Itron NIC515 Radio Module User Manual

Silver Spring Networks Radio Module

User manual

Silver Spring Networks555 Broadway StreetRedwood City, CA 94063www.silverspringnet.comBridges Hardware Guide
Bridges Hardware Guide Silver Spring Networks 2Bridges Hardware GuideBridges Hardware GuideDocument Number BRIDGESv2.0UG_Rev1Confidential Information of Silver Spring Networks®, Inc., provided to licensed customer under NDA.Copyright © 2010, Silver Spring Networks, Inc. All rights reserved.The Silver Spring Networks logo, UtilityIQ®, and UtilOS® are registered trademarks of Silver Spring Networks, Inc. Smart Energy Networks™, Success.Guaranteed™, Metro Gateway™, Metro Relay™, Gas Interface Management Unit™, and Water Interface Management Unit™ are trademarks of Silver Spring Networks, Inc.All other company and product names are used for identification purposes only and may be registered trademarks, trademarks, or service marks of their respective owners. Please consider the environment before printing this document.Revision number Date Revision1 June 16, 2010 Add FCC 15.247 information to Appendix, and incorporate updates to specify max gain for sBridge and eBridge.
Bridges Hardware Guide Silver Spring Networks 3 Contents Contents1.  Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4The eBridge  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4The sBridge  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5Audience. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6Silver Spring Networks Documentation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6Customer Support  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  72.  Deploying Silver Spring Networks Bridges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8Installing Bridges in the Network  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8Types of Bridge Deployments  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  9Deployment Considerations  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  10Supported Network Topologies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11Master/Remote Topology  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11Centralized and Decentralized Master/Remote Deployments   . . . . . . . . . . . . . . . . . . . . . . . . . . . .  12Teaming Topology   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  13Supported Interfaces  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  13Ethernet   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  13Serial . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14Deployment Mode Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14Mixed IPv4 Sample Deployment (Master eBridge only)  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14Serial Master/Serial Remote IPv6 Sample Deployment  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  15IPv6 Addressing in the RF Network   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  16Ethernet Teaming Sample Deployment   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  16A.  Specifications   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  18Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  18eBridge and sBridge Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  18Silver Spring Networks eBridge Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Silver Spring Networks sBridge Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Regulatory Compliance - Module Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  24FCC Certification (Radiated/Conducted Emissions Compliance FCC Part 15.247)  . . . . . . . . . . . .  24Industry Canada Certification (Radiated/Conducted Emissions Compliance RSS-210) . . . . . . . . .  24C-Tick Level 3 (Radiated/Conducted Emissions Compliance AS/NZS4268, AS/NZS4778) . . . . . .  25Silver Spring Networks NIC, FCC IDs: OWS-NIC515 IC: 5975A-NIC515 (sBridge)OWS-NIC506, IC:5875A-NIC506 (eBridge)  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  25Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  27Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  36
Bridges Hardware Guide Silver Spring Networks 41 Introduction1IntroductionSilver Spring Networks’ Distribution Automation (DA) network is designed to help electrical utilities manage field devices such as reclosers, capacitor banks, voltage regulators, and transformers, through more efficient two-way communication. The utilities’ primary tools for monitoring power distribution systems are called Remote Terminal Units (RTUs). Utilities use Supervisory Control And Data Acquisition (SCADA) centers to remotely control substation and distribution equipment through these RTUs. Unfortunately, many RTUs don’t communicate effectively to SCADA management systems, making fault detection and field response difficult. The DA network is designed to address this problem, by building a comprehensive fault-tolerant wireless IP network for two-way communications with distribution RTUs.The devices used to improve communications between the utility’s SCADA central office and its RTUs are the Silver Spring Networks eBridge® and the Silver Spring Networks sBridge®. Each are separate bridge types that differ based on their provided types of port connectors.Note: In this document, whenever applicable, the eBridge and sBridge will be referred to generically as “bridges.” Silver Spring Networks bridges are devices that provide a network for reliable and secure IP-based two-way communications between RTUs and the SCADA system. Faster communication with RTUs helps create a smarter, more reliable electrical grid. The eBridgeThe eBridge provides the following interfaces:•One (1) 100Base-T RJ-45 Ethernet interface.•One (1) DB-9 nine-pin serial interface.•One (1) 900 MHz RF wireless interface. The Ethernet port on the eBridge often connects to the network leading to the back office or the electrical substation SCADA system. A remote eBridge can use its Ethernet port to connect to one
Bridges Hardware Guide Silver Spring Networks 51 Introductionor more RTUs. The RF interface connects all bridges together in a routable RF wireless network for DA communications. A serial port can also be used for RTU connections. The sBridgeNote: sBridges can be used for meter connectivity and for DA RTU connectivity.The application described in this guide is for DA connectivity. sBridges are not designed for use as a master bridge. The Silver Spring Networks sBridge provides similar functionality to the eBridge, with the primary difference being support for two serial interfaces as shown in Figure 2. Serial port 1 is designated as a remote communication port, passing raw serial traffic, for central offices to diagnose, monitor and remotely configure the device. Serial port 2 connects to an RTU and passes DNP3/IP traffic. Either port can be set to function in either mode. As with the eBridge, an RF interface connects the sBridges to the RF network. Figure 1.  Front and back view of the eBridgeFigure 2.  Front and rear view of the sBridgeSerial port USB Ethernet PowerSMA female RF conn.GPIOFront BackSerial Port 1Serial Port 2PowerSMA female RF connector
Bridges Hardware Guide Silver Spring Networks 61 IntroductionFigure 3 shows an example of an RTU, which provides an Ethernet port, two serial ports and terminals for the electrical equipment to which it connects.Note: For more information about network deployments of the eBridge and sBridge, refer to Chapter 2, Deploying Silver Spring Networks Bridges on page 8. For instructions on how to configure eBridges and sBridges, refer to the Bridge Configurator 2.0 User’s Guide.AudienceThis guide is intended for networking and IT professionals and system administrators who perform one or more of the following tasks:•Management of distribution electrical equipment•Network Management•Support information technology•Install, monitor and troubleshoot devicesSilver Spring Networks DocumentationSilver Spring Networks provides the following documents:•Bridges Hardware Guide (this document)•Bridge Configurator 2.0 User’s Guide (software for configuring bridges)•DA NEM 1.0 User’s GuideOther documents may be available from the Silver Spring Networks web site:www.silverspringnet.comFigure 3.  An RTU
Bridges Hardware Guide Silver Spring Networks 71 IntroductionCustomer SupportSilver Spring Networks offers expert technical support and guaranteed response times. Table 1. Support InformationCountry Email Telephone HoursAustralia aus-support@silverspringnet.com +03 9607 8521 9:00 AM - 6:00 PMCanada support@silverspringnet.com Toll free:1-888-SSN-9876(1-888-776-9876)6:00 AM - 6:00 PM US Pacific TimeUnited StatesWorldwide +1-650-298-4298
Bridges Hardware Guide Silver Spring Networks 82 Deploying Silver Spring Networks Bridges2Deploying Silver Spring Networks BridgesEssential to the complete creation of a DA network are the Silver Spring primary devices: the eBridge and the sBridge. The DA network is designed to help utilities effectively communicate with field-installed remote terminal units (RTUs) and power system device controllers in the electrical distribution network.This chapter introduces the use of Silver Spring Networks eBridges and sBridges to create and support the Distribution Automation (DA) network, in the following topics:•Installing Bridges in the Network on page 8•Deployment Considerations on page 10•Deployment Mode Examples on page 14Note: For complete information on configuring and deploying bridges, please see the Bridge Configurator 2.0 User’s Guide.Installing Bridges in the NetworkFour basic steps are required to install eBridges and sBridges for supporting Distribution devices:1. Physical Installation: bridges are not weather-hardened. They must be installed indoors or inside a weather-hardened enclosure, normally in the same enclosure as the RTU or device controller. Four mounting holes are located on the bottom edges of the bridge chassis.2. Bridge Powerup: preferably, along with a battery backup. 3. RF Antenna Attachment: bridges may be connected with different antennas depending on the application. All antennas connect to the SMA female RF connector on the back of all bridges. Keep the following considerations in mind when attaching the proper antenna for the current device:CAUTION: With the sBridge, using an antenna with greater than 3dBi gain is not allowed. Up to 6dBi is allowable with the eBridge.a. The recommended antennas for use in outdoor environments are listed in Table 2, below.b. An N-Female to SMA-male adapter is required for antenna cable connection to the SMA connector on the back of the bridge.c. Because the SMA connector is so small, physical stress may result when connecting a heavy coaxial transmission cable to the back of the eBridge or sBridge during installation. Use a pigtail on the SMA connector to support the weight of a heavy transmission line to the bridge.
