Identification process of the MorphoAccess® Sigma Series terminal proceeds by comparison of the biometric data of the finger placed on the biometric sensor, with all the biometric data stored in the database. It means that the biometric data of the allowed users must be stored in the internal database before they can request the access on the terminal. This biometric data is acquired  either  directly  on  the  terminal  (using  the  embedded  interface  or  the MorphoEnroll  utility), or  on an enrolment system using  the  same  type  of  biometric sensor. The  access  control  by  identification  process  is  started  when  a  finger is detected on the biometric sensor When the user requests the access, his identity is unknown, and it is the terminal that searches for his identity. The terminal grants the access if a match is found (the user is identified); otherwise the access is denied (the user remains unknown). For  further  information,  please  see  the  "Identification  mode"  section  in  the MorphoAccess® Sigma Series terminal user manual. Authentication (verification) mode Unlike the "identification" mode, the user identity must be known in order to execute the authentication process. Indeed,  authentication  is  an  identity  verification  process:  the  user  provides  his identity and the terminal checks it with the relevant process. This mode doesn’t compare the user’s data to the data of several users: it compares the  data  provided  by  the  user  with  the  reference  data  provided  by  the  same  user during enrollment phase. The data can be on a card presented to the terminal or in a database and ID is provided by the user.
 MorphoAccess® Sigma Series – Installation Guide  Section 5 : User Interface   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 49 September 2013    Access is authorized if the terminal finds a correspondence. For  further  information,  please  see  the  "Authentication  mode"  section  in  the MorphoAccess® Sigma Series terminal user manual. Multi-factor mode In  this  mode,  the  "identification"  and  "authentication"  modes  are  available simultaneously; the user decides which control method will be used:  by placing his finger on the sensor, thereby triggering the identification process,  by placing his contactless card on the reader, thereby triggering the authentication process, This is the default mode for terminals fitted with a contactless smartcard reader. For  further  information,  please  see  the  "Multi-factors  method"  section  in  the MorphoAccess® Sigma Series terminal user manual. Proxy mode In this mode, the access rights check process is controlled by an application on a host system. This application sends commands to the terminal to tell it on how to proceed. For further information, please see the "Proxy Mode" section in the MorphoAccess® Sigma Series terminal user manual. Polling mode The Proxy mode is an operating mode where the access control main  application is located  in  a  distant  system.  This  is  not  a  standalone  mode  like  Identification  and Authentication modes. It  means  that  the  terminal  becomes  a  slave  of  the  host  system  application.  The terminal does not have any user data in its database. The access control application is running on the host system and used MorphoAccess® terminal high level functions: •  Identification function •  Authentication function •  Read data on a contactless card •  Access control result signal command The MorphoAccess® Sigma Series terminal is driven through an Ethernet (or Wi-Fi™) link using TCP or SSL protocol. The MorphoAccess® terminal acts as a server: it is either waiting for a command or executing a command. The  commands  allowed  by  the  MorphoAccess®  terminal  are  described  in  the MorphoAccess® Host System Interface Specification document. For further details about SSL on the MorphoAccess® terminal, please refer to the SSL Solution for MorphoAccess® documentation.
  MorphoAccess® Sigma Series - Installation Guide   Section 5 :User Interface  50 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  To be explained : is it really polling mode or proxy mode ?
 MorphoAccess® Sigma Series – Installation Guide  Section 5 : User Interface   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 51 September 2013    Configuring the terminal MorphoAccess®  Sigma  Series  terminals  are  standalone  biometric  systems  which offers advance features for access control. MorphoAccess® Sigma Series terminals are equipped with a facility to support the MorphoAccess® and Bioscrypt legacy systems. When  MorphoAccess®  Sigma  Series  terminal  is  set  in  any  of  the  legacy  modes,  it supports  the  database  structures  and  configurations  of  the  selected  legacy  system. When the terminal  is booted for the first time, user  can select any of the following modes: MorphoAccess® 500 or J Series legacy mode MorphoAccess® Sigma Series terminal can be operated in MA500 or MA J mode (also refered as Lagacy Morpho). In this mode, the terminal will support configurations and operations of MA500 devices. Terminal can authenticate users enrolled in the MA500 devices,  using  biometric  check  as  well  as  contactless  card.  