Riello S p A 20142445 RiCLOUD NA WiFi Thermostat User Manual

Riello S.p.A. RiCLOUD NA WiFi Thermostat

User manual

RiCloud Control SystemUser ManualBoiler RF Receiver (20142446)Thermostat (20142444)Wifi Box (20142445)
49ENGLISHSUMMARY1  GENERAL INFORMATION ....................................................501.1  General notices ..................................................................... 501.2  What is the RiCLOUD for? ..........................................................511.3  Modes of use .........................................................................521.4  Glossary of technical terms  .....................................................521.5  RiCLOUD control Class Declaration, according to the ErP Directive .. 542 INSTALLATION ..................................................................562.1  Contents of the package ......................................................... 562.2  Practical installation diagramspage ......................................... 582.3  Technical Data ....................................................................... 582.4  Three-phase installation ........................................................583 COMMISSIONING ..............................................................653.1  User interface ........................................................................ 653.2 Display ................................................................................. 653.3  Setting the date and time ....................................................... 653.4  Setting the heating/cooling mode ........................................... 663.5  Setting the operating mode .....................................................673.6  Setting the extra functions ......................................................693.7  Setting the heating/cooling time program in automatic operating mode .....................................................................703.8  Setting the DHW time program .................................................723.9  Setting the heating/cooling room setpoint temperature ..............733.10  Setting the DHW setpoint temperature  .....................................753.11  Displaying operating information  ............................................763.12  Technical menu – Advanced programming ............................... 793.13  Linking function ....................................................................864  ALARMS AND OPERATING STATUSES ..................................... 894.1  LED notication lights for the WiFi Box and boiler RF receiver ** ... 894.2  Boiler and RiCLOUD alarms ......................................................90
501  GENERAL INFORMATION1.1  General noticesPlease read this manual before installing and using the device. 9 Risk  of  electric  shock.  This  device  should  be  installed  by  a  qualied professional  and  in  line  with  the  standards  in  force  for  electrical installations. Always disconnect the power supply before installing. 9 Note to the installer: −Most of the product parameters are factory set. If the device is activated without  a  WiFi  connection,  the  date  and  time  should  be  set  on  the thermostat  as  a  minimum  (this  information is  wiped  every  time  the batteries are removed and if not updated via the web). All other settings –  such  as  linking  the  receiver  and  the transmitter  (for  the WiFi Box), usage mode and temperatures – are pre-congured. 9 These instructions must be read together with the sections of the boiler manual  regarding  the  room  thermostat/boiler  remote  control.  It  is recommended that the device be installed by qualied technicians. 9 RiCLOUD should be installed in the most accessible room for you as regards controlling the room temperature (usually the living room). 9 As per the standards, RiCLOUD should be positioned 1.5 m from the oor to make sure that you can easily read the display.  9 RiCLOUD is powered by 2 x AA batteries. 9 RiCLOUD must be kept away from sources of heat or air currents as these may affect the accuracy of the readings from the incorporated room sensor. 9 Do not open RiCLOUD for any reason, unless to replace the batteries; it does not require any maintenance to operate.  9 Do not press on the liquid crystal display glass as this may damage the glass and cause problems with reading the display.  9 To clean the display, use a dry cloth only. Any seepage would damage the liquid crystal display.
51ENGLISH 9 When the WiFi Box is connected in ON/OFF mode to the boiler or another device via cable, should all the thermostats be faulty or the batteries at, the Box will show as OFF (no heating/cooling requests). The Wi-Fi Box relay can be forced on and off manually using the APP. 9 With the WiFi Box connected in OTBus mode to the boiler via cable, should all the thermostats be faulty or the batteries at, the Box will remain in the last operating mode. From the APP, you can manually force the boiler in heating mode on or off when connected to the internet. 9 With RiCLOUD connected (ON/OFF) to the boiler or another device via cable, should all the thermostats be faulty or the batteries at, the thermostat relay will remain in the last operating mode. 9 With the WiFi Box connected in ON/OFF or OTBus mode to the boiler via cable, should there be a power outage, the WiFi box remains in the last operating mode.1.2  What is the RiCLOUD for?The  RiCLOUD  allows  you  to  check  the  temperature  in  your  house  and  the operation of your boiler without you needing to access it. For reasons of space optimisation, your boiler may be located outside (for example, on a terrace or balcony or in an outdoor space); RiCLOUD, on the other hand, is usually installed in the largest room in the house, where it can be easily checked and adjusted. Where installed in systems with a boiler which is not equipped with the specic communication bus,  RiCLOUD allows you to check the temperature of  the  room where  it  is  installed  and  consequently  send  the  heat  requests to the  house generator with  no boiler remote control  (domestic  hot  water temperature and boiler settings/alarms cannot be managed).For  both  types  of  installation,  the  RiCLOUD  system  allows  you  to  check  the temperature  in  different zones  in  your  house,  where  there  are  zone  valves and each one of these is connected to a single additional RiCLOUD (multi-zone management).If RiCLOUD  is  installed  together  with  the  WiFi  Box  and  you  have  a  WiFi internet connection in your home, RiCLOUD system allows you to carry out the same functions available via RiCLOUD itself remotely on a smartphone.
521.3  Modes of useRiCLOUD  means  you  can  manage  your  domestic  heating  in  a  more sophisticated way; you can decide how and when the boiler will come on to heat your living spaces. In addition, it allows you to set the domestic hot water temperature, without having to access the boiler panel (where connected to the boiler via OTBus or a specic communication bus). The purpose  of  this  manual  is  to  explain  each  of  these  ways  of  using  the device and the related functions.1.4  Glossary of technical terms Heating water: the water in the radiators that has been heated by the boiler.Domestic hot water: the water heated by the boiler which is dispensed from the domestic taps.Fault code: this code shows on the display to ag any boiler or RiCLOUD faults.Original set-up:  this  is  the  control  panel conguration after turning on  the device for the rst time or after a reset.Display: this is the liquid crystal panel where each of the symbols corresponding to the various functions are shown.Anti-freeze function: this function ensures that any drops in temperature do not cause the water inside the pipes to freeze and cause damage to the heating system. This function is activated when the room temperature drops below 5°C (this value can be changed by the qualied technical service). NOTEThis function is active only if the boiler is in the correct operating condition (i.e. powered and not blocked) and no hydraulic system splitting into sections.Restore factory settings: this restores the control panel to its original set-up, resetting any user programming excluding the system clock.Summer: the heating system is not active in this mode (for example, during the summer). The  boiler  can  dispense  domestic  hot  water.  If  correctly  connected  and congured (in cooling mode), RiCLOUD can be used to manage a cooling system in the summer, turning the relay on in ON/OFF mode, in the opposite way to the winter operating mode. The relay keeps the user request connected (e.g. a zone valve) until the room temperature falls below a certain level. The cooling mode requires a specic system and generator for this purpose.