Bridges Hardware Guide Silver Spring Networks 92 Deploying Silver Spring Networks Bridges4. Interface Connections: Connect the required interface cables between the bridge and the RTU. Bridges can also connect to voltage, capacitor, tap changer and VAR management controllers, which usually provide their own serial and Ethernet ports. The eBridge or sBridge must be installed in the same enclosure as the controller.Types of Bridge DeploymentsRTUs are key components of the electrical system that act as collection points for sensor data and issue simple commands to control relays, regulators and other electrical system distribution devices. After installation, the bridges bring the RTUs into a new Distribution Automation (DA) network. Figure 4 shows a highly simplified example.Table 2. Available antennas for Silver Spring Network bridgesSSN Antenna Part # Description315-00012 Rev. 5 JPole antenna315-000002 Rev. A sBridge: Rubber Duck, 3dBI maximum gain, SMA Female, AntennaeBridge: Rubber Duck, 6dBI maximum gain, SMA Female, AntennaFigure 4.  Example of a Master/Remote bridge deployment
Bridges Hardware Guide Silver Spring Networks 102 Deploying Silver Spring Networks BridgesDeployment ConsiderationsBefore deploying bridges, allow for the following deployment considerations:•Network topology•Interfaces and protocols•Deployment modesTable 3 summarizes bridge deployment choices in the network.Note: The sBridge operates only as a Remote or in teaming mode. sBridges do not operate as a Master.Table 3. Bridge Deployment Topologies and Modes Deployment Considerations DescriptionNetwork topology Bridges can be deployed in the following network topologies:•Master/Remote (with a centralized Master or decentralized Masters)•Teaming•Combination of Master/Remote and TeamingFor more information about DA network topology, refer to Supported Network Topologies on page 11.Interfaces and protocolsThe eBridge supports the following interfaces and protocols:•Ethernet using IPv4•Serial using IPv4 or IPv6For more information on this topic, refer to Supported Interfaces on page 13.The sBridge supports the following interfaces:•Serial using IPv4 or IPv6All bridges operate RF interfaces in a wireless network, running IPv6 by default.Deployment modes The eBridge supports the following deployment modes:•Mixed IPv4 (Ethernet Master/Serial Remote)•Mixed IPv6 (Ethernet Master/Serial Remote)•Ethernet Master/Ethernet Remote•Ethernet Master/Serial and Ethernet Remotes•Serial Master/Serial Remote•Ethernet Teaming and Serial TeamingThe sBridge supports the following deployments:•Serial Remote•Serial Teaming
Bridges Hardware Guide Silver Spring Networks 112 Deploying Silver Spring Networks BridgesSupported Network TopologiesTo accommodate placements of existing RTUs in the field, bridge units can be deployed in the following network topologies:•Master/Remote Topology•Teaming Topology on page 13•A combination of Master/Remote and Teaming TopologyIn the Master/Remote topology, a master bridge connects to the SCADA (Supervisory Control And Data Acquisition) master. The master bridge communicates over RF to remote bridges that connect in turn to RTUs. Master/Remote TopologyIn the Master/Remote topology, an eBridge master residing at the substation communicates with a larger set of remote bridges in the field. Note: Master and Remote bridges are configured as Masters and Remotes at the manufacturing facility. The first device to be deployed in the DA network is the master device, which can act as the takeout point for DA management traffic bound for the CO. The master bridge may also connect to an Access Point, that itself acts as the takeout point for the DA network. In our examples for this chapter, an Access Point is not shown.To deploy bridges in a Master/Remote topology:•At a substation, connect the master bridge to the local SCADA master.•In the field, connect an eBridge or sBridge Remote to the RTU.When the SCADA master sends a message to the RTU, it passes through the master bridge, which sends it on to the remote bridge in the field, wirelessly via RF. The remote, in turn, passes the message to the RTU. In an extremely simplified manner, this system represents
Bridges Hardware Guide Silver Spring Networks 122 Deploying Silver Spring Networks Bridgesthe DA (Distribution Automation) network, as indicated in Figure 5. Here, the pre-existing electrical distribution grid is overlaid with the bridge-based DA network deployment.Relays are used to extend the RF signal to greater distances and to extend the signal around obstacles in the field.Centralized and Decentralized Master/Remote DeploymentsA Master/Remote deployment can be centralized or decentralized. In a centralized Master/Remote deployment, the SCADA system resides at the back office and all data is drawn back to the central location. This resembles the classic “star” network.Figure 5.  Master/Remote ExampleFigure 6.  Example of a Centralized Master/Remote Deployment
Bridges Hardware Guide Silver Spring Networks 132 Deploying Silver Spring Networks BridgesIn a decentralized Master/Remote deployment, multiple SCADA systems exist (for example, substations in different locations) and data is drawn back to multiple points. Larger DA networks will roughly follow this model.Teaming TopologyIn the Teaming topology, a small set of bridges send each other messages to accomplish specific tasks. There can be up to ten members in a team and an unlimited number of teams. In Teaming, bridges communicate with each other, maintaining all routes to all members of the team.Teaming is useful when dealing with devices such as reclosers that need to communicate with each other to accomplish group switching and fault isolation. These devices require a Teaming topology because it supports routing tables to all possible combinations of paths. Refer to Figure 10 for an illustration of a Teaming topology.Supported InterfacesConnect bridges to a SCADA network and/or RTUs through either of the following interfaces:•Ethernet•SerialEtherneteBridge only: In Ethernet mode, the eBridge connects to an RTU through an Ethernet interface. Because all communication between bridges over the Silver Spring Networks RF network always uses IP, the end point of the network is the RTU. When an eBridge uses Ethernet to communicate with an RTU, it operates like a router and does not require DNP information. When a packet comes across the RF network, the bridge makes a routing decision to send the packet to the destination IP address (an RTU). On master bridges, Ethernet is used to communicate with the SCADA network.Figure 7.  Example of a Decentralized Master/Remote Deployment
