MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 335. If constant interference is present in a particular frequency zone, it may be necessary to “lock out” that zone from the radio’s hopping pattern. The radio includes built-in tools to help users do this. Refer to the discussion of the SKIP command (Page 49) for more information. In the USA, a maximum of four zones may be skipped, per FCC rules. Check the regulatory requirements for your region.6. Interference can also come from out-of-band RF sources such as paging systems. Installation of a bandpass filter, such as Part No. 20-2822A02 in the antenna system may provide relief from this type of interference. 7. Proper use of the RETRY and REPEAT commands may be helpful in areas with heavy interference.The RETRY command sets the maximum number of times (1 to 10) that a radio will re-transmit upstream data over the air. Values greater than 1 successively improve the chances of a message getting through when interference is a problem. The REPEAT command sets a fixed number of unconditional retransmissions for downstream data.8. The RF power output of all radios in a system should be set for the lowest level necessary for reliable communications. This lessens the chance of causing unnecessary interference to nearby systems and keeps power consumption to a minimum.
34 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 10.0 PROGRAMMING REFERENCEAll programming and control of the transceiver is performed through a PC terminal connected to the radio or the Evaluation Board DIAG connector. There are no manual adjustments or jumper settings used for configuration. This section explains how to establish terminal communication, and provides a complete list of user commands.10.1 Programming MethodsTerminal Interface ModeA PC may be used by operating it in a basic terminal mode (e.g., a HyperTerminal session) and entering the radio commands listed in the tables contained in this section. The PC must be connected to the radio via its 16-pin header connector, or, if using the Evaluation Board, via the modular diagnostics connector. In the latter case, an RJ-11 to DB-9 Adapter Cable (Part No. 03-3246A01) is required. A cable of this type may be constructed using the information shown in Figure 10 on Page 11.Once a PC terminal is connected, communication (baud rate) is automatically established through the command interface. To access the command interface, press the ESCAPE key, followed by one or more ENTER keystrokes (delivered at about half-second intervals), until the “>” prompt is displayed.NOTE: The diagnostic interface uses 8 data bits, 1 stop bit, and no parity. It automati-cally configures itself to function at 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200 bps.If the DLINK setting is ON, the interface will start out in Diagnostic Link mode. This is a special protocol used to support Network-Wide Diagnostics. The pro-cess described in the paragraph above causes the radio to exit diagnostic link mode and enter command mode. If there is no input in command mode for 5 minutes, the interface will revert back to diagnostic link mode.PC-Based Configuration SoftwareThe Windows™-based TransNET Configuration Software (P/N 06-4059A01) is designed for use with the OEM Transceiver. This software provides access to all of the radio’s capabilities with the benefit of context-sensitive help. The program is shipped as part of the TransNET Support Package CD included with every order.10.2 User CommandsA series of tables begin on the next page listing the various user commands for the OEM transceiver. The tables provide abbreviated command descriptions. Complete descriptions follow in Section 9.3.
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 35Entering CommandsThe proper procedure for entering commands is to type the command, followed by an   keystroke. For programming commands, the command is followed by  , the appropriate information or values, and then .  Table 11. Network Configuration—Master Station  COMMAND  DESCRIPTION BAND [abc]Details, page 41 Selects which of three frequency ranges the transceiver will operate in.BUFF [ON, OFF]Details, page 42 ON = Seamless dataOFF = Fast byte throughput.FEC [ON, OFF]Details, page 44 Sets/disables FEC (Forward Error Correction) setting.HOPTIME [7, 28]Details, page 44 Displays hop-time or sets it to 7 or 28 ms.REPEAT [0–10]Details, page 47 Sets/displays the fixed downstream re-send count.RETRY [0–10]Details, page 47 Sets/displays the maximum upstream re-send count for ARQ (Automatic Repeat Request) operationSAF [ON, OFF]Details, page 49 Enables/disables the store-and-forward func-tion for the network controlled by this Master unit.SKIP [NONE, 1...8]Details, page 49 Skip one or more frequency zonesTable 12. Network-Wide Diagnostics   Command DescriptionDLINK [xxxxx/ON/OFF]Details, page 43 Controls operation of diagnostic link function.DTYPE [NODE/ROOT]Details, page 44 Set radio’s operational characteristics for net-work-wide diagnosticsENTERSPACEENTER