53ENGLISHWinter: RiCLOUD dispenses domestic hot water and hot water for heating in this mode.T1 anti-freeze temperature: this is the temperature used when the rooms are not lived in.T2 economy temperature: this is the temperature used when the rooms are not lived in during the day, at night or when you are on holiday.T3 comfort temperature: this is the temperature at which you obtain ideal room heating during the day.Room temperature:  this  is  the  temperature  in  the  room  where  RiCLOUD is installed (see "NOTE 1" page 54).Room setpoint temperature: this is the desired room temperature.External  temperature:  this  is  the  temperature  outside,  read  using  an external probe connected to the  boiler or read in another way (see "NOTE 2" page 54). Heating curve: this is the relationship between the external temperature and the heating ow temperature. Where external temperature data are available (via  an  external  probe  or  other  method),  the  heating  ow  temperature  is automatically adjusted as the external temperature varies in order to maintain a constant temperature in the room. The heating curve must be set by the installer on the basis of the geographical location and type of system.Connection  via  OTBus  communication  bus:  this  is  a  communication  mode between RiCLOUD and the boiler, where a series of information is exchanged between the two electronic systems. This proprietary connection can be used as opposed to the simple ON/OFF (open/closed contact) and is set by the boiler manufacturer specically for RiCLOUD Check the compatibility of your boiler with the OTBus connection rst.ON/OFF connection (boiler room thermostat): this is the simple communication method  between  the  RiCLOUD  and  the  boiler  (or  any  other  unit  capable of receiving this command), where the relay in RiCLOUD (or on the WiFi Box/receiver) sends an on/off request via the room thermostat (TA) contact on the boiler. The ON/OFF connection is also used when a request is made to another system component such as a zone valve or similar.
54RiCLOUD  ON/OFF  contact  always  maintains  the  same  technical  characteristics (RiCLOUD relay, WiFi Box relay, boiler RF receiver relay) wherever it is positioned and these must be respected when connecting the relay and the components it controls via cable. NOTE: Never exceed the maximum electrical loads (see page 211).NOTE 1The display range for the room temperature is between -7°C and +50°C.NOTE 2The display range for the external temperature is between -40°C and +60°C.Temperatures outside of these ranges are shown as three dashes “- - -”.1.5 RiCLOUD control Class Declaration, according to the ErP DirectiveWith reference to Delegated Regulation (EU) No. 811/2013, the data in the table can be used to complete the product data sheets and energy labelling of space heaters, combination heaters, packages of space heater, temperature control devices and solar devices.Manufacturer/Brand ModelRIELLO SpA / RiCLOUD RiCLOUDPossible  RiCLOUD  congurations,  the  relative  conguration  classes  and  the energy contribution to the system.Boiler  characteristics RiCLOUD congurationClass and contributionBoiler  with xed  delivery temperature (ON/OFF control)RiCLOUD ON/OFF connection I = 1%Boiler with variable delivery temperature (controlled by communication bus)Connection via communication bus to RiCLOUD. Delivery temperature to the boiler calculated on the basis of one room temperature onlyV = 3%Boiler with variable delivery temperature (controlled by communication bus)Connection via communication bus to RiCLOUD. Delivery temperature to the boiler calculated on the basis of the room temperature and the external temperature (given by the external probe or via the web).VI = 4%
55ENGLISHBoiler  characteristics RiCLOUD congurationClass and contributionBoiler with variable delivery temperature (controlled by communication bus)Connection via communication bus to RiCLOUD. Delivery temperature to the boiler calculated on the basis of at least 3 distinct room temperatures. At least 3 RiCLOUDs (sensors) connected to at least 3 zone valves (actuators) are required.VIII = 5%Denition of classesClass I – On/off room thermostat: a room thermostat that controls the on/off operation of a heater. Performance parameters, including switching differential and room temperature control  accuracy  are determined by the  thermostat’s mechanical construction.Class V – Modulating room thermostat, for use with modulating heaters: an electronic  room  thermostat  that  varies  the  ow  temperature  of  the  water leaving  the  heater  dependent  upon  measured  room  temperature  deviation from room thermostat set point. Control is achieved by modulating the output of the heater.Class VI  – Weather  compensator and  room sensor,  for  use  with  modulating heaters: a heater ow temperature control that varies the ow temperature of water leaving the heater dependent upon prevailing outside temperature and selected weather compensation curve.  A room temperature  sensor monitors room temperature and adjusts the compensation curve parallel displacement to improve room comfort. Control is achieved by modulating the output of the heater.Class VIII –  Multi-sensor room temperature control, for use with  modulating heaters:  an  electronic control, equipped  with  3  or more room sensors, that varies the ow temperature of the water leaving the heater dependent upon the aggregated measured room temperature deviation from room sensor set points. Control is achieved by modulating the output of the heater.
562  INSTALLATION2.1  Contents of the packageThe WiFi RiCLOUD package contains the following components:Qty Component Description1RiCLOUD = boiler remote control with room programmable thermostat function (*) or room programmable thermostat (**).(*)  where  there is an active OTBus connection in one of the following congurations: between the WiFi Box and the boiler, between the RF receiver (optional) and the boiler, between RiCLOUD and the boiler, (**) where the TA connection between the WiFi Box and the boiler is active1WPS/Smartlink Outputs BoilerWiFi Box = device for communicating with RiCLOUD programmable thermostat. It can operate with the Boiler RF receiver (optional) via radio frequency, with the boiler itself via cable (provided as standard) and with your home router via a WiFi connection. Magnetic back so that it can be attached to the boiler’s metal casing.1USB power adapter1USB cable A – USB Mini B = WiFi Box power cable 1USB cable A = cable connecting the WiFi Box and the boiler21.5V AA batteries1Installer/User Manual
57ENGLISHQty Component Description2Screws with plugs1OTBus connector (only for boilers without one) for an OTBus connection between the WiFi Box and the boiler or the Boiler RF receiver (optional) and the boiler or RiCLOUD and the boiler. It can also be used to connect the external probe (optional). 9 If installing additional RiCLOUDs or boiler RF receivers, you must follow the procedure to link them to the WiFi Box (see "3.13 Linking function" page 86).RiCLOUD package contains the following components:Qty Component Description1RiCLOUD = boiler remote control with room programmable thermostat function (*) or room programmable thermostat (**).(*)  where  there is an active OTBus connection in one of the following congurations: between the WiFi Box (optional) and the boiler, between the RF receiver (optional) and the boiler, and between RiCLOUD and the boiler, (**) where the TA connection between the WiFi Box (optional) and the boiler is active21.5V AA batteries1Installer/User Manual2Screws with plugs 9If installing additional RiCLOUDs or boiler RF receivers, you must follow the procedure to link them to the WiFi Box (see "3.13 Linking function" page 86).
582.2  Practical installation diagramspageSee practical installation diagrams on page 192.2.3  Technical DataSee page 210.2.4  Three-phase installationPreparationBefore installing the device Check  that  the  thermostat  is compatible with the boiler (see boiler installer manual).The  wireless  RiCLOUD  thermostat can be installed anywhere, however the  most  suitable  place  should be  chosen  taking  into  account  the following:  −Avoid draughts (A). −Do not install above sources of heat (B). −Avoid direct sunlight (C). −Position  at  the  appropriate height (D).1,5mA BC DWireless installation does not require  any  wiring,  making  the process very simple.RiCLOUD  thermostat  can  also  be installed  with  wiring,  to  replace any  existing  thermostat,  provided compatibility is checked in advance.Before  installing  the  boiler  control unit (WiFi Box), disconnect the boiler from the power supply. Installation The following tools are required: −Phillips screwdriver −Small slotted screwdriver  −Pliers and wire strippersInstalling RiCLOUDRemove RiCLOUD from its base;Fix  RiCLOUD  base  to  the  wall  or electrical  box  using  the  screws provided, use the optics level in  the plastic wrapping to install RiCLOUD horizontally.Using  screws  other  than  those PROVIDED may compromise the correct closure of the plastic. Make sure that the screw head is correctly inserted in the hole.