New  users  can  also  be enrolled in MA500 mode. Access Path First Boot Assistant > Protocol Configuration > Legacy Morpho  Once the product is configured in Legacy Morpho mode, the following methods can be used to configure the terminal:  through the Ethernet interface (remote management)  using USB key containing configuration scripts (local management) Configuration  procedures  are  described  inside  the  MorphoAccess®  Sigma  Series Administrator / User Guide as follows:  Section XXX: Terminal Configuration Bioscrypt 4G Series legacy mode MorphoAccess® Sigma Series can be operated in Bioscrypt 4G mode (also refered as Legacy  L1).  In  this  mode,  the  terminal  will  support  limited  operations  and configurations that are done using Secure Admin application. The terminal in L1 mode is  able  to  authenticate  the  users  enrolled  on  4G  terminals  and  contactless  cards. However it is not possible to enrol users in legacy L1 mode on  MorphoAccess® Sigma Series terminal. In case,  users are enrolled  in MA5G mode,  the user  data cannot be exported when terminal is in L1 mode. Access Path First Boot Assistant > Protocol Configuration > Legacy L1
  MorphoAccess® Sigma Series - Installation Guide   Section 5 :User Interface  52 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Once  the  product  is  configured  in  Legacy  L1  mode,  the  following  methods  can  be used to configure the terminal:  through the Ethernet interface (remote management) Configuration  procedures  are  described  inside  the  MorphoAccess®  Sigma  Series Administrator / User Guide as follows:  Section XXX : Terminal Configuration  MorphoAccess® Sigma Series native mode MorphoAccess® Sigma Series terminal is by default in native mode, that is MA5G. It will  support  only  the  new  features  and  configurations  in  the  native  mode.  The terminal can be configured using Webserver. This guide details you entire operations that can be performed from SIGMA terminal and from Webserver connected to SIGMA terminal. Access Path First Boot Assistant > Protocol Configuration > MA5G  NOTA :  When terminal mode is switched from MA5G to any of the legacy modes, the entire configuration and all databases, excepted communication links and users database, are erased NOTA :  The terminal is rebooted on mode change and factory settings are applicable.    Once the product is configured in Legacy Morpho mode, the following methods can be used to configure the terminal:  through the Ethernet interface (remote management)  using USB key containing configuration scripts (local management) Configuration  procedures  are  described  inside  the  MorphoAccess®  Sigma  Series Administrator / User Guide as follows:  Section XXX : Terminal Configuration
 MorphoAccess® Sigma Series – Installation Guide  Section 5 : User Interface   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 53 September 2013    Anti-tamper / anti-pulling switches Please refer also to “Tamper Switch” section. These  switches  are  activated  as  soon  as  there  is  enough  pressure  applied  on  the terminal  against  the  wall.  They  are  deactivated  as  soon  as  this  pressure  is  not  big enough, e.g. when the terminal is pulled out of the wall. When the switches are deactivated, the MorphoAccess® Sigma Series terminal acts as required  by  the  related  configuration  key  (see  MorphoAccess®  Sigma  Series Administrator / User Guide for key configuration description):  Ignore the event (default): useful during normal maintenance operations.  Send an alarm message to the Central Access Controller, through the usual channel of the access control result messages (Wiegand, DataClock, RS485, Ethernet or Wi-Fi™).  An  alarm  switch  (relay  contact)  is  directly  available  on  block  terminal «tamper switch pins». Please refer to “Wiring overview” and to “Tamper Switch” sections.  Generate an audible alarm signal with the buzzer and a visual alarm signal with the status Led.
  MorphoAccess® Sigma Series - Installation Guide   Section 6 : Accessories, Software Licenses and PC Applications  54 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013   Section 6 :  Accessories, Software Licenses and PC Applications
 MorphoAccess® Sigma Series – Installation Guide  Section 6 :  Accessories, Software Licenses and PC Applications   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 55 September 2013    Compatible Accessories, Licenses and Software The following items can be ordered directly to Morpho or to an official distributor, so as to enjoy all the features of your MorphoAccess® Sigma Series terminal:  Power supply units,  Power Over Ethernet module: enabling POE capabilities on the product,  Contactless smartcards: MIFARE® 4K; DESFire® 2K, 4K or 8K, HID iClass, Prox  MA WI-FI PACK: containing a Wi-Fi™ USB dongle and a Wi-Fi™ license to activate Wi-Fi™ capability on your terminal,  MA 3G PACK: containing a 3G USB dongle and a 3G license to activate 3G network communication on your terminal,  User  database  size  licenses  (MA_10K_USERS,  MA_50K_USERS, MA_100K_USERS): enabling database size upgrade from  3,000 to  10,000, 50,000 or  100,000  users  capacity  (2  fingers  per  record)  at  creation  of  the  database. Requires µSD card in the terminal.  Log  size  licenses  (MA_250K_LOGS,  MA_500K_LOGS,  MA_1M_LOGS):  enabling logs  size  upgrade  from  100,000  to  250,000,  500,000  or  1,000,000.  Requires  µSD card in the terminal.  MA_PAC license: enabling physical access control mode.  MA_TA license: enabling time and attendance mode.