36 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 Table 13. Operational Configuration—Set/Program  Command DescriptionADDR [1–65000]Details, page 40 Program network addressAMASK [0000 0000–FFFF FFFF]Details, page 41 Sets alarm response. Default: FFFF FFFFASENSE [HI/LO]Details, page 41 Sense of the radio’s alarm output in the EIA-232 mode. Default: Alarm present = HI. BAND [abc]Details, page 41 Selects which of three frequency ranges the transceiver will operate in.BAUD [xxxxx abc]Details, page 41 Data communication parametersCODE [NONE, 1…255]Details, page 42 Select the security/encryption setting in the radio.CTS [0–255]Details, page 43 CTS delay in milliseconds.(A value of 0 returns CTS immediately)CTSHOLD [0–60000]Details, page 43 “Hold time” that CTS is present following last character from DATA port.DEVICE [DCE, CTS  KEY]Details, page 43 Device behavior: DCE (normal) or CTS KeyLEDS [ON, OFF]Details, page 45 Enables/disables transceiver LEDsMODE [M, R, X]Details, page 45 Operating mode: where M = Master, R = RemoteOWM [xxxxx]Details, page 46 Owner’s message, or alternate message (30 characters maximum)OWN [xxxxx]Details, page 46 Owner’s name, or alternate message(30 characters maximum)PORT [RS232, RS485]Details, page 46 Data port (DATA connector) interface signal-ing mode: RS232 or RS485PWRDetails page 47 Forward power-output setting in dBmREPEAT [0–10]Details, page 47 Forward power output in dBm.RXTOT [NONE, 0–1440]Details, page 48 Maximum duration (in minutes) before time-out alarm. Default is OFF.
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 37 RTU [ON, OFF, 0-80]Details, page 48 Enable or Disable unit’s built-in RTU simula-tor. Default is OFF. Set RTU address between zero and 80.SLEEP [ON, OFF]Details, page 50 Enable or Disable the radio’s Sleep mode function.UNIT [10000–65000]Details, page 51 Unit address used for network-wide diagnos-tics. (Unique within associated network.)XADDR [0–31]Details, page 51 This unit’s Extended addressTypically, the Master is set to zero (0). XPRI [0–31]Details, page 51 Address of the primary Extended radio unit (Extension).XMAP [00000000-FFFFFFFF]Details, page 51Included Extended units in MODE X. (Exten-sions and Remotes only). XRSSI [NONE, –40...–120]Details, page 51 Minimum RSSI level required to preserve syn-chronization with a non-primary radio. (Only meaningful when XPRI is not NONE)ZONE CLEARDetails, page 51 Reset zone data statisticsTable 14. Operating Status—Display Only Command DescriptionADDRDetails page 40 Network addressAMASKDetails page 41 Alarm mask (response)ASENSEDetails page 41 Current sense of the alarm output.BANDDetails page 41 Shows which of three frequency ranges the transceiver is set to operate in (A, B, or C)BAUDDetails page 41 Data communication parameters. Example: BAUD 9600 8N1BUFFDetails page 42 Data buffering mode: ON = seamless data, OFF = fast byte throughputCODEDetails page 42 Security/encryption operational status.“NONE” (Inactive), or “ACTIVE”Table 13. Operational Configuration—Set/Program  (Continued)Command Description
38 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 CTSDetails page 43 CTS delay in milliseconds (0–255 ms)CTSHOLDDetails page 43 “Hold time” that CTS is present following last character from DATA port.DEVICEDetails page 43 Device behavior Alternatives: DCE and CTS KEYHOPTIMEDetails page 44 Hop-time value in milliseconds (ms).HREVDetails, page 45 Hardware revision levelLEDS [ON, OFF]Details, page 45 Enables/disables transceiver LEDsMODEDetails page 45 Current operating mode: M = MasterR = RemoteX = Extension (Repeater)OWMDetails page 46 Owner’s message or site nameOWNDetails page 46 Owner’s name or system namePORTDetails page 46 Current data port (DATA connector) interface signaling mode: RS232 or RS485PWRDetails page 47 Show forward power-output setting in dBmREPEATDetails page 47 The fixed downstream re-send count.RETRYDetails page 47 The maximum upstream re-send count for ARQ (Automatic Repeat Request) operation.SAFDetails page 49 The store-and-forward function status.SKIPDetails page 49 Table of frequency zones programmed to be skippedRSSIDetails page 48 Received signal strength indicator (dBm). Unavailable at Master unless SETUP is enabled.Table 14. Operating Status—Display Only (Continued)Command Description