59ENGLISHRiCLOUD can be installed in one of the following ways:Wireless No wiring is required. Please check the maximum open-eld  distances  shown  in  RiCLOUD thermostat technical data.Loss of radio frequency communication is agged with alarm E82.  Distances  which  exceed  the maximum may occasionally generate an E82 alarm, causing incorrect system operation.Wired in ON/OFF mode (room thermostat contact on RiCLOUD base)When  replacing  old  thermostats  or as a new wired ON/OFF installation.  RiCLOUD can be connected to a boiler,  zone  valve  or  other  device. The  electrical  load  on  RiCLOUD room thermostat contact must not exceed the  specications  for  the  relay  itself (see  page  211).  Should  the  electrical load  not  be  compatible  with  the technical characteristics  indicated in RiCLOUD  thermostat  technical  data, it  is  recommended that  you  use  an additional separation relay. Connect the cables from the boiler room  thermostat  terminal  or  the power supply for any zone valves to RiCLOUD room thermostat terminal.TAON/OFFWired in OTBus mode (OTBus contact on RiCLOUD base).Direct connection via two wires to the  boiler  equipped  with  the  same communication protocol.We  recommend  checking  the maximum  cable  length  between the  WiFi  Box  and  the  boiler  OTBus terminal or RiCLOUD  and  the  boiler OTBus terminal (see page 211). For the electrical connection to the boiler, please see the boiler manual. 9 A wired connection via OTBus between  the  RiCLOUD  and  the boiler  is  recommended  in  the absence  of  a  WiFi  Box.  With the  above  connection  and  a WiFi Box, only one zone can be controlled and operation via the APP is not guaranteed.OTBus PROTOCOLInsert  the  2  x  AA  batteries  provided, with correct polarity.
60AAAAFit the RiCLOUD onto the base;Installing the WiFi BoxDescription of the WiFi BoxThe  WiFi  Box  communicates  with RiCLOUD thermostat or with the boiler RF receiver only via radio frequency (wireless).OUTPUTSThe  WiFi  Box  contains  a  relay  (see page  211)  which  replicates  RiCLOUD thermostat relays linked to it. It is ON if at least 1 of RiCLOUD relays is ON, and OFF if all of RiCLOUD relays are OFF.The WiFi Box can be wired to the boiler OTBus  connection.  This  transforms the WiFi  Box into  a  wireless receiver of  an  OTBus  command.  All  of  the information available in RiCLOUD via the  OTBus  connection  is  repeated to the receiver which wires it to the boiler;  it  is  therefore  an  example of complex radio frequency communication.The  relay  and  OTBus  outputs  are identied on the WiFi Box by the term OUTPUTS and are available via a USB plug. The position and distinction between the  2  outputs  on  the  USB  plug  are given below.USBUSBmini BBlack TABlack TARed OTRed OTnever120 VUSB Outputs/Boiler:Dry contact TAON/OFF relaymax 2 A at 30 VDCmax 0.5 A at 120 VACOTBus protocol contactNever 120 VPower supply: USB mini B 5V - 1AWiFi: IEEE 802.11 b/g/n - 2.4 GHzRadio frequency: 915 MHz Power consumption: 0.5 WTwo USB cables are also supplied, one to provide power via the USB  power adapter and the other to connect the WiFi Box to the boiler.120 V
61ENGLISHThe cable to connect it to the electrical power supply is a USB mini.The USB cable to connect the device to  the  boiler  has  an  end  with  4 terminals.The black terminals are for the ON/OFF connection and are to be connected to  the  “boiler  room  thermostat” output.The  red  terminals  are  for  the connection via OTBus and are to be connected to the “OTBus” output on the boiler.O TSESE = External sensorIf there is a RF boiler receiver installed in the system, these do nothing other than repeat everything that happens in the WiFi Box on a RF receiver with the same outputs (ON/OFF and OTBus) which  use  the  same wiring  colours: Red = OTBus, Black = ON/OFFWiFi  Box  connection  via  OTBus (only  for  boilers  equipped  with  a compatible OTBus protocol)Connect the red wires of the USB cable to  the  boiler  OTBus  terminal  (please consult  the  boiler  installer  manual). Should  the  boiler  not  be  equipped with an OTBus terminal, you can use an  OTBus  connector  provided  in  the WiFi RiCLOUD package (only for boilers without one).  9 Only one of RiCLOUD system components (RiCLOUD, WiFi Box or boiler RF receiver) must be connected to the boiler via cable via OTBus.  9 For Family models for interiors (exterior and recessed versions are  not  compatible  with  this operating  mode),  the  NEUTRAL ITRF11 INTERFACE BOARD KIT PART NO.20047522  must  be  bought and  the  communication board  installed,  following  the instructions included in the kit.
62ON/OFF WiFi Box connectionConnect  the  black  wires  of  the  USB cable to the boiler room  thermostat terminal (it is recommended that you consult the boiler installer manual). 9 In the case of RiCLOUD thermostats wired in ON/OFF mode, or zone  valve  microswitches, it  is  recommended  that  you connect  these  to  the  boiler room  thermostat  terminal  and wire the  WiFi  Box to  the boiler via OTBus only (only for boilers equipped  with  a  compatible OTBus protocol). OTBus on the RiCLOUDOTBus on the boilerTAOT Black cables = TA (ON/OFF)Red  cables = OTBus communication protocolAttach  the  WiFi  Box  to  the  boiler casing using the magnet on the back; WPS/Smartlink Outputs BoilerConnect  the  USB  connector  on  the previously connected cable to the WiFi Box OUTPUTS/BOILER output;WPS/Smartlink Outputs BoilerUSBOutputs Boiler
63ENGLISHPower the  WiFi  Box  via  the  relevant cable and power adapter provided.Resetting  the  OTBus  connection auto-conguration functionRiCLOUD is  congured  to  function  in ON/OFF mode.Should  it  be  connected  to  an  OTBus communication bus (wired or wireless/radio frequency), RiCLOUD auto-congures to the “Boiler remote control” operating mode.To restore the thermostat to its original operating mode (ON/OFF), remove and then reinsert the batteries. 9 The alarm E82 may be triggered by a change of operating mode from OTBus to ON/OFF or vice versa.Installing  and  conguring  the smartphone APPDownload  the  APP  on  your smartphone or tablet;Create a user account;MAC:     000000000000ID WiFi: 0000000000000 WPS/Smartlink Outputs BoilerMatch the WiFi ID  of the WiFi Box to the user account.
