Specifications:Temperature Monitor Range:  32.2°F to 99.9°F (0.0°C to 37.7°C)Setpoint Range:  60.0°F to 85.0°F (15.5°C to 29.5°C)*Setpoint:  72°F (22°C)*Comfort Limits:  65.0°F (18.5°C) cooling  85.0°F (29.5°C) heating Display Format:  Liquid Crystal Display (LCD)Backlight:  EL blue greenSampling Rate:  Every 15 secondsAccuracy:  ± 1°F (0.5°C)Power Source:  24VAC/DC (20 minimum to 32 maximum)Load Rating:  1.5 amps per load circuit *Fan Control:  Selectable:  Auto cycle, Low, Medium, High    Heat/Cool Control:  1 heat and 1 cool circuit (see system function)*Economy Limits: Maintains room temperature between 60.0°F and 85.0°F  (15.5°C and 29.5°C) when thermostat is in economy (ECON) mode*Fan Purge Timer:  30 secondsAnti-short Cycle:  3 minute hold in no call state at all times*Cycle Rate:  8 cycles per hour* Differential:  0.4°F * Display Mode: Setpoint temperature* System Function:  Heat and Cool*See Field Programming InstructionsApplication:This thermostat is a 24 volt heating and cooling digital temperature control designed to operate 2 or 4-pipe fan coil systems.  Switching of load circuits is through relay contacts.  Fan outputs can be configured to operate 3, 2 or single speed fan motors. The fan control also has configurations for user select fan speed with economy function, continuous fan or auto cycle fan. This thermostat operates on a single setpoint with automatic changeover from heating to cooling.   Installation Notice:This high performance digital thermostat is designed to provide many years of superior comfort control when properly installed and maintained.  To achieve maximum performance, this device is designed to draw room air into itself continuously.  Reasonable care must therefore be taken with regard to air quality at the time of installation as well as during periods of normal use, see operating conditions below.Operating Conditions:The electronic mechanisms incorporated within this unit REQUIRE operating conditions similar to other electronic devices intended for INDOOR USE ONLY, such as would be acceptable for TV and similar household appliances.  Relative humidity must be less than 95% and the atmosphere must be non-condensing.  For operation in bathrooms, shower or pool areas, outdoor entry ways, greenhouses and similar applications, order the “-k” option.  This product includes protection for coastal/tropical application, therefore it is suitable for use in high humidity environments.  Air quality must be maintained FREE of heavy dust or debris which may infiltrate the interior of this device.  Installation in any space which is unfinished or undergoing repainting or general rehabilitation is also considered product abuse.  This device should be removed from service during any local construction activity.Cleaning:This device incorporates a high impact polycarbonate enclosure which is easily cleaned with a dry cloth or vacuum brush.  Occasional soiling may be cleaned with a soft cloth lightly dampened with water and/or mild cleaning solution.  IN NO CASE should this device be directly sprayed with or exposed to free flowing liquids, including water, which could penetrate its interior. FAILURE TO OBSERVE ANY OF THE ABOVE CONDITIONS OF USE WILL COMPLETELY VOID THE SUPPLIER WARRANTY.                                                                        CAUTIONMAKE SURE UNIT IS PROPERLY CONNECTED.  DAMAGE TO THE DIGITAL CONTROL CAN BE CAUSED BY MISWIRING, WHICH WILL VOID THE WARRANTY.  FOR SAFETY REASONS ALWAYS USE WIRE NUTS ON ALL WIRE CONNECTIONS!!! ◦ +3V SB1 SB2 COM SEN3 SEN2 REF +3V SB1 SB2 COM +3V SB1 SB2 COM ◦ ◦ Installation and Operating Instructions Premier Series 24 Volt  PFC-M24 PFC-M24-RS SETPOINT AUTO ◦ ◦ System Mode Switch HEAT/AUTO/COOL °F/°C PFC-A24 PFC-A24-RS  SETPOINT AUTO ◦ ◦ Decrease temperature Switches between °F and °C Selects fan function Increase temperature °F/°C                   4-PIPE FAN COIL, 2-PIPE ELECTRIC HEAT OR                    ELECTRONIC AQUASTAT INSTALLATION:This device should be installed and serviced by a qualified technician.  