  MorphoAccess® Sigma Series - Installation Guide   Section 6 : Accessories, Software Licenses and PC Applications  56 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Compatible PC applications MorphoAccess® Sigma Series terminals are fully compatible with:  the low level protocol using thrift commands (not recommended),  Morpho Integrator’s Kit (MIK) software development kit (version 6 or later).  M2A management application (version XXX or later)  Using Legacy Morpho mode, MorphoAccess® Sigma Series is also compatible with:  MEMS,  MIK 5 or later, The limitations in Legacy mode are described in the following document: MA SIGMA Series Release Note - Legacy Morpho limitations  Using Legacy L1 mode, MorphoAccess® Sigma Series is also compatible with:  SecureAdmin (version XXX or later), The limitations in Legacy mode are described in the following document: MA SIGMA Series Release Note - Legacy L1 limitations
 MorphoAccess® Sigma Series – Installation Guide  Section 7 :  Recommendations   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 57 September 2013     Section 7 :  Recommendations
  MorphoAccess® Sigma Series - Installation Guide   Section 7 : Recommendations  58 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Notice The  manufacturer  cannot  be  held  responsible  in  case  of  non-compliance  with  the following recommendations or incorrect use of the terminal. General precautions  Do not attempt to repair your MorphoAccess® Sigma Series terminal yourself. The manufacturer cannot be held responsible for any damage/accident that may result from  attempts  to  repair  components.  Any  work  carried  out  by  non-authorized personnel will invalidate your warranty.  Do  not  expose  your  MorphoAccess®  Sigma  Series  terminal  to  extreme temperatures.  Use your MorphoAccess® Sigma Series terminal with original accessories. Attempts to integrate unapproved accessories to the MorphoAccess® Sigma Series terminal will void your warranty.  Due  to  electrostatic  discharge,  and  depending  on  the  environment,  synthetic carpet  should  be  avoided  in  areas  where  the  MorphoAccess®  Sigma  Series terminal has been installed. Areas containing combustibles It is strongly recommended that you do not install your MorphoAccess® Sigma Series terminal  in  the  vicinity  of  gas  stations,  petroleum  processing  facilities  or  any  other facility containing flammable or combustible gasses or materials. Specific precautions for terminals equipped with a contactless smartcard reader It is recommended to install MorphoAccess® Sigma Series terminals equipped with a contactless smartcard reader at  a  certain distance (>  30cm)  from  metallic elements such as iron fixations or lift gates. Performances in terms of contactless badge reading distance will decrease when metallic elements are closer. Ethernet connection It is recommended to use a category 5 shielding cable (120 Ohms). It is also strongly recommended to insert a repeater unit every 90m. Extreme care must be  taken while connecting  Ethernet wire to  the  MorphoAccess® Sigma Series terminal block board since low quality connection may strongly impact Ethernet signal sensibility. It is recommended to connect Rx+ and Rx- with the same twisted-pair wire (and to do the same with Tx+/Tx- and the other twisted-pair wire).
 MorphoAccess® Sigma Series – Installation Guide  Section 7 :  Recommendations   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 59 September 2013    Date / Time synchronization If you want to use the MorphoAccess® Sigma Series terminal for application requiring high  time  precision,  we  recommend  synchronizing  regularly  your  MorphoAccess® Sigma Series terminal time with an external clock. The  MorphoAccess®  Sigma  Series  terminal  clock  has  a  +/-10  ppm  typical  time deviation at +25°C (roughly less than +/- 1 sec per day). At +55°C, the time deviation may be up to +/-8sec per day. At -10°C, the time deviation may be up to +/-8sec per day. Cleaning precautions The use of a dry cloth is recommended to clean the terminal, especially the biometric sensor. Acid liquids, alcohol or abrasive materials are prohibited. Legacy mode Installation in L1 / Morpho Legacy field : limitations, wiring precautions, …  When using SDAC, GPI??? Shall be connected to ground to avoid Door Open alarm  Lighting conditions for face detection In  order  to  get  good  performance  of  the  face  detection,  the  following recommendations shall be respected:  the user shall not be against the light  the light in front of the user shall be at least 500 Lux (to be confirmed)  the  background  of  the  user  shall  be  as  neutral  as  possible  (avoid  images  which could be mixed up with face)
  MorphoAccess® Sigma Series - Installation Guide   Annex 1 :  Finger Placement Recommendations  60 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013   Annex 1 :   Finger Placement Recommendations
 MorphoAccess® Sigma Series – Installation Guide  Annex 1 :   Finger Placement Recommendations   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 61 September 2013    Main principles Acquisition needs to be done with extreme care, in order to:  get the best image quality  increase recognition performance  reduce recognition time Then, it is highly recommended to:  Maximize the contact between the fingerprint and the sensor  Exert firm, but not excessive, finger pressure on the surface of the sensor  Do not press too hard  Do not slide nor roll the finger across the sensor  Do not move the finger during acquisition  Wait for the extinction of sensor backlight before removing the finger