64If you need to link other thermostats and/or  boiler  RF  receivers  to  the WiFi Box via radio frequency, press the clear button on  the WiFi Box for 5 seconds until the LEDs ash at the same time  and set the device to be linked  to  the  same  operating  mode (see "3.13 Linking function" page 86).  After  making  these  links,  the system automatically resumes normal operation.WPS/Smartlink Outputs BoilerLink you home  modem password to the WiFi Box via one of the following methods. 9 Smartphones or tablets must be connected  to  the  WiFI  network that will be matched to the WiFi Box.Smart Link −Press  the  Smart  Link  button on the WiFi Box once with an appropriate implement. −The  green  and  red  LEDs  start ashing frequently. −Select  the  “Congure  WiFi” eld  from  the  drop-down menu  in  the  APP,  insert  your home  modem  password  and press the “Connect” button.The  process  is  complete  if  the  APP displays  the  message  “Connection complete”. 9Once  online,  the  system  requires up to 4 minutes to auto-congure.WPS (only for modems with this function) −Set  your  home  modem  to WPS mode. −Press  the  WPS  button  on  the WiFi Box using an appropriate implement  and  hold  for  5 seconds  until  the  red  and green LEDs ash frequently.The link has been made if the red LED on  the  WiFi  Box  ashes  frequently after a few seconds. 9Once  online,  the  system  requires up to 4 minutes to auto-congure.WPS/Smartlink Outputs BoilerRestart  the  WiFi  router  after  the operation is completed.NOTEFor  further  information,  please  see RiCLOUD APP manual.
65ENGLISH3  COMMISSIONING3.1  User interfaceSee page 188.3.2  DisplaySee page 191.3.3  Setting the date and timeFrom the HOME screen, press the SET/PROGRAM button twice.Select  the  desired  eld  (hours, minutes or day) using the FORWARD   or BACK   button (time, minutes , day, month and year).When  day  is  selected,  the corresponding  number  ashes  and the message dAY is displayed.When  month  is  selected,  the corresponding  number  ashes  and the message Non is displayed.When  year  is  selected,  the corresponding  number  ashes  and the message YEA is displayed.Change the value using the UP   or DOWN   buttons.Press  the  SET/PROG  button  to  save and  return  to  the  programming menu, press ESC/MODE to save and exit the programming menu, or wait 30 seconds to automatically save the value and return to the home screen.
663.4  Setting the heating/cooling modeRiCLOUD  is  default  set  to  heating mode.In  heating  mode,  RiCLOUD activates a  request  for  heat  when  the  room temperature is below  the  set temperature.In cooling mode, RiCLOUD activates an ON request (where there is a cooling system) when the room temperature is above the set temperature.From the HOME screen, press the SET/PROGRAM  button  to  open  the  user menu.Press the FORWARD   or BACK   button to select the eld HEATING/COOLING. Press the SET/PROG button to set.Press the UP   or DOWN   button to select the desired mode.IN=WINTERHeating mode.SU=SUMMERCooling mode.Press  the SET/PROG button to  save and  return  to  the  programming menu, press ESC/MODE to save and exit  the  programming  menu,  or wait 30 seconds to automatically save  the  value  and  return  to  the HOME screen 9 If at least one RiCLOUD thermostat is  in  cooling mode, the heating request via OTBus is not considered.
67ENGLISH3.5 Setting the operating modeFrom  the  HOME  screen,  press  ESC/MODE repeatedly to select one of the following modes:3.5.1 OFF mode In OFF mode, RiCLOUD guarantees the  minimum  room  temperature  set at parameter 01 from the PL technical menu only. NOTE Only  if  the  boiler  is  in  the  correct operating condition (i.e. powered and not blocked).In case of an OTBus connection between the WiFi Box and the boiler (including other types of  connection via OTBus), the  boiler  remains OFF  if all RiCLOUD thermostats in the system are OFF. When the boiler is OFF it does not provide any heating or domestic hot water.3.5.2  SUMMER/DHW mode   RiCLOUD in SUMMER/DOMESTIC HOT WATER mode. In this mode, the boiler provides  domestic  hot  water  where requested (instant boiler).If the parameter 24 CLOC is set to ON;  RiCLOUD follows the time periods set in  the  user-programming  menu  for DHW,  pre-heating  the  water  in  the storage  tank  (only  for  boilers  with integrated tank). The minimum room temperature set at parameter 01 from the PL technical menu is, however, guaranteed.In case of an OTBus connection between the WiFi Box and the boiler (including other types of  connection via  OTBus),  the  boiler  remains  in SUMMER mode if at  least one of  the thermostats is in summer mode and the others are OFF.
683.5.3  WINTER/AUTOMATIC mode In Winter/AUTOMATIC mode, RiCLOUD follows the time  program  set  in  the user-programming menu for heating.In case of an OTBus connection between the WiFi Box and the boiler (including other types of  connection via  OTBus),  the  boiler  remains  in Winter/AUTOMATIC mode if at least one of the thermostats is in heating mode. 9 For  installations  with  multiple RiCLOUD thermostats connected via OTBus, if one of these devices is in cooling mode, the heating request  to  the  boiler  is  not considered.3.5.4  WINTER/MANUAL mode RiCLOUD in Winter/MANUAL mode,  RiCLOUD  programmable  thermostat takes  the  T3  room  setpoint temperature  (comfort),  ignoring  the heating time program. In case of an OTBus connection between the WiFi Box and the boiler (including other types of connection via OTBus), the  boiler  remains  in  Winter/MANUAL mode if at least one of the thermostats is in heating mode. 9 For  installations  with  multiple RiCLOUD  thermostats  connected via OTBus, if one of these devices is in cooling mode, the heating request  to  the  boiler  is  not considered.3.5.5  WINTER/HOLIDAY mode In HOLIDAY mode, RiCLOUD takes the  T2  room  setpoint  temperature (economy), ignoring the heating time program,  for  the  days  set  with  the FORWARD   or BACK   buttons.RiCLOUD returns to AUTO mode   once the days set in HOLIDAY mode   have lapsed.In case of an OTBus connection between  the  WiFi  Box  and  the boiler  (including  other  types  of connection  via  OTBus),  the  boiler remains in Winter/HOLIDAY mode if at least one of the thermostats is in heating mode.  9 Every day, including programming day, ends at 24h00. 9 For  installations  with  multiple RiCLOUD thermostats connected via OTBus, if one of these devices is in cooling mode, the heating request  to  the  boiler  is  not considered.