Junction box mounting is highly recommended.1.      Caution:  Make sure that power has been disconnected.2. All wiring must comply with applicable codes and ordinances.3. A thorough check-out of the system should be made after   installation is complete.4. If fan motor is larger than 1/4 HP and/or electric heaters are used   for heating, additional power relays will be required5. If retrofitting old thermostat, remove old thermostat from the   junction box, carefully noting the wire connections on the old unit.     Record wire color and terminal legends in spaces provided.Disconnect old thermostat and remove any existing backplate or mounting plate.Old thermostatwire functionPower FeedCommonHeatCoolLow FanMedium FanHigh FanCablewire colorUser Note:  The top of this unit will become warm to the touch.  This is a  normal operation.  Internal heating is employed to continuously convect  air upward through the thermostat, thereby improving room air temperature  measurement.  Direct conflict with a downward ceiling fan or system fan air  flow may result in false temperature reading.  Locate thermostat to avoid  interference. Screw: 6/32 x 3/4"Mounting BracketStandardJunctionBox6. Install the mounting bracket to the   junction box with the two long   mounting screws provided.    See mounting detail to the right. Note:  If application involves a   double ganged junction box,   a backplate will be required for a   complete installation.    Please consult your supplier.1 ◦ SEN3 SEN2 REF +3V SB1 SB2 COM ◦ ◦ ◦
New Stat Wire Function Control Feed Load Feed Common Heat Cool Low Fan Medium Fan High Fan New Stat Wire Color Red Orange Black White Yellow Green Blue Violet Cable Wire Color 7. From the wire chart found in step 5, assign, according to function,   the cable wire colors to the thermostat wire legend provided below.    Note:  The control feed and the load feed will be connected together   for the 4-pipe installation.  If this is a new installation, record the cable   wire colors in the thermostat legend provided below.8.  Connect the thermostat wires to the cable wires recorded in step 7.NOTE:  When the thermostat is programmed for 2 speed the High fan wire will not be used.  Also, when the thermostat is programmed for single speed fan,  only the low fan wire connection will be used.  Isolateany unused fan speed wires from the thermostat. 10. Turn power on.        At start up,  the low fan will automatically run for three minutes to   cycle room air.        If cooling or heating is required, it may become active after the   first 30 seconds of fan run time.  Room  Temperature Indicator Fan Icons Mode Icons  Cool Icon  Heat Icon Diagnostic Indicator Programming Icons Scale Indicator Setpoint Indicator ROOM  SETPOINT AUTO ECON PROG ERASE DIAG ◦ ◦ +3V SB1 SB2 COM SEN3 SEN2 REF +3V SB1 SB2 COM +3V SB1 SB2 COM ◦ ◦ ◦ ◦ 2 Red Wiring Diagram 4-pipe Fan Coil3 Speed Fan (default configuration)Violet HIGH 24VACBlue MEDIUMWhiteOrangeBlackYellowGreen LOW FanCoolValve HeatValveCommonFeedRed Wiring Diagram 4-pipe Fan Coil2 Speed Fan (programmed setting)Violet NOT USED 24VACBlue MEDIUMWhiteOrangeBlackYellowGreen LOW FanCoolValve HeatValveCommonFeed9. Push the wires into the junction box.  Tilt   the thermostat so that the bottom of the   thermostat is resting on the mounting tabs   of the mounting plate.  