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 39RXTOTDetails page 48 The amount of time (in seconds) to wait before issuing a time-out alarm. RTUDetails page 48 RTU simulator’s operational status (ON/OFF)SAFDetails page 49 Store-and-forward mode status in this unit. (ON/OFF)SERDetails page 49 Serial number of radioSHOW PWRDetails page 49 Show measured RF output power in dBmSHOW SYNCDetails page 49 Information on synchronization source and depthSKIPDetails page 49 Frequency zones that are skippedSLEEPDetails page 50 Radio’s Sleep Mode setting. (At Remotes Only)SREVDetails page 50 Transceiver firmware revision levelSTATDetails page 50 Current alarm statusTEMPDetails page 50 Transceiver’s internal temperature (°C)UNITDetails page 51 Programmed unit address for network-wide diagnosticsXADDRDetails page 51 This unit’s Extended addressXPRIDetails page 51Address of the primary Extended radio unit (Extension).XMAPDetails page 51Included Extended units in MODE X. (Exten-sions and Remotes only). XRSSIDetails page 51 Minimum RSSI level required to preserve syn-chronization with a non-primary radio. (Only meaningful when XPRI is not NONE)Table 14. Operating Status—Display Only (Continued)Command Description
40 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01   10.3 Detailed Command DescriptionsThe essential commands for most applications are Network Address (ADDR), Mode (MODE), and Baud Rate (BAUD). However, proper use of the additional commands allows you to tailor the transceiver for a specific use, or to conduct basic diagnostics on the radio. This section gives more detailed information for the commands listed above in section 9.2.Most of the commands below can be used in two ways. First, you can type only the command name (for example, ADDR) to view the currently programmed data. Second, you can set or change the existing data by typing the command, followed by a space, and then the desired entry (for example, ADDR 1234). In the list below, allowable programming variables, if any, are shown in brackets [  ] following the command name.ADDR [1–65000]This command sets or displays the radio’s network address. The network address can range from 1 to 65000.A network address must be programmed at the time of installation and must be common across each radio in a given network. Radios are typically shipped with the network address unprogrammed, causing the address to display as NONE. If the address is not set (or is set to a wrong value) it leaves the system in an invalid state, preventing operation and generating an alarm.NOTE: It is recommended that the last four digits of the master radio’s serial number be used for the network address. This helps avoid conflicts with other users.Table 15. Diagnostic and Test Functions  Command DescriptionKEYDetails, page 45 Enables the transmitter test. (Radio must be in Setup mode.)DKEYDetails, page 44 Turns off the transmitter test. (Radio must be in Setup mode.)TX [xxxx]Details, page 50 Set/display transmit test frequency. (Radio must be in Setup mode.)RX [xxxx]Details, page 48 Set/display receive test frequency. (Radio must be in Setup mode.)SETUPDetails, page 49 Enables Setup mode. Times out after 10 min-utes. Press “Q” to quit.ZONE DATADetails, page 51 Zone data statisticsZONE CLEARDetails, page 51 Clears the Zone Data log
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 41AMASK [0000 0000–FFFF FFFF]This command sets the alarm bits that cause the alarm output signal to be triggered. The PWR LED will still flash for all alarms, but the alarm output signal will only be activated for those alarms that have the corresponding mask bit set. The hex value for the mask aligns directly with the hex value for the ALARM command. The default is FFFF FFFF. Through proper use of the AMASK command, it is possible to tailor the alarm response of the radio. Contact the factory for more information on configuring the alarm mask.ASENSE [HI/LO]This command is used to set the sense of the radio’s alarm output at Pin 3 of the 16-pin