69ENGLISH3.5.6  WINTER/PARTY mode In PARTY mode, RiCLOUD takes the T3 room setpoint temperature (comfort), ignoring  the  heating  time  program, until midnight of the current day, and then  automatically  switches  back  to AUTO mode  .In case of an OTBus connection between the WiFi Box and the boiler (including other types of  connection via  OTBus),  the  boiler  remains  in Winter/PARTY mode if at least one of the thermostats is in heating mode.  9 For  installations  with  multiple RiCLOUD thermostats connected via OTBus, if one of these devices is in cooling mode, the heating request  to  the  boiler  is  not considered. 3.6  Setting the extra functions3.6.1  ADVANCE function for AUTOMATIC operating modeThe  ADVANCE  function  allows  you to  bring  forward  the  next  heating/cooling time period and  the  relative room setpoint temperature desired, or to disable the heating time period if it is already running.To  activate/deactivate  the  ADVANCE function, from the HOME screen press the FORWARD button   (if active, the MAN icon is displayed).3.6.2  ONE HOUR BOOSTER function for AUTOMATIC operating modeThe ONE HOUR BOOSTER function allows you  to  activate  the  heating/cooling time period and the relative T3 room temperature (comfort) for 60 minutes, if it is not already in operation. 9 If  the  heating  time  period relative to the T3 room setpoint temperature (comfort) is already running, by activating the function the time period is extended by one  hour,  but not beyond midnight of the current day.To  activate/deactivate  the  ONE  HOUR BOOSTER  function,  from  the  HOME screen  press  the  BACK  button   (if active, the MAN icon is displayed).3.6.3  SEMI-AUTOMATIC FILLING functionThe  SEMI-AUTOMATIC  FILLING  function allows the correct system pressure to be restored and is only available for boilers  equipped  with  the  relevant
70function (if OTBus connection available between  the  WiFi  Box and the boiler or the RF receiver and the boiler or RiCLOUD  and  the  boiler,  if provided for by the OTBus protocol).If the rIE alarm is quickly ashing (0,5 sec) on the HOME screen in the room temperature eld, press the ESC/MODE button and hold for 5 seconds to start semi-automatic lling  (the  message  rIE  will  stop ashing and remain on). When releasing the button ESC/MODE the rIE message starts ashing slowly (2 secs) until the end of the function.Once  the  system  pressure  has  been restored,  RiCLOUD automatically returns  to  the  normal  HOME  screen display. 9 If  the  SEMI-AUTOMATIC  FILLING function is not carried out within 90 seconds, the rIE alarm ashes  quickly  (1sec.)  and  is displayed  on  the  HOME  page again.3.6.4  KEY-LOCK functionTo  enable/disable  the  KEY-LOCK function, press the FORWARD > and UP ^ buttons together for 5 seconds from the HOME page (if enabled, LOC will be displayed for 5 seconds, if disabled, UnL will be displayed for 5 seconds).3.7  Setting the heating/cooling time program in automatic operating modeFrom the HOME screen, press the SET/PROGRAM  button  to  open  the  user menu.Press the FORWARD   or BACK   button to  select  the  eld  HEATING/COOLING TIME PROGRAM  .Press the SET/PROG button to set.
71ENGLISHPress the FORWARD   or BACK   button to select the day or period of the week to be changed.Days DisplayMondayFridaySaturday SundayMonday SundayMondayTuesdayWednesdayThursdayFridaySaturdaySundayPress  the  SET/PROGRAM  button  to conrm the day or period of the week to be changed.Press the FORWARD   or BACK   button to  select  the    time  segment  to  be changed.Press  the  ESC/MODE  button  to select  the  desired  room  setpoint temperature (T1, T2, T3).Press  the  UP  button    to  copy  the previous setting to the following time segment (the DOWN   button can be used to go back or copy the setting to the previous time segment). Press  the SET/PROG button to  save and  return  to  the  programming menu, press ESC/MODE to save and exit  the  programming  menu,  or wait 30 seconds to automatically save  the  value  and  return  to  the HOME screen.
723.8  Setting the DHW time programThis  function  is  available  only  if  the parameter 24 CLOC is set to ON.The time periods are default set to ON  (domestic  hot  water  function active). From the HOME screen, press the SET/PROGRAM  button  to  open  the  user menu.Press the FORWARD   or BACK   button to select the eld DHW TIME PROGRAM . Press the SET/PROG button to set.Press the FORWARD   or BACK   button to select the day or period of the week to be changed.Days DisplayMondayFridaySaturday SundayMonday SundayMondayTuesdayWednesdayThursdayFridaySaturdaySunday
73ENGLISHPress  the  SET/PROGRAM  button  to conrm the day or period of the week to be changed.Press the FORWARD   or BACK   button to  select  the    time  segment  to  be changed.Press the ESC/MODE button to activate or deactivate the domestic hot water function.Press  the  UP  button    to  copy  the previous setting to the following time segment (the DOWN   button can be used to go back or copy the setting to the previous time segment). Press  the  SET/PROG  button  to  save and  return  to  the  programming menu, press ESC/MODE to save and exit the programming menu, or wait 30 seconds to automatically save the value and return to the HOME screen.3.9  Setting the heating/cooling room setpoint temperatureTo change the T1/T2/T3 room setpoint temperature, press the SET/PROGRAM button from the HOME screen to enter the user menu.Press the FORWARD   or BACK   button to  select  the  eld  HEATING/COOLING TEMPERATURE. Press the SET/PROG button to set.  Press the FORWARD   or BACK   button to  select  the  temperature  to  be changed.Press  the UP   or DOWN   button to modify the selected room setpoint temperature. 9The  T3  temperature  (comfort) cannot  be  higher  than  35°C or  less  than  or  equal  to  T2 (economy). 9 The  T2  temperature  (economy) cannot be higher than or equal
74to  T3  (comfort)  or  less  than  or equal to T1 (anti-freeze). 9 The T1 temperature (anti-freeze) cannot be higher than or equal to T2 (economy) or less than 1°C.Press  the SET/PROG button to  save and  return  to  the  programming menu, press ESC/MODE to save and exit  the  programming  menu,  or wait 30 seconds to automatically save  the  value  and  return  to  the HOME screen.The room setpoint temperatures can also be modied instantly if RiCLOUD is in the operating mode corresponding to the room setpoint temperature to be modied.3.9.1  Setting the temperature in MANUAL mode From  the  HOME  screen,  press  the UP   or DOWN   button to set the desired T3 (comfort) room setpoint temperature. 9 The room setpoint  temperature set  cannot  be  less  than  or equal  to  the  T2  temperature (economy).Press  the  SET/PROG  button  to  save and return to the HOME screen, press ESC/MODE  to  save  and  return  to  the HOME screen, or wait 5 seconds to automatically  save  the  value  and return to the HOME screen.3.9.2  Setting the temperature in AUTOMATIC mode From  the  HOME  screen,  press  the UP   or DOWN   button to set the desired room setpoint temperature for the current time period. Press  the  SET/PROG  button  to  save and return to the HOME screen, press ESC/MODE  to  save  and  return  to  the HOME screen, or wait 5 seconds to automatically  save  the  value  and return to the HOME screen.3.9.3 Setting the temperature in HOLIDAY mode From  the  HOME  screen,  press  the UP   or DOWN   button to set the desired T2 (economy) room setpoint temperature. 9The room setpoint temperature set  cannot  be  higher  than  or equal to T3 (comfort) or less than or equal to T1 (anti-freeze).Press  the  SET/PROG  button  to  save and return to the HOME screen, press ESC/MODE  to  save  and  return  to  the HOME screen, or wait 5 seconds to automatically  save  the  value  and return to the HOME screen.