Bridges Hardware Guide Silver Spring Networks 142 Deploying Silver Spring Networks BridgesSerialIn serial mode, the remote or teaming bridge connects to an RTU through a serial interface. Because serial RTUs have DNP addresses, the end point of the IP network is the bridge device. Note: The Silver Spring Networks sBridge provides two DB-9 serial interfaces. (The eBridge provides a single DB-9 serial port.) On the sBridge, one port is dedicated to DNP3 traffic for the RTU (Serial Port 2) and the second serial port (Serial Port 1) passes raw serial traffic regardless of protocol, operating as a terminal communication port for remote troubleshooting and control. Either port can function with either setting; use the Bridge Configurator software to configure the ports.When the remote or teaming bridge receives a packet, it removes the IP header and forwards the DNP3 payload serially to the RTU device. During network configuration, a DNP3-to-IP mapping table is created by the Bridge Configurator software; this mapping table is stored on the master bridge. When the master bridge receives a DNP3 packet from the SCADA system, it uses that table to look up the destination IP address, encapsulates the DNP3 packet into an IP header and sends it to the destination bridge, where it is de-encapsulated back into DNP3 and forwarded over the serial port to the destination RTU.The RTUs communicate with the master bridge using the master bridge’s IP address. The eBridge and sBridge support both IPv4 and IPv6 in serial mode. Deployment Mode ExamplesThis section provides the following deployment mode examples:•Mixed IPv4 Sample Deployment (Master eBridge only) below•Serial Master/Serial Remote IPv6 Sample Deployment on page 15•Ethernet Teaming Sample Deployment on page 16Mixed IPv4 Sample Deployment (Master eBridge only)In Mixed deployments, the master bridge connects to the SCADA master through its Ethernet interface, while its associated remote bridges connect to RTUs, in this case voltage regulators shown in Figure 8, through serial ports. The master bridge acts as a router, routing packets between its Ethernet and RF interfaces, and does not perform DNP encapsulation. The remotes encapsulate DNP messages coming from the voltage regulators into IP messages, and pass them on to the master bridge. The remote bridges also de-encapsulate incoming IP messages from the
Bridges Hardware Guide Silver Spring Networks 152 Deploying Silver Spring Networks Bridgesmaster bridge into DNP messages, and pass them on to the RTU. The remote bridges require the DNP address of the RTU to which they are serially connected.Serial Master/Serial Remote IPv6 Sample DeploymentIn Serial Master/Serial Remote deployments, no Ethernet/IP network appears at the master bridge location. The master connects to the SCADA network using DNP3 over serial. In this case, the master requires the DNP address from both the SCADA system and from the voltage regulators. The master bridge performs DNP encapsulation and de-encapsulation from its serial interface to IP over the RF network. The master requires the DNP3 address of the voltage regulators because it routes to the remote bridges using IPv6 addresses across the RF network.Figure 8.  Example of a Mixed IPv4 DeploymentFigure 9.  Example of a Serial Master/Serial Remote IPv6 Deployment Mode
Bridges Hardware Guide Silver Spring Networks 162 Deploying Silver Spring Networks BridgesThe Bridge Configurator program provides the settings to associate the DNP3-based RTU address with each Remote bridge.IPv6 Addressing in the RF NetworkWhen a device registers with a subnet, the master bridge assigns it an IPv6 prefix, which the device appends to its MAC address to create a globally unique IPv6 unicast address, formatted according to the IEEE EUI-64 standard.All Silver Spring IPv6 network addresses contain the prefix 2001:1868:209::/48 (defined at the manufacturing facility, this value cannot be changed) with a 16-bit reserved subnet value (0xfffd) and the MAC address of the device.For example: 2001:1868:209:fffd::/64+MAC AddressWhen the master sends a message to one of the RTUs, it contains the IPv6 prefix plus the MAC address of the eBridge master.For example, given an original Ethernet MAC address for an eBridge master: 00-0C-F1-56-98-ADEach Silver Spring Networks bridge provides a sticker on the rear of the case showing the 64-bit MAC address of the device. This value is the EUI-64 value, containing the inserted 0xfffd value to extend the original 48-bit MAC to a 64-bit MAC address. 00:0C:F1:FF:FE:56:98:ADWhen operating in the RF network in IPv6, the bridge recalculates the MAC to the bridge’s IPv6 unicast address by complementing the high-order byte of the EUI-64 MAC address and appending it to the prefix.2001:1868:209:fffd:020C:F1FF:FE56:98ADWhen the remote bridge sends a message back to the master eBridge, the message must contain that same prefix and IPv6 unicast address in its packet header. This value also appears in diagnostics and logs, in the Bridge Configurator software, as a true IPv6 unicast address.Note: Each sBridge and eBridge provides the device’s unique IEEE EUI-64 MAC address in a sticker on the back of the bridge chassis. In this case, the high-order byte is not complemented, remaining as 0x00, as it is the 64-bit MAC hardware address of the device.Ethernet Teaming Sample DeploymentIn Ethernet teaming, a group of bridges send each other messages to accomplish specific tasks with reclosers. In a traditional DA communications network, all devices communicate with one or more SCADA masters. Individual DA devices, such as capacitor banks or reclosers, do not communicate with each other. However, new types of reclosers can communicate with their neighbor reclosers to effect a coordinated switching action in the event of an electrical fault. This helps rapidly isolate the electrical fault and reduce the duration of the electrical outage. For reclosers to communicate with each other, Teaming mode is required. Teaming mode forces each member of a team to
Bridges Hardware Guide Silver Spring Networks 172 Deploying Silver Spring Networks Bridgesdetermine the routing paths to all other members of the team. Figure 10 shows the path of various messages between the teaming members.All team members exist on the same subnet. An eBridge or Access Point acts as the master for the teaming network.Note: For more information on configurations and bridge deployment modes, see the Bridge Configurator 2.0 User’s Guide.Figure 10.  Example of an Ethernet Teaming Deployment Mode1. The recloser IPx2 sends an“Open” message to the 192.168.0.4Ethernet EthernetEthernet192.168.0.5 192.168.0.6192.168.0.7192.168.0.8 192.168.0.93. This bridge receives the “Open” message from IPx1and sends it, through Ethernet,2. Bridge IPx1 sendsthe packet to eBridge IPy1 over RF.Substationrecloser at IPy2 through the predetermined path. to the recloser at IPy2.