Push the top of the   thermostat towards the wall and secure into   place with the self-tapping screw as shown   to the right.StandardJunctionboxNOTE:  For more details on Electronic Aquastat installions, refer to Remote Sensor/Aquastat Option on page 5.BASIC FUNCTIONS             Adjust Temperature Setpoint:  Press up button (    ) to raise the temperature (warmer)   Press down button (    ) to lower the temperature (cooler)  Select Fan Operation:   Press fan button (     ) to select the following fan functions*     Continuous HIGH speed fan           Continuous Medium speed fan     Continuous LOW speed fan     AUTO on/off with automatic speed change     ECON, economy function     *fan function sequence with auto as the starting point  Change Scale Units:   Slide the °F/°C switch to the left to display °F   Slide the °F/°C switch to the right to display °C   When the °F/°C switch is invoked, the thermostat will reset and    display the default setpoint in the selected scale.  Cycle Timing:  (Anti-short cycle protection)   3 minute (minimum) dwell time in no-call states (both heat and cool).    1 minute (minimum) dwell time in call states (both heat and cool).    Temperature is sampled every 15 seconds. 9510-0712Rev D    10-23-07Check Heating: Press and hold the up button until the heat   symbol appears on the LCD.  Within 4 seconds   the heat valve will be activated. For manual  changeover models place the system mode   switch in the heat or auto position. Note:  Room temperature must be below   the Comfort Heating Limit 85.0°F (29.5°C)   for heating to become active.HEAT/AUTO/COOL °F/°C SETPOINT AUTO ◦ SEN3 SEN2 REF +3V SB1 SB2 COM Check Low Fan Function:  Press the fan button.  One fan symbol will appear      on the LCD.  Low fan speed will turn on immediately.      Medium or high fan, if active, will turn off.SETPOINT ◦ ◦ Check Medium Fan Function:  Press the fan button.  Two fan symbols will appear      on the LCD.  Low fan will turn off and medium fan      will turn on immediately.SETPOINT ◦ ◦ Check High Fan Function:  Press the fan button.  Three fan symbols will appear    on the LCD.  Medium fan will turn off and high fan    will turn on immediately.SETPOINT ◦ ◦
◦ TROUBLE SHOOTING TESTS (4-Pipe System)Voltage: When using a voltmeter across "Black" and "Red" and      “Black” to “Orange”, voltage must be 24VAC.  To Check Continuity:  (Using a Voltmeter with all loads connected)A)  When the thermostat is calling for Cooling, meter should read      24VAC from “Black” to “Yellow”.  When cooling is deactivated,      meter should read 0VAC from “Black” to “Yellow”.B)  When the thermostat is calling for Heating,  meter should read      24VAC from “Black” to “White”.  When heating is deactivated,      meter should read 0VAC from “Black” to “White”.C)  When the thermostat is calling for High Fan,  meter should read      24VAC from “Black” to “Violet”.  When all fan speeds are turned      off,  meter should read 0VAC from “Black” to “Violet”. D)  When the thermostat is calling for Medium Fan, meter should read      24VAC from “Black” to “Blue”.  When all fan speeds are turned off,     meter should read 0VAC from “Black” to “Blue”. E)  When the thermostat is calling for Low Fan,  meter should read      24VAC from “Black” to “Green”.  When all fan speeds are turned      off, meter should read 0VAC from “Black” to “Green”.2-PIPE FAN COIL INSTALLATION: (Bimetal Aquastat ONLY)NOTE:  For Electronic Aquastat applications (RS models) use the4-Pipe wiring ONLY.Follow the instructions for a 4-pipe installation with the following exceptions:Old Thermostat Function Control Feed Common Water Valve Aquastat Heat Aquastat Cool Low Fan Medium Fan High Fan  Cable Wire Color New Stat Wire Function Control Feed Common Load Feed (valve) Aquastat Heat Aquastat Cool Low Fan Medium Fan High Fan New Stat Wire Color Red Black Orange White Yellow Green Blue Violet Cable Wire Color NOTE:  When the thermostat is programmed for 2 speed the High fan  wire will not be used.  Also, when the thermostat is programmed for  single speed fan, only the low fan wire connection will be used.  Isolate any unused fan speed wires from the thermostat.  +3V SB1 SB2 COM SEN3 SEN2 REF +3V SB1 SB2 COM +3V SB1 SB2 COM ◦ ◦ ◦ ◦ 3  9510-0712Rev D    10-23-07HEAT/AUTO/COOL °F/°C SETPOINT AUTO Check Cooling: Press and hold the down button until the cool   symbol appears on the LCD.  Within 4 seconds   the cool valve will be activated.  For manual  changeover models place the system mode   switch in the cool or auto position.   Note:  Room temperature must be above   the Comfort Cooling Limit 65°F (18.5°C)  for cooling to become active.Adjust setpoint as follows: 6.0°F or more ABOVE room temperature 3.0°F to 5.9°F ABOVE room temperature 0.4°F BELOW to 2.9°F ABOVE room temperature 1.9°F to 0.4°F BELOW room temperature 2.0°F BELOW room temperature (cool threshold) Heating Currently Active FUNCTION CHART MED Lo Hi Med Lo Med Med Lo Med Lo Off Med Lo Med HIGH Hi Hi Hi Hi Hi Lo On On On Off Reset Set LOW AUTO COOL HEAT FAN SPEED SYSTEM Lo Adjust setpoint as follows: 2.0°F ABOVE room temperature 1.9°F ABOVE to 1.9°F BELOW room temperature 2.0°F BELOW room temperature Heating or Cooling Not Currently Active MED Lo Lo Med Lo Off Med Lo Med HIGH Hi Hi Hi Set Off Off Set LOW AUTO COOL HEAT FAN SPEED SYSTEM Lo Adjust setpoint as follows: 2.0°F ABOVE room temperature (heat threshold) 1.9°F to 0.4°F ABOVE room temperature 0.4°F ABOVE to 2.9°F BELOW room temperature 3.0°F down to 5.9°F BELOW room temperature6.0°F or more BELOW room temperature Cooling Currently Active MED Lo Lo Med Lo Off Med Lo Med Lo Med Med Lo Med HIGH Hi Hi Hi Hi Hi Hi Set Reset Off On On On LOW AUTO COOL HEAT FAN SPEED SYSTEM Lo ◦ SEN3 SEN2 REF +3V SB1 SB2 COM ◦ ◦ ◦ RedWiring Diagram 2-pipeFan Coil with 3 Speed Fan24VACBlackGreen  LOWBlue  MEDIUMViolet  HIGHOrangeYellowWhiteFanValveCommonFeedAquastat (mounted on watersupply line) or season changeswitchRedWiring Diagram 2-pipeFan Coil with 2 Speed Fan24VACBlackGreen  LOWBlue  MEDIUMViolet  NOT USEDOrangeYellowWhiteFanValveCommonFeedAquastat (mounted on watersupply line) or season changeswitch
◦ TROUBLE SHOOTING TESTS (2-Pipe System)Voltage: When using a voltmeter across “Black" and "Red", voltage must be 24VAC.  To Check Continuity:  (Using a Voltmeter with all loads connected)Cold pipe or season switch set to cool: (power supplied through yellow wire)A)  When the thermostat is calling for cooling and low fan,  meter      should read 24VAC from “Black” to “Orange” and from “Black” to      “Green”. When cooling is deactivated, meter should read 0VAC      from “Black” to “Orange” and “Black” to “Green”.B)  When the thermostat is calling for cooling and medium fan,    meter should read 24VAC from “Black” to “Orange” and from      “Black” to “Blue”. When cooling is deactivated, meter should read     0VAC from ”Black” to “Orange” and “Black” to “Blue”.C)  When the thermostat is calling for cooling and high fan,  meter      should read 24VAC from “Black” to “Orange” and from “Black” to      “Violet”.  When cooling is deactivated, meter should read 0VAC      from ”Black” to “Orange” and “Black” to “Violet”.Hot pipe or season switch set to heat: (power supplied through white wire)A)  When the thermostat is calling for heating and low fan,  meter      should read 24VAC from “Black” to “Orange” and from “Black” to      “Green”. When heating is deactivated, meter should read 0VAC      from ”Black” to “Orange” and “Black” to “Green”.B)  When the thermostat is calling for heating and medium fan,    meter should read 24VAC from “Black” to “Orange” and from      “Black” to “Blue”. When heating is deactivated, meter should read     0VAC from ”Black” to “Orange” and “White” to “Blue”.C)  When the thermostat is calling for heating and high fan,  meter      should read 24VAC from “Black” to “Orange” and from “Black” to      “Violet”. When heating is deactivated, meter should read 0VAC      from ”Black” to “Orange” and “Black” to “Violet”.