75ENGLISH3.9.4  Setting the temperature in PARTY mode Press  the UP   or DOWN   button on the HOME screen to set the desired room setpoint temperature.The  room  temperature  set  cannot be  less  than  or  equal  to  the desired T3 (comfort) room setpoint temperature. 9 The room setpoint  temperature set  cannot  be  less  than  or equal  to  the  T2  temperature (economy).Press  the  SET/PROG  button  to  save and return to the HOME screen, press ESC/MODE  to  save  and  return  to  the HOME screen, or wait 5 seconds to automatically  save  the  value  and return to the HOME screen.3.10  Setting the DHW setpoint temperature From the HOME screen, press the SET/PROGRAM  button  to  open  the  user menu.Press the FORWARD   or BACK   button to select the eld DOMESTIC HOT WATER TEMPERATURE.Press the SET/PROG button to set.Press  the UP   or DOWN   button to  modify  the  domestic  hot  water setpoint temperature.Press  the SET/PROG button to  save and  return  to  the  programming menu, press ESC/MODE to save and exit  the  programming  menu,  or wait 30 seconds to automatically save  the  value  and  return  to  the HOME screen.
763.11  Displaying operating information This  function  (available  with  OTBus connection  between  the  WiFi  Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol) allows you to display the boiler probe values and some boiler operating statuses.From the HOME screen, press the SET/PROGRAM  button  to  open  the  user menu.Press the FORWARD   or BACK   button to select the eld InFO.Press  the  SET/PROGRAM  button  to display this eld.Press the UP   or DOWN   button to select the desired parameter and wait until it is displayed.Parameter DescriptiontSEt Heating delivery setpoint calculated by RiCLOUD (shown only if RiCLOUD has received a heating  request). The value  calculated by RiCLOUD  may  differ  from  the  real  heating delivery setpoint delivered by the boiler, if the minimum boiler heating setpoint parameter is higher than this value. EXAMPLE:The  heating  delivery  setpoint  calculated  by RiCLOUD is  30°C,  the minimum boiler heating setpoint parameter is 40°C, the real heating delivery setpoint delivered by the boiler is 40°C.tFLO Temperature  read  by  the  boiler  heating delivery  probe  (available  with  OTBus connection  between  the  WiFi  Box  and  the boiler  or  the  RF  receiver  and  the  boiler  or RiCLOUD and the boiler, if provided for by the OTBus protocol).
77ENGLISHParameter DescriptiontrEt Temperature read by the boiler heating return probe  (available  with  OTBus  connection between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol).tdH Temperature  read  by  the  boiler  DHW  probe (available  with  OTBus  connection  between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol).tFLU Temperature read by the boiler ue gas probe (available  with  OTBus  connection  between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol).tESt Temperature  read  by  the  external  probe connected  to  the  boiler  or  the  external temperature  communicated  via  the  APP (available  with  OTBus  connection  between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol).MOdU Boiler fan speed percentage (available with OTBus connection between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus  protocol).  The  value  0.0  corresponds to the MINIMUM DOMESTIC HOT WATER POWER; the value  100  corresponds  to  the  MAXIMUM DOMESTIC HOT WATER POWER.
78Parameter DescriptionFLOr Flow  meter  rate  in  litres/minute,  where  a ow meter is available (available with OTBus connection  between  the  WiFi  Box  and  the boiler  or  the  RF  receiver  and  the  boiler  or RiCLOUD and the boiler, if provided for by the OTBus protocol).HOUr Number  of  operating  hours  in  high condensation  mode  (available  with  OTBus connection  between  the  WiFi  Box  and  the boiler  or  the  RF  receiver  and  the  boiler  or RiCLOUD and the boiler, if provided for by the OTBus protocol).PrES  System  pressure  (available  with  OTBus connection  between  the  WiFi  Box  and  the boiler  or  the  RF  receiver  and  the  boiler  or RiCLOUD and the boiler, if provided for by the OTBus protocol).tFl2  Temperature  read  by  the  delivery  probe  in the  second  heating  circuit  (available  with OTBus connection between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol).Press the SET/PROG button to save and return to the programming menu, press ESC/MODE  to  save  and  exit  the  programming  menu,  or  wait  180  seconds to automatically save the value and return to the HOME screen.
79ENGLISH3.12  Technical menu – Advanced programmingFrom the HOME screen, press the SET/PROGRAM  button  to  open  the  user menu.Press the FORWARD   or BACK   button to select the eld PL.Press the SET/PROG button to set.Press  the UP   or DOWN   button to  insert  the  installer  password (password = 18). Press the SET/PROG button to set.Press  the  FORWARD   or BACK   button  to  select  the  desired parameter.Press  the  SET/PROGRAM  button  to set  the  selected  parameter.  For parameters 08 to 19, use the FORWARD  or BACK   button to select the 2 sub-parameters.Press the UP   or DOWN   button to modify the selected parameter.Press  the  SET/PROG  button  to  save and  return  to  the  technical  menu, press  ESC/MODE  to  save and  exit  the technical menu, or wait 120 seconds to  automatically save the value  and return to the HOME screen.
80ParameterDescription01 t0Minimum safety temperature. The value can be set from 1°C to 5°C. Default set to 3°C. Should  RiCLOUD room probe detect a temperature  below  the  parameter  set,  a heating  request  is  generated  –  only  when HEATING in operating modes SUMMER/DOMESTIC HOT WATER and OFF – taking into account the hysteresis set under the HOn and HOFF parameters.08 HHCHMaximun  local central  heating  temperature  setpoint  (available  with  OTBus  connection between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol).The value can be set between 80°C and 40°C (for high temperature heating) or from 45°C to 20°C (for low temperature heating).08 LLCH Minimum  heating  setpoint  temperature (available  with  OTBus  connection  between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol). The value can be set from 10°C to HHCH -1°C.10 CLIThermoregulation curve with external probe connected to the boiler or external web probe via the APP (available with OTBus connection between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol). Default set to 1.2°C. The value can be set from 0.2°C to 3°C. The  parameter  in  question  affects  the calculation  of  the  heating  delivery  setpoint temperature.
81ENGLISHParameterDescription1008060402020 16 12 8 4 03 2,521,51,210,80,60,40,2-4 -8 -12 -16T Mand risc = T Mand Curva + ( CLI * InFL * ΔT Amb)T Mand Curva = Delivery temperature calculated using the thermoregulation curve set under parameter CLICLI = thermoregulation curveInFL = room inuenceΔT Amb = (room temperature set) – (current room temperature)11 InFLInuence  of  room  probe  on  calculation of  heating  delivery  setpoint  temperature (available  with  OTBus  connection  between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol).Default set to 10. The value can be set from 0°C to 20°C.T Mand risc= T Mand Curva + ( CLI * InFL * ΔT Amb)T Mand Curva = Delivery temperature calculated using the thermoregulation curve set under parameter CLICLI = thermoregulation curveInFL = room inuenceΔT Amb = (room temperature set) – (current room temperature) 9Setting the parameter InFL=0, with the external probe disconnected from the boiler and the web external probe not enabled on the app, the heating delivery temperature (per la zona comandata dal RiCLOUD)  is the same as the temperature set under parameter LLCH.
82ParameterDescription13 CALI Correction  of  the  temperature  detected  by RiCLOUD room probe. The  value  can  be  set  with  a  hysteresis  of +-7°C.14 FACtRestore factory settings. The value can be set from 0 to 1. By setting this parameter to 1, RiCLOUD values are restored to the default setting, excluding the  date  and  time  and  the  domestic  hot water temperature.16 SOFtRiCLOUD software version. Read-only parameter.17 dEgrSetting the unit of measure. The value can be set to °C or °F. The default setting is °C (degrees Centigrade). This parameter allows you to set and view temperatures on the degrees Centigrade or degrees Fahrenheit scale.