header connector. The default setting is HI which means an alarm exists when an RS-232 high is on Pin 3.BAND [abc]The BAND command is used to select one of three frequency ranges that the transceiver will operate in (A, B, or C). All transceivers in a given network must have the same band setting or communication will not be possible. Conversely, radios may be set to different bands to enable up to three separate radio networks to operate in the same vicinity, without cross-network interference.Each frequency band is approximately 26 MHz wide, and contains eight “zones” within. These zones are described in more detail under the ZONE DATA command (see Page 51). The frequency ranges for each band are as follows:Band A: 2.4016–2.4270 GHzBand B: 2.4272–2.4526 GHzBand C: 2.4528–2.478.2 GHzBAUD [xxxxx abc]This command sets or displays the communication attributes for the normal payload communications through the DATA port. The command has no effect on the RJ-11 DIAG(NOSTICS) port.The first parameter (xxxxx) is baud rate. Baud rate is specified in bits-per-second and must be one of the following speeds: 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200. At baud rates of 19200 bps or less, the radio can support unlimited continuous data transmission at any hop rate.The second parameter of the BAUD command (abc) is a 3-character block indicating how the data is encoded. The following is a breakdown of each character’s meaning:a = Data bits (7 or 8)b = Parity (N for None, O for Odd, E for Even)c = Stop bits (1 or 2)The factory default setting is 9600 baud, 8 data bits, no parity, 1 stop bit (Example: 19200 8N1).
42 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 NOTE: 7N1, 8O2, and 8E2 are invalid communication settings and are not supported by the transceiver.BUFF [ON, OFF]This command sets or displays the received data handling mode of the radio. The command parameter is either ON or OFF. (The default is OFF.) The setting of this parameter affects the timing of received data sent out the DATA connector. Data transmitted over the air by the radio is unaffected by the BUFF setting.If data buffering is set to OFF, the radio will operate with the lowest possible average latency. Data bytes are sent out the DATA port as soon as an incoming RF data frame is processed. Average and typical latency will both be below 10 ms, but idle character gaps may be introduced into the outgoing data flow.If data buffering is ON, the radio will operate in a seamless mode. That is, data bytes will be sent over the air as quickly as possible, but the receiver will buffer the data until the entire packet has been collected. The delay introduced by data buffering is variable and depends on message size and the number of retransmissions required, but the radio will not create any gaps in the output data stream. This mode of operation is required for protocols such as MODBUS™ that do not allow gaps in their data transmission.Seamless mode (BUFF ON) is intended only for applications where the message size is 256 characters or less. Enforcement of this rule is left up to the user. If more than 256 characters are transmitted data delivery will not be seamless and data may be lost.Changes to the BUFF setting may only be made at the master radio. This is because the master radio broadcasts the buffer setting for the entire network. At remote radios, the buffer setting may be read when the radio is in synchronization with the master, but it may not be changed.CODE [NONE, 1…255]The CODE command is used to select or display the security/encryption setting in the radio.The default is CODE NONE. Setting CODE to a value other than NONE provides an extra level security beyond that provided by the Network Address (ADDR). The disadvantage is increased complexity in managing the network. The CODE command takes an argument 1…255, or “NONE”. Entering CODE without an argument will display either “NONE” or “ACTIVE”. ACTIVE means that security/encryption has been enabled, but the radio will not display the security argument.When a CODE value is active, all radios in the system must use the same code value. If the code value is not properly programmed, a remote radio will not synchronize with the master.CAUTION: Record the CODE value and store it in a safe place. If the code is later forgotten, and a unit is to be added to the system, all radios in the network must be set to NONE and then reprogrammed to a new value.