Bridges Hardware Guide Silver Spring Networks 18A SpecificationsASpecificationsSpecifications are provided in the following topics:•Overview•eBridge and sBridge Features•Silver Spring Networks eBridge Specifications on page 19•Silver Spring Networks sBridge Specifications on page 22•Regulatory Compliance - Module Certifications on page 24OverviewThe eBridge and sBridge are Commercial and Industrial SCADA products that are attached to the Silver Spring Networks Smart Energy Networks. Their primary function is remote control of local devices such as capacitor banks, instrument transformers and reclosers to utilize the Smart Grid network. The eBridge can also be used as a network bridge into the Smart Grid network. The Silver Spring Networks’ RF network uses multi-protocol, multi-priority mesh routing for the smart grid distinguished by the following features:•Low-latency, high-priority, DA/SCADA applications supported at 10-15 hop/second•High-capacity, normal-priority AMR applications transport 5-15 packets per second at the eBridge or sBridgeeBridge and sBridge Features•Built on a scalable platform that is easily integrated it into the existing network•Supports industry standard protocols; DNP3.0 and TCP/IP•Integrates with capacitor bank controllers, circuit reclosers, and other devices through built-in serial and Ethernet interfaces, supporting IPv6 and 256-bit encryption•Integrates with all Silver Spring Networks solutions and products•Small size and easy replacement•Two-way frequency-hopping spread spectrum (FHSS) communications•One-watt transmitter•Dynamic IP-based network routing•Time synchronization and management•Continuous self-healing neighbor monitoring and route calculation
Bridges Hardware Guide Silver Spring Networks 19A SpecificationsSilver Spring Networks eBridge SpecificationsThis section contains the following tables to provide eBridge specifications:•eBridge Communications Specifications •eBridge Approvals•eBridge Environmental Specifications •eBridge Protocols/Security•eBridge Interfaces •eBridge DB-9 Interface Definition•eBridge Isolated Input/Output •eBridge RJ-45 Hub Interface Definition•eBridge Power ConsumptionTable 4. eBridge Communications Specifications Data Rate 100 kbpsFrequency11.Frequency range adjusted to meet country-specific requirements.902-928 MHzSpread Spectrum Technology FHSS (Frequency Hopping)Transmitter Output 30 dBmChannels22.Channels are adjusted to meet country-specific requirements. Australia limited to 43 channelson frequency range 915-928 MHz.83Output Impedance 50 ohmsReceiver Sensitivity -102 dBm for 10-3 PERModulation Binary FSKUtilOS 1.6 or laterAntenna Connector SMA, FemaleAntenna See Table 2 on page 9: sBridge max 3dBi gain, eBridge max 6dBi gainSerial RS-232, DB9, FemaleSerial Data Rates 2400 bps to 115K bpsUSB Mini-USB v2.0 ClientEthernet RJ45LED Network (Transmit, Idle, Receive, Error)Table 5. eBridge Environmental Specifications Operating Temperature  -40°C to +85°C (-40°F to +158°F) Humidity  0% to 95%, non-condensingSize  15 cm (6") L x 14 cm (5.5") W x 4.2 cm (1.75") H"Weight  425 g (15 oz.)Enclosure  IP50, blue, aluminumPower  DC 10-60 120 to 277 VAC. 50 to 60 HzPOE  802.3af (class 2)
Bridges Hardware Guide Silver Spring Networks 20A SpecificationsTable 6. eBridge InterfacesRS-232 DB-9 Serial, DCE device, RS-232 levelsEthernet RJ-45, 10-100BaseT Hub, 36-57 VDC PoE inputMini-USB USB Serial deviceDC Voltage Input 10-30VDC DC InputTable 7. eBridge Isolated Input/OutputPin# Signal Direction Description Current1 Input Input Isolated Output 1 mA (min) 2 mA (max)2 Output Output Isolated Input 1 mA (min) 2.3 mA (max)3 GND –Signal Ground (Common) – An isolated input and an isolated output are located at P2.Table 8. eBridge Power ConsumptionNominal - Idle  0.88 WNominal - TX  5 WMax 7 WTable 9. eBridge ApprovalsFCC Part 15.247Industry Canada  RSS-210Table 10. eBridge Protocols/SecurityAddressing  Internet Protocol Version 6 (IPv6)Security  Secure Hash Algorithm 256 bit (SHA-256)RSA-1024 and / or ECC-256Encryption  256 bit Advanced Encryption Standard (AES-256)Serial Encapsulation over IPv6 (tunneling) for asynchronous serial (DNP3)
Bridges Hardware Guide Silver Spring Networks 21A SpecificationsAll RS-232 receptacles are standard DB-9 receptacle DCE pinout.Table 11. eBridge DB-9 Interface DefinitionPin# Signal Direction Description1 DCD Output Data Carrier Detect2 TXD Output Transmit Data3 RXD Input Receive Data4 DTR Input Data Terminal Ready5 GND -- Signal Ground6 DSR Output Data Set Ready7 RTS Input Request To Send8 CTS Output Clear To Send9 RI Output Ring IndicatorTable 12. eBridge RJ-45 Hub Interface DefinitionPin # Signal Direction Description1 RX+ (+V1)  Input Receive Data + (+ Voltage Supply type 1) 2 RX- (+V1)  Input Receive Data - (+ Voltage Supply type 1)3 TX+ (-V1)  Output Transmit Data + (- Voltage Supply type 1)4 No Connect (+V2)  –(+ Voltage Supply type 2)5 No Connect (+V2)  –(+ Voltage Supply type 2)6 TX- (-V1)  Output Transmit Data - (- Voltage Supply type 1)7 No Connect (-V2)  –(+ Voltage Supply type 2)8 No Connect (-V2)  –(+ Voltage Supply type 2)
Bridges Hardware Guide Silver Spring Networks 22A SpecificationsSilver Spring Networks sBridge SpecificationsThis section contains the following tables to provide sBridge specifications:•sBridge NAN Transceiver •sBridge Environmental•sBridge NAN Network •sBridge DB-9 Interface Definition•sBridge Processing •sBridge DC Power Input•sBridge Physical •sBridge Physical•sBridge InterfacesTable 13. sBridge NAN TransceiverFrequency11.Frequency range adjusted to meet country-specific requirements.902-928 MHzSpread Spectrum Technology FHSS (Frequency Hopping)Transmitter Output 30 dBmChannels22.Channels are adjusted to meet country-specific requirements. Australia limited to 43 channelson frequency range 915-928 MHz.83Receiver Sensitivity -98 dBm for 10-3 PER Power, transmit 5.2 W nominalTable 14. sBridge NAN NetworkAddressing 8 byte MAC AddressProtocol UDP/IPv6Image Security Secure bootloaderPayload Confidentiality AES-256 EncryptionAuthentication ECDH and RSA SignaturesTable 15. sBridge ProcessingProcessor ARM7Clock Speed 19.2 MHzRAM 4 MBFlash 4 MB/8 MBTable 16. sBridge PhysicalSize 4.50” (w) x 2.48” (l) x 0.7’ (d)WeightPower, idle 0.88 W nominalPower, Max 7.0 W max
Bridges Hardware Guide Silver Spring Networks 23A SpecificationsAll RS-232 receptacles are standard DB-9 receptacle DCE pinout.Table 17. sBridge InterfacesRS-232 DB-9 Serial, DCE device, RS-232 levelsDC Voltage Input 10-30VDC DC InputTable 18. sBridge EnvironmentalTemperature, operating -40°C to +85°Humidity 95%, non-condensingTable 19. sBridge DB-9 Interface DefinitionPin# Signal Direction Description1 DCD Output Data Carrier Detect2 TXD Output Transmit Data3 RXD Input Receive Data4 DTR Input Data Terminal Ready5 GND -- Signal Ground6 DSR Output Data Set Ready7 RTS Input Request To Send8 CTS Output Clear To Send9 RI Output Ring IndicatorTable 20. sBridge DC Power Input Pin # Signal Direction Input definition1 GND -- Signal Ground2 +Voltage Input Voltage supply
Bridges Hardware Guide Silver Spring Networks 24A SpecificationsRegulatory Compliance - Module CertificationsThis section contains the following regulatory compliance information:•FCC Certification (Radiated/Conducted Emissions Compliance FCC Part 15.247)•Industry Canada Certification (Radiated/Conducted Emissions Compliance RSS-210)•C-Tick Level 3 (Radiated/Conducted Emissions Compliance AS/NZS4268, AS/NZS4778)•Silver Spring Networks NIC, FCC IDs: OWS-NIC515 IC: 5975A-NIC515 (sBridge) OWS-NIC506, IC:5875A-NIC506 (eBridge)FCC Certification (Radiated/Conducted Emissions Compliance FCC Part 15.247)The sBridge is compliant to FCC regulations for radiated and conducted emissions. The sBridge uses a 1W, 900 MHz, FHSS radio.15.247(a)(1) The system shall hop to channel frequencies that are selected at the system hopping rate from a pseudo randomly ordered list of hopping frequencies. Each frequency must be used equally on the average by each transmitter. The system receivers shall have input bandwidths that match the hopping channel bandwidths of their corresponding transmitters and shall shift frequencies in synchronization with the transmitted signals.15.247(g) Frequency hopping spread spectrum systems are not required to employ all available hopping channels during each transmission. However, the system, consisting of both the transmitter and the receiver, must be designed to comply with all of the regulations in this section should the transmitter be presented with a continuous data (or information) stream. In addition, a system employing short transmission bursts must comply with the definition of a frequency hopping system and must distribute its transmissions over the minimum number of hopping channels specified in this section.15.247(h) The incorporation of intelligence within a frequency hopping spread spectrum system that permits the system to recognize other users within the spectrum band so that it individually and independently chooses and adapts its hopsets to avoid hopping on occupied channels is permitted. The coordination of frequency hopping systems in any other manner for the express purpose of avoiding the simultaneous occupancy of individual hopping frequencies by multiple transmitters is not permitted.Industry Canada Certification (Radiated/Conducted Emissions Compliance RSS-210)The sBridge is compliant to ICC regulations for radiated and conducted emissions. The sBridge uses a 1W, 900 MHz, FHSS radio.