83ENGLISHParameterDescription19 HOnSetting  the  ON  hysteresis  for  heating  or cooling requests. The  value  can  be  set  from  0°C  to  2°C;  the default setting is 0.4°C. RiCLOUD processes an ON request below the target room temperature set (desired room setpoint – H On) if the heating mode is active, or  above  the  target  room  temperature  set (desired room setpoint + H On) if the cooling mode is active.19 HOFFSetting  the  OFF  hysteresis  for  heating  or cooling requests. The  value  can  be  set  from  0°C  to  2°C;  the default setting is 0.1°C. RiCLOUD processes an OFF request above the target room temperature set (desired room setpoint  +  H  OFF)  if  the  heating  mode  is active, or below the target room temperature set  (desired  room  setpoint  –  H  OFF)  if  the cooling mode is active.21 ALLAlarm  history  display  (available  with  OTBus connection  between  the  WiFi  Box  and  the boiler  or  the  RF  receiver  and  the  boiler  or RiCLOUD and the boiler, if provided for by the OTBus protocol). The last 9 alarms generated by  the  boiler  and  saved  by  RiCLOUD are shown. 22 tSPSetting  boiler  parameters  (available  with OTBus connection between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol). This parameter is set by the Authorised Service Centre.
84ParameterDescription23 LEgIEnabling  the  anti-legionella  function for  boilers  with  domestic  hot  water  tank (available  with  OTBus  connection  between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol). Default set to OFF. This value can be set to ON or OFF. By setting this parameter to ON; every 20 domestic hot water request  cycles a  request to replenish the tank is sent with a domestic hot water delivery  setpoint  of  65°C.  If  the  20  cycles have not be performed within one week, a request to replenish the tank is sent with a domestic hot water delivery setpoint of 65°C on Saturday at 1.00 a.m. 24 CLOCEnabling domestic hot water timer for boilers with domestic hot water tank (available with OTBus connection between the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol). Default set to OFF.  This value can be set to ON or OFF.  Setting this parameter to ON, the domestic  hot  water  time  periods  can  be programmed, as explained in "3.8 Setting the DHW time program" page 72.26 tSFtThe  parameter  will  only  be  shown  if  the SEnS parameter is OFF (available with OTBus connection  between  the  WiFi  Box  and  the boiler  or  the  RF  receiver  and  the  boiler  or RiCLOUD  and  the  boiler,  if  provided  for  by the OTBus protocol). Default set to 10°C. The value can be set from 1°C to 20°C. The value set for this parameter will be subtracted from the  heating  delivery  setpoint  calculated  by RiCLOUD (tSEt), only in AUTO   operating mode, during the  T2 (economy) or T1  (anti-freeze) time period.27 SEnSEnabling/disabling room sensor to activate pure climate control (thermoregulation from a single external probe). Default set to ON. This value can be set to ON or OFF. In AUTO  , MAN   and PARTY   operating modes only, by setting this parameter to OFF the heating/cooling request is processed as follows:
85ENGLISHParameterDescription −In ON/OFF mode, the heating/cooling request is always active (relay closed) if the T3 (comfort) time period is active. −In OTBus mode, the heating request is always active (only with the external probe connected to the boiler or the external web probe via the APP) and the heating setpoint temperature is calculated using the external probe value only. The value set for parameter  26 (tSFt) is  subtracted from the heating delivery setpoint calculated by RiCLOUD (tSEt), only in AUTO   operating mode, during the T2 (economy) or T1 (anti-freeze) time period. 9 This function uses one RiCLOUD only.28 FCLOTime display setting. Default set to 24-hour clock. The format can be set to the 12- or 24-hour clock. Setting  the  parameter  to  12H,  the  eld  is display in the 12-hour a.m./p.m. format.29 CHOtEnabling/disabling  heat  request  via  OTBus (available  with  OTBus  connection  between  the WiFi Box and the boiler or the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol). Default set to ON. This value can be set to ON or OFF. Setting this parameter to OFF,  RiCLOUD  thermostat  does  not  consider  the heating request via OTBus to the boiler.30 btLtEnable/disable backlighting.ON/OFF Congurable value: set to OFF so that the backlighting will not switch on at every operation  thus  making  the  batteries  last longer.  Press  the  button  SET/PROG  or  ESC/MODE to go back to the HOME page.31 HHbOMaximun  boilerl  central  heating  temperature  setpoint  (available  with  OTBus  connection between  the  WiFi  Box  and  the  boiler  or  the RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol).The value can be set between 80°C and 40°C (for high temperature heating) or from 45°C to 20°C (for low temperature heating). This parameter has to be set by the Authorised Service Centre.00 EHItPress  the  SET/PROG  button  or  ESC/MODE  to return to the HOME screen.
863.13  Linking functionRiCLOUD linking with the WiFi Box RiCLOUD and the WiFi Box in the WiFi RiCLOUD package are already linked.If installing an additional RiCLOUD, follow the procedure below.Ensure that RiCLOUD and the WiFi Box are connected to a power source and there are no alarms.Press  the  prismatic  dome  clear  LED button  (A)  and  hold  for  5  seconds until  the  green  and  red  LEDs  ash slow  (1  sec)  at  the  same  time  (once linked the ash will return to normal).WPS/Smartlink Outputs BoilerAWiFi BoxFrom  RiCLOUD HOME screen, press the  ESC/MODE  button  and  hold  for 5  seconds  to  display  the  following (alternating) information.  EXAMPLE OF LINKED RICLOUD  1231  Radio frequency channel 2 Receiver (WiFi Box) number3 Radio frequency addressEXAMPLE OF LINKED RICLOUD44  Transmitter number (RiCLOUD)To  complete  the  link,  press  the  SET/PROGRAM button or wait for RiCLOUD to return to the HOME screen. 9 This  may  take  up  to  2 minutes,  after  which  RiCLOUD automatically  returns  to  the HOME screen.Should  the  link  not  be  successful, please contact the Authorised Service Centre.
87ENGLISHLinking the boiler RF receiver to the WiFi BoxIf installing a boiler RF receiver, please follow the procedure below.Press  the  prismatic  dome  clear  LED button (A) on the WiFi Box and hold for 5 seconds until the green and red LEDs  ash  slow  at  the  same  time  (1 second).Press  and  hold  again  for  5  seconds until  the  green  and  red  LEDs momentarily  switch  off  and  then ash slowly (every 2 seconds).WPS/Smartlink Outputs BoilerBAWiFi BoxRicevitore RF caldaiaBoiler RF receiverPress  the  prismatic  dome  clear  LED button  (B)  on  the  boiler  RF  receiver and hold for 5 seconds until the green and  red LEDs ash  frequently  (every 0.5 seconds) at the same time. The WiFi Box ashes frequently (every 0.5  seconds)  to  show  the  link  has been made. Press the button on the WiFi Box again to conrm.The boiler RF receiver auto-congures to normal operating mode. 9 This may take up to 2 minutes, after  which  the  RiCLOUD automatically  returns  to  the HOME screen.Should  the  link  not  be  successful, please contact the Authorised Service Centre.Linking the boiler RF receiver to the RiCLOUD RiCLOUD  programmable  thermostat can be linked to a wireless receiver if  you  want  to  replicate  the  relay functionality on  the  thermostat in a remote zone (e.g. zone valve), which is not accessible with a cable (wireless access).Follow  the  procedure  below  to  link them:Press  the  prismatic  dome  clear  LED button on the boiler RF receiver and hold  for  5  seconds  until  the  green and red LEDs ash slow (1 seconds) at the same time (once linked the ash returns to normal).