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 43CTS [0–255]The CTS (clear-to-send) command sets or displays the timer value associated with the CTS line response. The command parameter ranges from 0 to 255 milliseconds.For DCE operation, the timer specifies how long to wait after the RTS line goes high before asserting the CTS line. A timer value of zero means that the CTS line will be asserted immediately following the assertion of RTS.For CTS Key operation (see the DEVICE command), the timer specifies how long to wait after asserting the CTS line before sending data out the DATA port. A timer value of zero means that data will be sent out the data port without imposing a key-up delay. (Other delays may be in effect from other radio operating parameters.)CTSHOLD [0–60000]Used in DEVICE CTS KEY mode, this command sets the amount of time in milliseconds that CTS remains present following transmission of the last character out the RXD pin of the DATA port. This “hold time” can be used to prevent squelch tail data corruption when communicating with other radios.The CTSHOLD setting can range from 0 to 60000 (i.e., 60 seconds). The default value is 0, which means that CTS will drop immediately after the last character is transmitted. If the command is entered when the radio is in DEVICE DCE mode, the response CTSHOLD N/A will be displayed.DEVICE [DCE, CTS  KEY]The DEVICE command sets or displays the device behavior of the radio. The command parameter is either DCE or CTS KEY.The default selection is DCE. In this mode, CTS will go high following RTS, subject to the CTS programmable delay time. Keying is stimulated by the input of characters at the data port. Hardware flow control is implemented by dropping the CTS line if data arrives faster than it can be transmitted.If CTS KEY is selected, the radio is assumed to be controlling another radio, such as in a repeater or tail-end link system. The RTS line is ignored and the CTS line is used as a keyline control for the other radio. CTS is asserted immediately after the receipt of RF data, but data will not be sent out the DATA port until after the CTS programmable delay time has expired. (This gives the other radio time to key.)Following transmission of the last byte of data, CTS will remain asserted for the duration specified by the CTSHOLD command. CTSHOLD should be set sufficiently high.DLINK [xxxxx/ON/OFF] DLINK ON enables use of Diagnostic Link mode and establishes it as the default protocol on the RJ-11 DIAG port. Diagnostic Link mode is a special protocol used to support Network-Wide Diagnostics. DLINK must be set to ON to support connection to InSite or to support chained diagnostics between radio networks. DLINK OFF disables this feature. The default setting is ON.
44 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 The following DLINK baud rates selections are allowed:• 1200 • 4800 • 9600 • 19200 (default)• 38400 • 57600 • 115200Example: DLINK 4800 sets the RJ-11 DIAG port to operate at 4800 bps when diagnostics is “closed”. This setting will not affect the port’s autobaud operation. Use only of DLINK ON, will enable the use 19200 or the most recently programmed value. The default is DLINK 19200 and DLINK ON. NOTE: The same baud rate must be entered into the InSite Equipment List’s BAUD field.NOTE: The DLINK rate must match the rate of any connected device to the diagnostic port. This may be either another radio’s diagnostic port, the InSite computer, or another data link device that eventually connects to the InSite computer.DKEYDisables the transmitter when it is keyed. See also KEY command.DTYPE [NODE/ROOT]The DTYPE command specifies the radio’s operational characteristics for network-wide diagnostics. The transceiver uses the following types:•NODE–The most common setting, and the default. This is the basic system radio device-type. Typically, the radio network is comprised of nodes and one root. Intrusive diagnostics can originate from any node. However, non-intrusive diagnostics can only be conducted from the root node.•ROOT–Always one, and only one, per network (including units associated through Extension units.) The root is the focal point of network-wide diagnostics information. Intrusive diagnostics can originate from any radio, including the root. However, the root is the only radio through which non-intrusive diagnostics can be conducted.FEC [ON, OFF]This command is used to view the FEC setting, or turn it on or off. The default setting is FEC ON. (It needs to be turned off when throughputs exceed 57,600 bps.) FEC is set at the master and is automatically passed on to all of the remotes in a network.Setting FEC to ON improves sensitivity at the cost of reduced throughput. Typical SCADA/telemetry applications use low data rates and, as such, the FEC setting is normally transparent to them.HOPTIME [7, 28]The HOPTIME command is used to set or display the hop-time setting. The command is a digit corresponding to the hop-time setting in milliseconds. The default HOPTIME setting is 7. A setting of 28 must be used when throughputs exceed 57,600 bps.