Bridges Hardware Guide Silver Spring Networks 25A SpecificationsThis device has been designed to operate with the antennas listed below, and having a maximum gain of 3 dBi (sBridge) and 6 dBi (eBridge). Antennas not included in this list or having a gain greater than 3 dBi (sBridge) or 6 dB (eBridge), are strictly prohibited for use with this device. The required antenna impedance is 50 ohms. C-Tick Level 3 (Radiated/Conducted Emissions Compliance AS/NZS4268, AS/NZS4778)The NIC is compliant to C-tick testing for radiated and conducted emissions in compliance with Australian Communications Authority (ACA) adopted standards from CISPR, CENELC, and IEC. The sBridge uses a 1W EIRP, 900 MHz, FHSS radio.The C-Tick EIRP mark is filed under number N1571 for Silver Spring Networks. Silver Spring Networks NIC, FCC IDs: OWS-NIC515 IC: 5975A-NIC515 (sBridge)OWS-NIC506, IC:5875A-NIC506 (eBridge)The NIC515 must be professionally installed by a properly trained technician. Improper installation could void the user's authority to operate the equipment.The device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:1. The device may not cause harmful interference.2. The device must accept any interference received, including interference that may cause undesired operation.AntennaThe antenna of this transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.The device should be installed so that people will not come within 20 cm (8 in.) of the antenna.This equipment has been tested and found to comply with Part 15 of the FCC Rules. This equipment generates, uses and can radiate radio frequency energy, and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:Table 21. Available antennas for Silver Spring Network bridgesSSN Antenna Part # Description315-00012 Rev. 5 JPole antenna315-000002 Rev. A sBridge: Rubber Duck, 3dBI maximum gain, SMA Female, AntennaeBridge: Rubber Duck, 6dBI maximum gain, SMA Female, Antenna
Bridges Hardware Guide Silver Spring Networks 26A Specifications•Reorient or relocate the receiving antenna.•Increase the separation between the equipment and receiver.•Connect the equipment into an outlet on a circuit different from that to which the receiver disconnected.•Consult the dealer or an experienced Radio/TV technician for help.CAUTION: Changes or modifications not expressly approved by Silver Spring Networks could void the user's authority to operate the equipment.
Bridges Hardware Guide Silver Spring Networks 27 Glossary GlossaryAAccess Point (AP)   An Access Point is a router that performs the function of communicating over both a Wide Area Network (WAN) and the Neighborhood Area Network (NAN). See also primary Access Point.alternate Access Point   See secondary Access Point.AMR (Automated Meter Reading)    A form of ad-vanced metering that uses communications devic-es to send data from the meter to the utility. This includes simple energy consumption data to outage detection and over-the-air meter programming.ANSI   American National Standards Institute. A stan-dards organization that administers the standard-ization and conformity assessment system used in the U.S. and around the world. When ANSI adopts a standard, it disseminates a code to identify the standard. For example, ANSI Standard C12.19.asynchronous   In networking communications, an asynchronous signal occurs without a correspond-ing request for that signal. A last gasp from a meter is an example of an asynchronous signal.attenuation   The decrease in amplitude of a signal during its transmission from one point to another.Bbackbone device   Normally a poletop device such as an Access Point or a Relay. In some cases, a meter that acts as a relay can be designated as a back-bone device. In some cases, a Relay may not be a backbone device. All backbone devices are includ-ed in the backbone ping schedule.backhaul   To transmit data to a point from which it can be sent over a network (hauled back) to the data center.bandwidth   The amount of data transmitted in a given amount of time, usually measured in bits per sec-ond, kilobits per second, or megabits per second.CC&I (Commercial & Industrial)   The reference to commercial and industrial energy and water cus-tomers.capacitor bank   Used to improve electric power sys-tem efficiency and to aid in transmission voltage stability during disturbances.Two varieties exist: distribution capacitor banks and substation capaci-tor banks. An example of an RTU device.CDMA   Code-Division Multiple Access. A digital wire-less technology that uses spread spectrum technol-ogy to send its signals over a wider bandwidth than the original signal.child   A meter that is associated with a Relay is a child of that Relay. Similarly, a Relay is a child of the Ac-cess Point to which it is associated. A meter can also be a child of another meter. In this case, the parent meter is acting as a Relay. churn   Refers to endpoint devices recalculating the egress route to their preferred Access Point on a frequent basis. This is a sign of network instability because an endpoint’s IP address may become stale, resulting in missed reads.crumb   A single node in a series of hops comprising a source-routed path. As a source-routed path is de-fined by the Master bridge or an Access Point, each hop in the dedicated downstream path is termed a ‘crumb’ as in a trail of ‘bread crumbs.’ Customer Premise Equipment (CPE)   Customer Premise Equipment is all telecommunications ter-minal equipment located on the customer premis-es, such as a cable modem, router, or access point.DDA-NEM   Distribution Automation-Network Element Manager. A software application that allows users to manage the devices comprising a DA network. See also distribution automation (DA).DA Network   A network of Silver Spring Bridges, Re-lays, and an Access Point, designed and deployed to establish communications to help manage elec-
Bridges Hardware Guide Silver Spring Networks 28 Glossary trical distribution devices such as reclosers, switch-es, transformers and capacitor banks.dB   Decibels. A logarithmic unit of measurement that expresses the magnitude of radio power.dBm   The power ratio in decibels (dB) of radio power relative to one milliwatt (mW).dead area   Locations from which effective transmis-sion cannot be established because the transmitted signal is blocked by clutter. Also known as shadow.decimal degrees   A numerical way of expressing de-grees, minutes, and seconds longitude from Green-wich, England and latitude from the equator: decimal degrees = degrees + (minutes / 60) + (seconds / 3600)Positive numbers indicate East longitude or North latitude. Negative numbers indicate West longitude or South latitude. For example, W 122° 28’, 39.3” longitude by N 37° 49’, 11.2 latitude expressed in decimal degrees is:-122.477583 longitude by 37.819778 latitudedemand   The highest requirement for power, that is, the amount of power required to satisfy the de-mand. There is no time element involved. The high-est requirement for power can occur in an instant. In practice, most demand meters measure the aver-age peak demand over the 15 or 30 minute period. This definition of demand differs from energy in that energy is the usage of power over time whereas there is no time element in measuring demand. De-mand is measured in kilowatts (kW) and energy is measured in kilowatt-hours (kWh). For example, a demand for 100 kW continuous for an hour equals 100 kWh. If the demand rose to 400 kW continuous for the next hour, the demand for that hour equals 400 kWh. For the two hour period, the demand is 400 kW because that is the highest requirement for power. The energy used is 500 kWh because that is the actual usage of power over time. See also energy and time of use.device   Access Point, Relay, or meter. Meters can be electric, gas, or water. See also IMU.dissimilar neighbor   A neighbor device that, be-cause of its dissimilarity, maximizes the odds of re-ceiving a last gasp from another device.distance vector   One of the two major classes of routing protocols, distance vector routing requires that a router periodically inform its immediate neigh-bors of any changes in its topology. A distance vec-tor means that routes are advertised as a vector comprising several characteristics, including next hop address, egress interface, and metrics such as hop count. routers using such a protocol do not have knowledge of the entire path