+3V SB1 SB2 COM SEN3 SEN2 REF +3V SB1 SB2 COM +3V SB1 SB2 COM Diagnostic Mode: Press and hold the "up" and "down" buttons together until "DIAG" appears on the display.Diagnostic mode will alternately displaysetpoint and room temperature every 8 seconds.SETPOINT AUTO DIAG ◦ ◦ The current operating fan mode will also show. Low speed fan will display a single fan icon,two speed fan will display two fan icons and three speed fan will display three fan icons.ROOM AUTO DIAG ◦ ◦ ◦ ◦ 4 Adjust setpoint as follows: 6.0°F or more ABOVE room temperature 3.0°F to 5.9°F ABOVE room temperature 0.4°F BELOW to 2.9°F ABOVE room temperature 1.9°F to 0.4°F BELOW room temperature 2.0°F BELOW room temperature (cool threshold) Heating Season, Hot Pipe FUNCTION CHART MED Lo Hi Med Lo Med Med Lo Med Off Off Off Off Off HIGH Hi Hi Hi Off Off Off On On On Off Reset Set LOW AUTO COOL HEAT FAN SPEED SYSTEM Lo Adjust setpoint as follows: 2.0°F ABOVE room temperature, Hot Pipe 1.9°F ABOVE to 1.9°F BELOW room temperature 2.0°F BELOW room temperature Heating or Cooling Not Currently Active MED Lo Lo Med Off Off Off Lo Med HIGH Hi Off Hi Set Off Off Set LOW AUTO COOL HEAT FAN SPEED SYSTEM Lo Adjust setpoint as follows: 2.0°F ABOVE room temperature (heat threshold) 1.9°F to 0.4°F ABOVE room temperature 0.4°F ABOVE to 2.9°F BELOW room temperature 3.0°F down to 5.9°F BELOW room temperature6.0°F or more BELOW room temperature Cooling Season, Cold Pipe MED Off Off Off Off Off Off Lo Med Lo Med Med Lo Med HIGH Off Off Hi Hi Hi Hi Set Reset Off On On On LOW AUTO COOL HEAT FAN SPEED SYSTEM Lo SETPOINT ECON ◦ ◦ To deactivate the diagnostic mode, press the  "fan" button until the fan activity moves to  "ECON".  "DIAG" will disappear from the display. Press the "fan" button again to return to  operating mode.   Diagnostic mode can also be deactivated by  changing the °F/°C slide switch.   SEN3 SEN2 REF +3V SB1 SB2 COM ◦ ◦ ◦
◦ +3V SB1 SB2 COM SEN3 SEN2 REF Optional remote functions PFC-ALV-RS and PFC-MLV-RS models ONLY  Remote Setback Terminal Block Remote Sensor Terminal Block Remote Sensor/Aquastat Option: The remote sensor option features a dual mode external sensor function.  SEN2 is to be used only as a room temperature sensor (order PSG P-RS).  SEN3 is to be used only with the Electronic Aquastat Kit (order PSG P-AK).  The REF terminal is common to both sensor inputs.  To activate the SEN2 or SEN3 terminals see programming instructions.  Both sensor functions may be used at the same time, having both electronic aquastat and remote room temperature capability.  When the remote sensor is connected, it may be used to control the thermostat instead of the on board sensor or it may be averaged with the on board sensor.  Use only 3 conductor cable or shielded 2 conductor cable.  Connect the shield or the third wire to the COM terminal.  Remote Setback/Shutdown Option: The remote setback features a dual mode function.  SB1 is the input for remote setback (economy) and SB2 is the input for remote shutdown mode.  Setback mode when energized will remotely place the thermostat in economy mode using the programmable economy heat and cool setpoints.  Shutdown mode when energized will remotely place the thermostat in disable mode.  The thermostat, at this time, will not call for heating or cooling until taken out of shut- down mode. To activate the setback or shutdown mode use dry contacts (relays or mechanical switch) to connect the +3V terminal to the appropriate SB1 or SB2 terminal.  An open circuit on SB1 or SB2 will disable the remote function.    A COM terminal is provided for active type remote switch gear such as the electronic motion sensor.  Do not use the COM terminal for any other application.   +3V SB1 SB2 COM door  switch window switch Dry contact connections +3V SB1 SB2 COM window switch (-) (+3vdc) Motion Sensor and dry contact Motion Sensor ◦ ◦ Mount the Electronic Aquastat Sensor to the water pipe.  