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 45Changes to the HOPTIME setting may only be made at the master radio. (This is because the Master radio establishes the hop-time setting for the entire network.) At remote radios, the hop-time setting may be read when the radio is in synchronization with the master, but it may not be changed.INITThe INIT command is used to reset the radio’s operating parameters to the factory defaults listed in Table 16 on Page 46. This may be helpful when trying to resolve configuration problems that resulted from the entry of one or more improper command settings. If you are unsure of which command setting caused the problem, this command allows you to get back to a known working state.NOTE: Caution should be exercised when using the INIT command on radios in a sys-tem employing the Store-and-Forward feature. Settings relating to the use of Extension services will be lost and will need to be re-entered. Inventory and record the settings for XADDR, XPRI and XMAP before using the INIT com-mand.SPECIAL NOTE: Installing firmware of Revision 2.0 or later into a radio with Revi-sions 1.x firmware will preserve the radio’s compatibility with other radios run-ning Revision 1.x firmware. If updating the radio’s firmware is part of a system-wide upgrade, the last step should be to use the INIT command at the Master station. Use of the INIT command causes the changes shown in Table 16 on Page 46 to be appliedHREVShows the Hardware revision of the radio.KEYEnables the transmitter. (Radio must be in Setup mode.) See also DKEY command.LEDS [ON, OFF]This command is used to view the LED setting, or to enable/disable LED operation. In power-critical applications (battery/solar powered sites, for example), it may be desirable to turn off the LEDs.MODE [M, R, X]The MODE command sets or displays the operating mode of the radio. A master radio is set by MODE M; a remote set by MODE R, and an Extension is set by MODE X.All units default to remotes; other modes must be specifically programmed with the MODE command.If MODE X is used, the MODE X radio should be programmed with an Extended Address (XADDR). Units that need to hear this MODE X radio must be programmed with an appropriate XPRI and/or XMAP value.
46 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 OWM [xxxxx]The OWM command sets or displays an optional owner’s message, such as the system name. The entry can contain up to 30 characters.OWN [xxxxx]The OWN command sets or displays an optional owner’s name, such as the site name. The entry can contain up to 30 characters.PORT [RS232, RS485]Select or identify the current data interface signaling mode: RS232 or RS485. This is the port though which the payload data will pass. Pin descriptions for EIA-232 are on Page13 and EIA-485 can be found on Page13. Note: This command will always show TTL if the radio is only equipped for TTL service—see model number configuration code on Page 3.PWR [17–21]This command displays or sets the desired RF forward output power setting of the radio. The PWR command parameter is specified in dBm and can range from 20 dBm through 27 in 1 dBm steps. The default setting is 27 dBm (0.5 watt). To read the actual (measured) power output of the radio, use the SHOW PWR command.In the USA, maximum allowable power is governed by FCC limits on Effective Isotropic Radiated Power output (EIRP). The EIRP limit of +36 dBm means that any user with a net antenna gain greater than 10 dBi must decrease the PWR setting accordingly.Table 16. INIT Command Generated Defaults   Parameter Default Setting Corresponding CommandFor all radiosDevice operation DCE DEVICE DCECTS delay 0 (CTS is continuously asserted) CTS 0CTS hold-time 0CTSHOLD 0DATA Interface port • 9600 baud• 8 data bits• none (no parity)• 1 stop bitBAUD 9600 8N1Alarm Mask FFFF FFFF AMASKAlarm Output Sense RS-232 High (+5.0 Vdc) ASENSERX Time-out-Timer None/Disable RXTOTTransmittertest frequency 2.4xx GHz TX xxx
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 47REPEAT [0–10]The REPEAT command affects “downstream” data. The command causes a Master or Extension to always repeat transmissions for the specified number of times (range is 0 to 10; default selection is 3). Unlike the RETRY command, there is no acknowledgment that a message has been received. To display the current setting, use the REPEAT command without entering a value.RETRY [0–10]The RETRY command affects upstream data. The command selects, or displays, the maximum number of times (0 to 10) that a remote radio will re-transmit data. The default setting is 10.This command is associated with ARQ (Automatic Repeat Request) operation of the radio and is intended for use in areas with heavy radio interference.When the RETRY command is issued without parameters, the maximum retransmission count is shown. A value of 0 represents no retries, while values of 1 or greater successively improve the chance of data delivery in spectrally harsh environments (at the expense of possibly increased latency). The RETRY value is only settable at the Master. It is readable by a synchronized Remote.Receivertest frequency 2.4xx GHz RX xxxSleep Enable OFF SLEEP OFFData Port Setting RS/EIA-232 PORT RS232Primary Extension Radio Address 0 (Master) XPRI 0Synchronization Source Map None XMAP 0Extended Address 0XADDR 0For MASTER radiosSkipped frequencies None (radio will hop across all frequencies) SKIP NONEHop-time 7 ms HOPTIME 7Buffer mode OFF  BUFF OFFRetry Count 10 (max. 10 repeats for ARQ) RETRY 10Repeat Count 3 (downstream repeats) REPEAT 3Forward Error Correction ON FEC ONTable 16. INIT Command Generated Defaults (Continued) Parameter Default Setting Corresponding Command