  MorphoAccess® Sigma Series - Installation Guide   Annex 1 :  Finger Placement Recommendations  62 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Most useful areas for biometric data Fingerprint central area must be aligned with sensor centre  Area containing the maximum information
 MorphoAccess® Sigma Series – Installation Guide  Annex 1 :   Finger Placement Recommendations   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 63 September 2013    Position of finger Finger height Align center of 1st phalanx with sensor center  Finger angle The finger must be parallel to sensor sides  IDEALPOSITION
  MorphoAccess® Sigma Series - Installation Guide   Annex 1 :  Finger Placement Recommendations  64 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Finger inclination Finger must be parallel to the sensor surface  Finger rotation Finger must be parallel to the sensor surface   IDEALPOSITIONIDEALPOSITION
 MorphoAccess® Sigma Series – Installation Guide  Annex 1 :   Finger Placement Recommendations   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 65 September 2013    Troubleshooting When  finger  biometric  data  acquisition  is  difficult,  please  follow  the recommendations listed below:  The finger is cold o Solution : warm up the finger  The finger is wet o Solution : wipe the finger  The finger is dry o Solution : warm up the finger and/or add a little bit of humidity  The finger is dirty o Solution: wash hands  Remove bandages or adhesive tapes from the fingerprint area, and from the 2nd phalanx of the finger  Do not press or tense finger to avoid blood vessels constriction
  MorphoAccess® Sigma Series - Installation Guide   Annex 2 : Bibliography  66 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013   Annex 2 :  Bibliography
 MorphoAccess® Sigma Series – Installation Guide  Annex 2 :  Bibliography   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 67 September 2013    How to get the latest versions of documents The  last  version  of  the  documents  is  available  on  a  CD/ROM  package  from  our factory, or can be downloaded from our web site at the address below: www.biometric-terminals.com (Login and password required). To request a login, please send us an email to the address below: hotline.biometrics@t.my-technicalsupport.com
  MorphoAccess® Sigma Series - Installation Guide   Annex 2 : Bibliography  68 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Documents concerning the MorphoAccess® terminal Documents about installing the terminal MorphoAccess® Sigma Series Installation Guide, ref. SSE-00000XXXXX This document describes terminal physical mounting procedure, electrical interfaces and connection procedures. This document is in English. Documents about administrating / using the terminal MorphoAccess® Sigma Series Administrator / User Guide, ref. SSE-00000XXXXX This  document  describes  the  different  functions  available  on  the  terminal  and procedures for configuring the terminal. It also contains the full description of all the configuration parameters for the terminal. This document is in English. Documents for the developer MorphoAccess® Sigma Series Developers Guide, ref. SSE-00000XXXXX This document describes the commands supported by the MorphoAccess® terminal. This document is in English. Release note For each firmware version, a release note is published  describing the new features, the  supported  products,  the  potential  known  issues,  the  upgrade  /  downgrade limitations, the recommendations, the potential restrictions …
 MorphoAccess® Sigma Series – Installation Guide  Annex 3 :  Support   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 69 September 2013     Annex 3 :  Support
  MorphoAccess® Sigma Series - Installation Guide   Annex 3 : Support  70 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Troubleshooting The IP address for the terminal is unknown or it is not possible to connect to the terminal Use  terminal  interface  to  configure  a  valid  set  of  network  parameters  in  your terminal. The sensor is switched off Check that the database contains at least one record. Check that the identification mode is enabled. The terminal returns erratic responses to Ping commands Check the subnet mask. Ask the network administrator for the correct value. Check that each device connected to the network has a different IP address.
 MorphoAccess® Sigma Series – Installation Guide  Annex 3 :  Support   SSE-00000XXXXX-01 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN 71 September 2013    FAQ TBD
  MorphoAccess® Sigma Series - Installation Guide   Annex 3 : Support  72 MORPHO DOCUMENT – REPRODUCTION AND DISCLOSURE FORBIDDEN SSE-00000XXXXX-01   September 2013  Contacts Customer service Morpho SAV Terminaux Biométriques Boulevard Lénine - BP428 76805 Saint Etienne du Rouvray FRANCE Phone: +33 2 35 64 53 52 Hotline Morpho Support Terminaux Biométriques 18, Chaussée Jules César 95520 Osny FRANCE hotline.biometrics@t.my-technicalsupport.com Phone: + 33 1 58 11 39 19 (9H00am to 6H00pm French Time, Monday to Friday) http://www.biometric-terminals.com/ A login and password are required to access the  full  site  content. If  you don’t have one, please send us an email to the address above to request one. Contact by email is preferred.
  COPYRIGHT© 2013 Morpho   Head office : SAFRAN Morpho 11, boulevard Gallieni 92130 Issy-les-Moulineaux – France www.morpho.com

Navigation menu