to a destination unless that destination is directly connected to them. Routing in the Silver Spring system uses a distance vector protocol on Layer 2.distributed generation   A distributed generation sys-tem involves small amounts of generation or pieces of generation equipment applied to a utility’s distri-bution system for the purpose of meeting local peak loads and/or displacing the need to build additional infrastructure. Distributed generation may be in the form of gas or propane generators, fuel cells, or so-lar.distribution automation (DA)   The computerized or intelligent control of the electrical power grid down to the distribution level. In recent years, DA has be-come nearly synonymous with SCADA.distribution power    A packaged power unit located at the point of demand. While the technology is still evolving, examples include fuel cells and photovol-taic cells.DNS   Domain Name System. An Internet service that translates alphanumeric domain names into numer-ic IP addresses. For example, the alphanumeric do-main www.silverspringnet.com translated to its IP address through DNS is 64.207.187.4.downstream / upstream   Refers to the relationship between devices along the route. Downstream re-fers to moving toward a meter. Upstream means moving toward an Access Point. See also child and parent.EeBridge   A Silver Spring device that routes between an RF interface, an ethernet port and a serial port.
Bridges Hardware Guide Silver Spring Networks 29 Glossary endpoint   Meters, distribution controls, cap bank switches, and other specialized network devices. Many endpoints are assigned to nodes. See also node.energized   See set. energy   \The use of power over time, expressed in kilowatt-hours (kWh). See also demand and time of use.ESN   Electronic Serial Number. A unique identifier embedded on every cellular phone device by the manufacturer. The ESN is transmitted with each cell phone call and is used to authenticate the phone with the cellular service the phone is attempting to use. exception polling   A proactive outage detection tech-nique where pings are sent to devices to see if they are still alive. Devices that do not respond may sig-nify an outage.export   Meter read data, for a specific date and time, contained in a XML and HHF (Hand Held Format) files for integration with business systems. FFCI   Faulted Circuit Indicator. A device that, if tripped, indicates a failed utility condition such as a power failure.FHSS   Frequency-Hopping Spread Spectrum. Origi-nally developed during the Second World War to avoid jamming, FHSS is a method of sending radio signals over several frequency channels. Unlike DSSS, FHSS switches between channels in a pat-tern known to both sender and receiver, thereby avoiding interference in any one channel.filter   Band-pass filter, used to minimize out-of-band interference issues.firmware   A computer program embedded in a hard-ware device. See also image.fresnel zone   Refers to the elliptically shaped area formed by RF waves between a transmitter and a receiver. FSU   Field Service Unit. A portable NIC from Silver Spring used to install, test, and send commands to other SSN devices, including eBridges and sBridg-es.ftp   File Transfer Protocol. A protocol for transferring files over any network that supports TCP/IP.Ggap   Refers to a gap in the usage data collected from a meter. AMM automatically detects and fills such gaps. See also end gap and unfillable gap.gas day   A specific time of day when a gas meter be-gins its 24-hour day. For many utilities, the gas day is 9:00 AM, but this is not always the case.generation capacity     The maximum output (MW) that generating equipment can supply to system load.grid operator    The entity that oversees the delivery of electricity over the grid to the customer, while as-suring consistently high levels of reliability, and pub-lic and worker safety. The grid operator potentially could be independent of the utilities and suppliers.GWh Gigawatt-hours     One billion watt-hours.Hhash value   A block of data represented as a string of bits. See also program seal.Hata model   A path loss estimation model based on empirical research of various mophologies such as Urban Core, Dense Urban, and Suburban.HHF Files   Hand Held Format file. Contains meter in-terval read data. See also export. Home Area Network (HAN)   A data communications system contained within the home. hop   When data is transmitted across a network, the packet hops from device to device. A hop is a point along a network route between the Access Point and the meter. Though technically not a device, a hop is always associated with a device, usually a Relay or meter acting a a Relay. See also link and route.hosting location   The physical location of an Access Point or Relay.IIDR   Interval Data Recorder. A solid-state electronic device that measures consumption among high-us-
Bridges Hardware Guide Silver Spring Networks 30 Glossary age commercial and industrial accounts. The data collected is used by a utility to determine peak de-mand times and adjust its distribution system ac-cordingly.IEEE   Institute of Electrical and Electronics Engineers, a prominent standards body for the electrical, tele-communications, aerospace, and engineering in-dustries. IETF   Internet Engineering Task Force, a prominent standards body for the development and evolution of the Internet networking architecture and the sta-ble operation of the Internet. image   Firmware or software programming code that can be copied to multiple programmable chips in one or more devices, such as NICs or electricity meters. See also firmware and code float.IMU   Interface Management Unit. A two-way radio in-tegrated with gas and water meters that provides consumption reads and can be remotely config-ured.in-band interferers   Transmitters in the same ISM band that are not part of Silver Spring’ transmitters.info success rate   The percentage of data packets that succeed when a process sends a poll to a spe-cific node and receives an acknowledgement. Cal-culated by:(successes / (successes + failures)) * 100instrument transformer   A step-down transformer for scaling down actual power system quantities for metering, protective relaying and system monitor-ing equipment. An example of an RTU device.interferers   See in-band interferers and out-of-band interferers.IPv6   Internet Protocol Version 6. A network layer standard enables devices to communicate over a packet-switched network.ISM band   Industrial, Scientific, and Medical band. The 902-928 MHz band, an unlicensed frequency band governed by FCC, Part 15.Jjob   In AMM, a job is a running or scheduled process, including but not limited to metering schedules, im-ports, exports, and reports. In common usage, the term schedule is reserved for jobs that read meters over the network.jobs interface   The web services API used to run and manage jobs.joined   A NIC and its meter are said to be joined when they have been assembled, configured, tested, and communicating together as designed. See also un-joined.KkVA   Kilo Volt Ampere.kVAh   Kilo Volt Ampere Hours. kVAR   Kilo Volt Ampere Reactive. A measure of reac-tive energy usage. See also V, and Vrms.kVAR lag   The inductive reactance, or how much the voltage lags the current, of the circuit.kVAR lead   The capacitive reactance, or how much the voltage leads the current, of the circuit.kVARh   Kilo Volt Ampere Reactive Hours. A unit of en-ergy equivalent to one kVAR of power expended for one hour. See also V.kW   Kilowatt. A unit of power equal to 1000 watts.kWh   Kilowatt-hour. A unit of energy equivalent to one kilowatt (1 kW) of power expended for one hour.Llag   See kVAR lag.LAN   Local Area Network. Computers and other de-vices that share a common wireless link within a geographic area. See also NAN (Neighborhood Area Network) and Wide Area Network.last gasp   An asynchronous message from an elec-tricity meter that indicates the meter has lost power. Also known as a power out message. Last gasps can result when the loss-of-power pin becomes ac-tive, when a number of zero crossing events are missed, or when a transition from utility power to battery power occurs. There is no guarantee that a last gasp will be received by any other device in the network. See also Verified Single No Current.link   A connection between devices in a network. See also hop and route.