48 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 RSSIThis command displays the radio’s Received Signal Strength Indication in dBm (decibels relative to 1 mW). The output can range from –40 dBm to –120 dBm. Command availability and results depend on the mode of operation (master or remote). The closer to 0 dBm, the stronger the signal, thus a reading of –70 dBm is stronger than –80 dBm.For a remote radio, under normal operation, RSSI is based on the average signal strength of the SYNC message received in each of the eight frequency zones. (RSSI is sampled each time a SYNC message is received.) When using the RSSI reading to align a directional antenna, it is important to make changes slowly so that the RSSI reading will provide meaningful results. It will take several seconds to indicate a change in signal level. The radio stays in RSSI mode until   is pressed.For a master radio, under normal operation, entering the RSSI command causes the response NOT AVAILABLE to be returned. This is because a master is normally receiving signals from several remote stations and an RSSI reading would be continually changing. The only exception is when the SETUP command has been asserted. This disables hopping and allows reading a “raw” RSSI signal level in real time from a master or remote radio.NOTE: RSSI readings will not indicate signals stronger than –40 dBm.RTU [ON, OFF, 0-80]This command re-enables or disables the radio’s internal RTU simulator, which runs with proprietary polling programs such as poll.exe and rsim.exe. The internal RTU simulator is available whenever a radio has diagnostics enabled. This command also sets the RTU address that the radio will respond to.The internal RTU can be used for testing system payload data or pseudo bit error rate (BER) testing. It can be helpful in isolating a problem to either the external RTU or the radio. The default RTU setting is OFF.RX [xxxx]This command sets or displays the test receive frequency used in place of hopping when the radio is in SETUP mode. The test receive frequency can be reprogrammed to any value between 2.4016 GHz and 2.4782 GHz, inclusive. The factory default setting is 2.42420 GHz.RXTOT [NONE, 0–1440]This command sets or displays the amount of time (in minutes) to wait for the next received data packet before issuing a receiver time-out alarm. The default setting is NONE.ENTER
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 49SAF [ON, OFF]This command enables/disables the operation of the Store-and-Forward services. It can be set only at the network’s Master station, but will effect all radios in the associated network. The default setting is OFF. See related commands: “XADDR [0–31]” on Page 51, “XPRI [0–31]” on Page 51, and “XMAP [00000000-FFFFFFFF]” on Page 51.SETUPThis command sets up the transceiver for checking antenna SWR or trans-mitter power with external measuring equipment. Do not use this mode during normal operation.When the SETUP command is entered, the prompt changes to SETUP>, and:• Hopping is disabled.• Synthesizer frequencies are reset to the test frequencies specified by the TX and RX commands described earlier.• The radio can be keyed using the KEY command. DKEY is used to unkey the radio. (If the radio is left in a keyed state it is automatically unkeyed after several minutes.)• The RSSI is sampled in a raw, continuous fashion regardless of whether the unit is a master or a remote.Entering Q or QUIT returns the system to normal operation.A timer keeps the Setup mode from accidentally leaving the system disabled. After 10 minutes the system behaves as if Q or QUIT had been entered, returning to normal operation.SERDisplays the Serial Number of the radio.SHOW PWR The SHOW PWR command displays the actual (measured) RF power output in dBm. Unlike the PWR command, this command shows the actual level being measured, not the programmed RF power setting.SHOW SYNC When used at a Remote station, this command will display Extended Address and Unit Address of the Master or Extension radio to which the Remote is synchronized. The network depth at the remote, defined as the number of downstream links from the Master, is displayed in parentheses.SKIP [NONE, 1...8]This command sets or displays which, if any, of the eight 3.2 MHz-wide zones will be skipped from the radio’s hopping sequence. Skipping zones is one way of dealing with constant interference on one or more frequencies. See “DEALING WITH INTERFERENCE” on Page 32 for more information on dealing with interference.