The best location is to be as close to the main pipe as possible and attached before the water valve connection.  IMPORTANT:The electronic aquastat sensor replaces the bimetal switchwhich is common in most 2-pipe heat/cool fan coil systems.This allows for the thermostat to directly control the equipment as well as provide for alterations in change-over temperature thresholds.  Follow the standard 4-pipe wiring diagram. Cool wire will control the heat/cool valve,  the heat wire will operate as an auxilliary electric heat switch (depending on fan coil equipment).Isolate all of the unused wires.WaterMain ValveSensor WireTies◦ ◦ 5 ◦ Refer to the programming instructions for selecting the aquastatsensor function, temperature changeover settings, output configurations, purge frequency and purge time duration.  The thermostat will monitor pipe temperature every 5 seconds.  For a valvelss systems,  select the 2Pn configuration setting since this will bypass the valve purge functions and provide heating or cooling based on pipe temperature alone.   The 2PS and 2PE configurations operate with a valve purge functionto prevent incorrect temperature readings from static or standing water in the pipe.  The valve purge operates on a programmed interval(purge frequency) for a programed duration (purge time duration)in the event of low activity over an extended period of time.  If the heat or cool call has lasted for more than three minutes,  the pipe temperature heat or cool mode is rechecked to verify proper operating mode.              Function charts on next pageSEN3 SEN2 REF  Room Sensor Aquastat Sensor +3V SB1 SB2 COM ◦ ◦ ◦
◦ +3V SB1 SB2 COM SEN3 SEN2 REF +3V SB1 SB2 COM +3V SB1 SB2 COM ◦ ◦ ◦ ◦ PSG Controls, Inc.LIMITED WARRANTY POLICYPSG Controls, Inc. (Hereinafter referred to as "PSG") warrants the following:Only cataloged products sold to distributors are warranted to the original purchaser, to conform with specifications furnished or approved by PSG, and to be free from defects in material and workmanship, for a period of one (1) year from the date of purchase, unless specified in writing for a different period.Any PSG product that proves defective within the above described warranty period will be repaired or replaced (at PSG's option) free of any charge if returned to the PSG factory at 1225 Tunnel Road, Perkasie, PA. 18944 with transportation charges prepaid.  Prior to returning this product to PSG, the purchaser shall give PSG notice in writing stating how this product fails to fulfill this warranty.  No product shall be accepted for repair or replacement without a required written notice and without prior written authorization and shipping instructions having been received by the purchaser from PSG.  Only PSG's factory is authorized to perform services under this warranty.This warranty does not extend to any product that has been subjected to misuse, abuse, neglect, accidents, alterations, improper installation or use in violation of the printed instructions furnished by PSG.  This warranty neither applies to batteries nor deterioration of, nor damage to the product caused by the use of faulty batteries.  Final determination as to whether any product is actually defective rests solely with PSG.  This warranty is expressly in lieu of all other agreements and warranties, expressed, implied, or statutory and PSG has no other obligations or liabilities in connection with this product.  In no event shall PSG's obligation or liability hereunder exceed the purchase price of this product.  PSG SHALL NOT IN ANY EVENT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.  This warranty gives you specific legal rights, and you also have other rights which vary from state to state.  