Bridges Hardware Guide Silver Spring Networks 31 Glossary link quality   The overall RF quality of a link between a transmitter and receiver. Often expressed in terms of message success rate and signal strength. See MSR and RSSI.link budget   The total amount of RF power available to establish a link between the transmitter and re-ceiver, expressed mathematically:PLinkBudget = PTx - PTxLoss + PTxAntenna + PRxAntenna -PRxLoss -PRxSensitivityLOS   Line of Sight. A direct path, free of clutter, be-tween a transmitter and a receiver.MMAC   Media Access Controller. A unique hardware identifier for network equipment. MLME   Media access control (MAC) Sublayer Man-agement Entity. An internal process handler for es-tablishing L2 network adjacencies and routing in the Silver Spring RF wireless mesh network.MSR   Message Success Rate. The percentage of packets that are transmitted (by the Access Point) and also acknowledged (by the meter). The MSR is derived from successful packet transmission during scheduled reads, On Demand reads, and segment retries. MSR is a metric for packet transmission and how well the Access Point can communicate with a meter. See also BSR and RSR.Nneighbor table   A memory structure within each NIC to store data about its neighboring NIC-enabled de-vices.net metering   Net metering applies to energy custom-ers, such as commercial and industrial users, who both generate and purchase power. Utilities need to meter the power generated by customers to deter-mine the credit the customer should receive. A net register calculates energy to be billed by subtract-ing power received from the customer from the power delivered to the customer. network discovery   When a new meter is first in-stalled, it broadcasts a discovery message. The dis-covery message is received by all NIC-enabled devices in range, which in turn, forward the mes-sage upstream through an Access Point to AMM. node   A network device. Examples include electricity meters, Relays, and IMUs.NIC   Network Interface Card. Attached to electricity meters and integrated with Water and Gas IMUs, the NIC card provides two way radio communica-tions across the network.OODS   Outage Detection System. An application from Silver Spring that manages outage-related messag-es from electricity meters, including last gasp and power restore messages. Unlike an OMS, and ODS does not include a work order management system.OMS (OM)   Outage Management System. A central-ized system that manages the identification of all outage events and the restoration of service in a utility grid. An OMS system usually is tightly inte-grated with a work order management system.one-time schedule   A schedule with a frequency of one-time. See also schedule.OSI   Open Systems Interconnection. A standard refer-ence model for how messages are transferred be-tween any two points in a network. The OSI reference model defines seven layers of function that take place at each end of a communication. It serves as a standard by which diverse applications can communicate with one another.over-the-air   Wireless communications between de-vices. Sometimes used to refer to the programming of devices through wireless communications.Ppackets   Packets consist of a header, which contains data such as destination address, and a payload, which contains application data such as interval read results. See payload and ping.packets in flight   The number of simultaneous pack-ets being transferred between a sender and a re-ceiver. A packet in flight is one that the sender has sent but the receiver has not yet acknowledged as received.parent   A network device to which other devices are registered.
Bridges Hardware Guide Silver Spring Networks 32 Glossary path   Refers to how cells, nodes, and endpoints are connected together. For example, the path from cell A to endpoint Z runs through node B. See also route.path loss   Total amount of power lost in the propaga-tion of the RF signal from the transmitter to the re-ceiver.payload   The payload is that part of a packet that is not the header. Payloads consist of application data such as interval read results. In the case of an On Demand ping, the user can set the payload size to increase or decrease the size of the packet. In RF networks, small packets can traverse the network more successfully than larger packets. When per-forming an On Demand ping, you can configure the payload up to 255 bytes. See also packet and ping.peak demand    The maximum level of use by custom-ers of a system during a specified period. peaking capacity    Capacity of generating equipment normally reserved for operation during the hours of highest daily, weekly, or seasonal loads.peaking plant     A power plant that normally operates only during peak load periods.percentile   Similar to the meaning of median, the per-centile is a value within a range of values at which the percentage of the values lie at or below the ex-pressed percentile. For example, 25% of the values lie at or below the 25th percentile, which implies that 75% of the values lie at or above the 25th percen-tile. Similarly, 75% of the values lie at or below the 75th percentile. The median can also be expressed as the 50th percentile.ping   Packet InterNet Groper or Packet InterNet Go-pher. A program to test the reachability of devices on a network. The ping program sends a packet to the named device and returns data indicating how long, in milliseconds, the packet took to reach the device and return (also known as round trip time). See also On Demand, packet, reachable, and trac-eroute.port   In networking, a port is used in conjunction with a computer address and specifies a process run-ning on the destination computer. potential transformer   A step-down transformer used to scale down very high voltages to levels that are safer for instrument operation. For example, 600:1 scale factors are not uncommon with poten-tial transformers. A common device in substations.power out message   See last gasp.preferred Access Point   See primary Access Point.primary Access Point   The best performing, most re-liable Access Point as determined by the endpoint device. See also secondary Access Point.protocol   An agreed upon format for transmitting data between two devices. Protocols have rules that govern the syntax, semantics, and synchronization of communication. Protocols may be implemented by hardware, software, or a combination of both.Qqueue   A list. In AMM, a list of meters associated with a schedule is referred to as a queue. In general computing, a queue can be a list of commands to execute one by one. See also requeue.Rrate structure    The various rates charged by a utility for its services.RDBMS   Relational Database Management System, such as Oracle.reactor   High-voltage inductors used as a shunt to regulate transmission voltage and to reduce fault current in transmission lines. An example of an RTU device.read (meter read)   The collection of usage data from a meter. Collections of meter reads are referred to as read data.reachable   The ability to send and receive data to and from a meter. A reachable meter is usually read-able. However, a meter may be reachable with small packet sizes, but may not be readable with the larger packet sizes necessary for a successful read.recloser   Similar to a circuit breaker, a recloser is equipped with a mechanism to automatically close the breaker after it has opened due to a temporary electrical fault. An example of an RTU device.relay   A device on a network used to extend the reach of a network. Relays are typically placed high for