88From  RiCLOUD HOME screen, press the  ESC/MODE  button  and  hold  for 5  seconds  to  display  the  following (alternating) information:EXAMPLE OF LINKED RICLOUD 1231  Radio frequency channel 2 Receiver (WiFi Box) number3 Radio frequency addressEXAMPLE OF LINKED RICLOUD44  Transmitter number (RiCLOUD)To  complete  the  link,  press  the  SET/PROGRAM button or wait for RiCLOUD to return to the HOME screen. 9 This  may  take  up  to  2 minutes,  after  which  RiCLOUD automatically  returns  to  the HOME screen.Should  the  link  not  be  successful, please contact the Authorised Service Centre.
89ENGLISH4  ALARMS AND OPERATING STATUSES4.1  LED notication lights for the WiFi Box and boiler RF receiver **LEDGreen LEDRed StatusF05 Relay = closed (only for ON/OFF connections)F1 Relay = open (only for ON/OFF connections)ON OTBus connection = OK (for OTBus connection)ON F01 Boiler alarm (only for OTBus connection)F05F1ON ON Network or RF error F05 F05 WPS mode active – Wait for WPS signal from the router*F05 WPS signal accepted*F05 F05 Smartlink mode active*F1 F1 Encoded RF mode active**  Only for WiFi Box**  The notication lights on boiler RF receivers may differ with respect to the table.LEDON  = remains onF05 = quick ash (every 0.5 seconds)F1   = slow ash (every 1 second)
90Operation of the prismatic dome clear LED button on the WiFi Box and boiler RF receiverWPS/Smartlink Outputs BoilerAWiFi BoxIn case of a boiler alarm (available with  OTBus  connection  between  the WiFi  Box  and  the  boiler  or  the  RF receiver and the boiler or RiCLOUD and the boiler, if provided for by the OTBus protocol),  the alarm can  be  reset  by pressing the prismatic dome clear LED button (A) (for alarm A99, reset from the boiler).With an ON/OFF connection, the relay can be activated or deactivated by pressing the prismatic dome clear LED button (A).4.2 Boiler and RiCLOUD alarmsThe  alarm  is  shown  in  alternation with the room temperature detected by RiCLOUD on the display.In case of a boiler alarm (available with  OTBus  connection  between  the WiFi Box and the boiler, if provided for by the OTBus protocol), the alarm can be  reset  by  pressing  the  BACK/RESET button   (for alarm A99, reset from the boiler). 9 RiCLOUD alarms (rIE, E82, E83) and the temporary boiler alarms may be automatically reset once the fault has been resolved.
91ENGLISHAlarm Description SolutionrIESemi-automatic ll function.  −See "3.6.3 SEMI-AUTOMATIC FILLING function" page 69 −Check the system pressure. −Should  you  not  be  able  to remove  the  alarm,  please contact  the  Authorised  Service Centre.ErrRiCLOUD room temperature sensor damaged. Cannot be repaired.  −Replace RiCLOUD  −Contact  the  Authorised  Service Centre.E82Communication failure between the RiCLOUD and the WiFi Box.  −Check  the  distance  between RiCLOUD  and  the  WiFi  Box  (see page 211). −Remove  and  then  reinsert  the batteries. −Check  that  the  WiFi  Box  is connected to a power source. −Check  the  coupling  between RiCLOUD  and  the  WiFi  Box  (see "3.13 Linking function" page 86). −Contact  the  Authorised  Service Centre.E83OTBus communication failure between the WiFi Box and the boiler or the RiCLOUD and the boiler. −Check  the  OTBus  electrical connection  and  the  maximum distance between  the WiFi Box and the boiler OTBus terminal or between RiCLOUD and the boiler OTBus terminal (see page 211). −Contact  the  Authorised  Service Centre.
92E84Hardware error RiCLOUD. Cannot be repaired.  −Replace RiCLOUD.  −Contact  the  Authorised  Service Centre.A01….99 Boiler alarm.  −See boiler manual.A99Too many boiler resets performed via remote control. −Reset from the boiler.Batteries running lowTo replace the batteries, remove RiCLOUD from its base. −Replace the batteries.  −Check that the contacts are not rusty.  −Replace RiCLOUD.  −Contact  the  Authorised  Service Centre. 9Replace  the  batteries  as soon as possible. When the low battery warning is on, correct operation of RiCLOUD and any RF communication is no longer guaranteed.
93ENGLISHAlarm DescriptionA01-A10Burner ignition/detection failure after numerous attemptsA02-A20 Limit thermostat trippedA03-A30 Flue gas thermostat and/or safety thermostat and/or air pressure switch and/or fan faultA04-A40 Primary circuit pressure insufcientA06-A60 DHW NTC probe anomalyA07-A70Alarm relating to heating NTC probe and/or delivery NTC probe and/or excessive differential between the delivery and return NTC probesA08 Alarm relating to return NTC probe and/or excessive differential between probesA09-A91 Flue gas NTC probe or dirty exchanger alarmA77 Low external temperature limit thermostat trippedA99 Too many resets performed via remote controlThe alarm history can be viewed under the parameter ALL from the advanced programming menu.For details of boiler alarms, please see the boiler installer manual.
FCC StatementThis device complies with Part 15 of the FCC Rules. Operation is subject to the following twoconditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.Changes or modifications not expressly approved by the party responsible for compliance couldvoid the user's authority to operate the equipment.NOTE: This equipment has been tested and found to comply with the limits for a Class B digitaldevice, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonableprotection against harmful interference in a residential installation. This equipment generates, uses instructions, may cause harmful interference to radio communications. However, there is noguarantee that interference will not occur in a particular installation. If this equipment does causeharmful interference to radio or television reception, which can be determined by turning theequipment off and on, the user is encouraged to try to correct the interference by one or more ofthe following measures:-- Reorient or relocate the receiving antenna.-- Increase the separation between the equipment and receiver.-- Connect the equipment into an outlet on a circuit different from that to which the receiver isconnected.-- Consult the dealer or an experienced radio/TV technician for help.IC StatementThis device complies with Industry Canada’s licence-exempt RSSs. Operation is subject to the following two conditions:(1) This device may not cause interference; and(2) This device must accept any interference, including interference that may cause undesired operation of the device.The distance between user and products should be no less than 20cm.Cet appareil est conforme aux CNR exemptes de licence d'Industrie Canada . Son fonctionnement est soumis aux deux conditions suivantes :( 1 ) Ce dispositif ne peut causer d'interférences ; et( 2 ) Ce dispositif doit accepter toute interférence , y compris les interférences qui peuvent causer un mauvais fonctionnement de l'appareil.la distance entre l'utilisateur et les produits devraient être au moins 20 cm.The distance between user and products should be no less than 20cm