Some states do not allow the exclusion or limitation of incidental or consequential damages, or implied warranties, so the above limitations or exclusion may not apply to you.Toll free technical assistance is availablevia our technical hotline: 1-800-523-2558Mon-Fri, 8:00 A.M. to 4:30 P.M. Eastern Standard Time1225 Tunnel Road - Perkasie, PA 18944 - 215-257-3621 - Fax 215-257-4288Web site - www.psgcontrols.com              E-mail - sales@psgcontrols.com R  PSG Controls, Inc. 6  9510-0712Rev D    10-23-072Ps Functions:System with a single valve used for hear and cool.The cooling wire of the thermostat will be used to control the water valve for heat and cool.The heat wire will not be used.FUNCTION CHART 2Ps Adjust setpoint as follows: 6.0°F or more ABOVE room temperature 3.0°F up to 5.9°F ABOVE room temperature 0.4°F BELOW to 2.9°F ABOVE room temperature more than 0.4°F BELOW room temperature Hot Pipe MED Lo Hi Med Lo Med Med Lo Med Lo Off Med HIGH Hi Hi Hi Hi On On On Off LOW AUTO VALVE FAN SPEED Lo Adjust setpoint as follows: more than 0.4°F ABOVE room temperature 3.0°F down to 5.9°F BELOW room temperature 0.4°F ABOVE to 2.9°F BELOW room temperature 6.0°F or more BELOW room temperature Cold Pipe MED Lo Off Med Lo Lo Med Lo Med Lo Hi Med HIGH Hi Hi Hi Hi Off On On On LOW AUTO VALVE FAN SPEED Med 2Pn Functions:System is valveless.Heating and cooling are provided by operating fans only.  The cooling wire of the thermostat will operate similiarly to the 2Ps above, but it is not necessary for connection.The heat wire will not be used.FUNCTION CHART 2Pn Adjust setpoint as follows: 6.0°F or more ABOVE room temperature 3.0°F up to 5.9°F ABOVE room temperature 0.4°F BELOW to 2.9°F ABOVE room temperature more than 0.4°F BELOW room temperature Hot Pipe MED Lo Hi Med Lo Med Med Lo Med Off Off *Off HIGH Hi Hi Hi *Off On On On Off LOW AUTO VALVE FAN SPEED Lo Adjust setpoint as follows: more than 0.4°F ABOVE room temperature 3.0°F down to 5.9°F BELOW room temperature 0.4°F ABOVE to 2.9°F BELOW room temperature 6.0°F or more BELOW room temperature Cold Pipe MED Lo Off *Off Lo Lo Med Lo Med Lo Hi Med HIGH *Off Hi Hi Hi Off On On On LOW AUTO VALVE FAN SPEED Med 2PE Functions:System with a single valve that supplies both hot and cold water and has an auxiliary electric strip heat for use when pipe is cold.The cooling wire of the thermostat will be used to control the water valve for heat and cool.The heat wire will operate auxiliary electric strip heat.FUNCTION CHART 2PE Adjust setpoint as follows: 6.0°F or more ABOVE room temperature 3.0°F up to 5.9°F ABOVE room temperature 0.4°F BELOW to 2.9°F ABOVE room temperature more than 0.4°F BELOW room temperature Hot Pipe MED Lo Hi Med Lo Med Med Lo Med Lo Off Med HIGH Hi Hi Hi Hi On On On Off LOW AUTO VALVE FAN SPEED Lo AUX HT SYSTEM Adjust setpoint as follows: 6.0°F or more ABOVE room temperature 3.0°F up to 5.9°F ABOVE room temperature 1.9°F BELOW to 0.4°F BELOW room temperature 2.0°F BELOW room temperature (cool threshold) Cold Pipe, Active auxiliary heat MED Lo Hi Med Lo Med Med Lo Med Lo Lo Med HIGH Hi Hi Hi Hi On On Off Set Reset LOW AUTO VALVE FAN SPEED Off AUX HT SYSTEM 0.4°F BELOW to 2.9°F ABOVE room temperature  Lo Med Hi On  Lo Adjust setpoint as follows: 2.0°F ABOVE room temperature 1.9°F ABOVE to 1.9°F BELOW room temperature Cold Pipe, Dynamic Dead Band MED Lo Lo Med Lo Off Med HIGH Hi Hi Set Off Off Set Off LOW AUTO VALVE FAN SPEED AUX HT SYSTEM 2.0°F BELOW room temperature  Lo Med Hi Lo Cooling Currently Active 2.0°F ABOVE room temperature (heat threshold) 1.9°F ABOVE to 0.4°F ABOVE room temperature 3.0°F BELOW to 5.9°F BELOW room temperature 6.0°F or more BELOW room temperature Cold Pipe, Active Cooling MED Lo Lo Med Lo Off Med Lo Med Lo Hi Med HIGH Hi Hi Hi Hi Set On On On Off Reset LOW AUTO VALVE FAN SPEED Med AUX HT SYSTEM 0.4°F ABOVE to 2.9°F BELOW room temperature  Lo Med Hi Lo ◦ SEN3 SEN2 REF +3V SB1 SB2 COM ◦ ◦ ◦