Bridges Hardware Guide Silver Spring Networks 33 Glossary best line-of-sight to meters. Normally, several me-ters are associated with each Relay and several Relays are associated with an Access Point. Meters can also act as a Relay. See also reachability.remote CHAP password   See CHAP.remote provisioning   See remote service manage-ment.remote telemetry units (RTUs)   A broad category of electrical distribution devices including different types of transformers, capacitor banks, reclosers/circuit breakers, and many other device types. route   The route from an Access Point to a Relay or a bridge, or to one or more meters. Routes can be network discovered, static, or temporary. In the con-text of DA, a network discovered route is deter-mined automatically by the takeout point (an eBridge or Access Point) when a new remote bridge is set and it broadcasts a discovery message across the network. A static route is a user-defined route saved and used for all subsequent communi-cations. A user-defined static route overrides all network discovered routes. When performing an On Demand ping, a user can specify a one-time route to a destination that is not saved or re-used.RF   Radio Frequency.RSSI   Received Signal Strength Indicator. A way to measure the strength of a received radio signal.run   A schedule run consists of the initial attempt and all retries of all meters associated with the sched-ule, plus the initial attempt and all retries of re-queued meters.SsBridge   A Silver Spring device that routes between an RF interface, and two serial ports.SCADA (Supervisory Control and Data Acquisition)   A computer system that super-vises and controls the electric utility distribution and transmission system. In recent years, SCADA has become nearly synonymous with distribution auto-mation.secondary Access Point   The next best performing, most reliable Access Point as determined by the endpoint device. See also primary Access Point. set   A device is set once it is physically installed and connected to electricity. Sometimes, this is referred to as energized.Smart Grid   Refers to technologies that enable a highly communicative, predictive, and self-healing utility grid.SOAP   Simple Object Access Protocol. A protocol for exchanging XML-based messages over a computer network. SOAP provides a basic messaging frame-work for web services.source select   Corresponds to a measurement chan-nel configured on an electricity meter. Each channel measures a particular source, such as energy deliv-ered in dWh. source route   A TCP routing construct, normally termed a ‘Loose Source route,’ in which a distant node establishes the best possible path, hop by hop, through a complex network to its destination..sparse deployment   A range-limited deployment where relatively few endpoints operate at minimum signal strength. See also dense deployment and spot deployment.spot deployment   Deployments to read a small num-ber of relatively contained endpoints, such as in an office park. See also dense deployment and sparse deployment.spectral inspection   A spectrum analyzer can be used to determine potential sources for out-of-band interference.standard tables   Tables in electricity meters that con-form to ANSI Standard C12.19.standby facility    A facility that supports a utility sys-tem and is generally running under no-load. It is available to replace or supplement a facility normal-ly in service.standby service    Support service that is available as needed to supplement a consumer, a utility system, or to another utility if a schedule or an agreement authorizes the transaction. The service is not regu-larly used.states   The states that apply to devices in a Silver Spring Network are of three types: CIS device states, network states, and operational states.
Bridges Hardware Guide Silver Spring Networks 34 Glossary static route   A user-defined route between Access Points, Relays, and meters. When you define a stat-ic route, it overrides all network discovered routes. See also network discovery.substation   A facility in an electricity distribution sys-tem used for switching and / or changing or regulat-ing the voltage of electricity. A substation is the location where high voltage transmission lines con-nect to switchgear and step-down transformers to produce lower voltages at lower power levels for lo-cal distribution networks.switching station    Facility equipment used to tie to-gether two or more electric circuits through switch-es. The switches are selectively arranged to permit a circuit to be disconnected, or to change the elec-tric connection between the circuits.TTCP/IP   Transmission Control Protocol / Internet Pro-tocol. A suite of communications protocols used to connect hosts on the Internet. TCP/IP is the defacto standard for transmitting data over networks.topology   The physical layout of a distribution net-work infrastructure with specific hierarchical identi-fication of all components.traceroute   A networking utility to track the routes tak-en by packets across a network. See also ping.trap   An asynchronous event, often in a managed subsystem.tunnel   In networking, a tunnel allows the encapsula-tion of the data of one protocol within another proto-col. By using a tunnel, you can pass the encapsulated data over an incompatible network or provide security for transferring data over an un-trusted network.UUTM   Universal Transverse Mercator. The UTM sys-tem divides the globe into 60 North-South zones, each measuring six degrees wide in longitude. Zones are numbered consecutively from West to East. Positions on the globe are given by zone co-ordinates, then the number of meters East (easting) or West (westing) from the center of the zone, and finally by the number of meters North (northing) or South (southing) from the center of the zone. UTM coordinates for the Golden Gate Bridge are zone 10 S, 545980m E. 4185742m N. VV   Volts or voltage. See also kVA, kVAh, kVAR, and kVARh.VEE   Validation, Estimation, and Editing. Software tools that manage data collected from endpoints.Verified Single Outage (VSO)   A last gasp followed by a measurable duration.Voltage regulator   An electrical device for regulating the voltage through a circuit, to provide customers with steady and consistent voltage flow. Normal practice is to try to regulate voltage flow within nom-inal 124Vac to 116Vac. An example of an RTU de-vice.WWAN   Wide Area Network. A dispersed telecommuni-cations network. In contrast to a local area network (LAN) or neighborhood area network (NAN), a WAN often includes public networks. See also Local Area Network and Neighborhood Area Network.Work Order Management System (WOMS)   In the utility industry, a software application used to dis-patch work crews to perform repairs. Such systems are often integrated with outage management sys-tems.XXML   Extensible Markup Language. An standard, structured file format for exchanging business data over networks. Silver Spring exports interval data to XML files, which can then be imported into back-end business systems.Zzero crossing   The event of standard AC line voltage crossing the zero volt, or reference level, from pos-itive to negative or negative to positive. An electric-ity meter monitors its zero crossings and interprets their absence as a loss of power.
Bridges Hardware Guide 36 Index IndexAAccess Point 11antennaregulatory information 25antennasconsiderations 8disc antenna 9, 25helical antenna 9, 25JPole antenna 9, 25part numbers 9, 25types 9, 25Bbenefits 4Bridge Configurator 14, 16Ccapacitor bank 4customer support 7DDB-9 4deploymentcentralized 12decentralized 13disc antenna 9, 25DNP3 14RTU address 15EeBridgeand 64-bit MAC address 16in DA network 8interfaces 4IPv6 addressing 16physical installation 8RF interface 5Ethernet100Base-T 4and mixed mode 14IPv4 13Ffeatures and benefits 4Hhelical antenna 9, 25IIEEE EUI-64 16interfacesEthernet 13serial 14IPv4 10IPv6 10, 15addressing 16IEEE EUI-64 address 16network prefix 16reserved subnet 16JJPole antenna 9, 25MMAC addresson bridges 16master/remotecentralized deployment 13decentralized deployment 13explained 12master/remote topology 11mixed deploymentsusing Ethernet 14using serial ports 14Nnetwork topology 11master/remote 11teaming 13PPoE 20Rrecloser 13Relaysin DA network 11RJ-45 4
Bridges Hardware Guide 37 Index RTUs 8and bridges 9DA communication with 4DNP3 address 15example 4in distribution network 9SsBridgeand serial modes 14in DA network 8physical installation 8port in raw mode 5, 14RF interface 5, 14serial port connectivity 5, 14serial port operation 5SCADA system 4, 11, 12serialIPv4 and IPv6 14serial modeDNP3-to-IP mapping 14in remote bridge 14in teaming bridge 14specifications 18communications 19environmental 19power consumption 20protocol/security 20star network 12Tteamingnumber of team members 13routing in 13topology 13Vvoltage regulator 14