50 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 The command parameter is either the keyword NONE or an undelimited string of up to four digits where each digit 1...8 represents a corresponding zone to skip. (For zone parameter input, the digits can appear in any order and can be optionally separated by a blank space.) The SKIP command is display-only at remote radios. (Remotes must be synchronized with the master radio to display the skip status.)In the USA, a maximum of four zones may be skipped, per FCC rules. Check the regulatory requirements for your region before deleting zones.SLEEP [ON, OFF]This command is used to set or display the radio’s Sleep Mode setting. The default setting is SLEEP OFF. When this mode is enabled (ON), a ground or logic low on Pin 6 of the 16-pin header connector (J3) suspends all normal radio functions, and power consumption is reduced to approximately 8 mA. The radio remains in this state until the low is removed. This function cannot be turned on for a Master or Extension radio.SREVThis command displays the version of the firmware currently loaded into the transceiver.A display of 06-4040A01, 2.0.0 is an example of the firmware version identifier—part number followed by release/version number.STATThis command is used to check the alarm status of the radio. If no alarms exist, the message NO ALARMS PRESENT is returned.If an alarm does exist, a two-digit alarm code (00–31) is displayed and the event is identified as a “Major” or “Minor” alarm. A brief description of the event is also given.If more than one alarm exists, the word MORE appears, and additional alarms may be viewed by pressing the   key. Detailed descriptions of the alarm codes are provided in Table 17 on Page 54.TEMPThis command displays the internal temperature of the transceiver in degrees Celsius. (Note that the radio is specified to operate in an environment between –30 C° and +60 C°). This internal reading may be higher than the outside temperature by several degrees.TX [xxxx]This command sets or displays the test transmit frequency used in place of hopping whenever the radio is in Setup mode. The test transmit frequency can be reprogrammed to any value between 2.4016 GHz and 2.4782 GHz, inclusive. The factory default setting is 2.42420 GHz.ENTER
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 51UNIT [10000–65000]This command sets the unit addressing for network-wide diagnostics. The unit address is factory programmed to the last four digits of the serial number. If re-programmed in the field, the entry must consist of five digits between 10000 and 65000.XADDR [0–31]Display or program the Extended Address of this radio that will serve as a common address for the sub-network synchronized to this Master or Extension. This value can be listed in the XPRI parameter of associated Extension or Remote radios to allow them to synchronize to this radio. We recommend setting the Master to zero (0). It is easy to remember, and is the default address when the INIT command is used. (Programmed only in Master and Extension radios.)XMAP [00000000-FFFFFFFF]XMAP is a 32-bit hex entry where the least significant bit represents XADDR 0 and the most significant bit represents XADDR 31. The full 32-bit hex value represents the entire list of extensions with which the radio will be allowed to communicate. (Remotes and Extensions only.)This parameter is easily programmed through the TransNET Configuration Software’s Store and Forward Settings panel.XPRI [0–31]Display or program the extended address of a primary radio with which this radio will attempt to synchronize and communicate. A setting of NONE will allow the unit to synchronize with any Master or Extension in the XMAP list. (Parameter only meaningful for a Remote or Extension.)XRSSI [NONE, –40...–120]The XRSSI command is used to set the RSSI minimum signal level required to preserve synchronization with a non-primary Extension radio. This parameter will be ignored if XPRI is set to NONE.ZONE CLEARThe ZONE CLEAR command clears the zone data for all zones in the Zone Data Log, resetting the count to 0. (Zone data is also cleared automatically upon reboot.)ZONE DATAThe transceiver divides its frequency operating spectrum into eight 3.2 MHz-wide zones. (These are the same zones referenced by the SKIP command described earlier.) Data frame statistics are maintained for each zone to indicate the transmission quality of data through the network. This information is useful for identifying zones where significant interference exists.
52 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 Zone quality information can be accessed using the ZONE DATA command. For each zone (1–8), it shows you the number of data frames sent, the number received, and the number received with errors. If an excessive number of errors are seen in one or more frequency zones, it may indicate interference, and you should consider “skipping” those zones using the SKIP command.Note: If a frequency zone has been skipped, all counts for that zone will be zeros.The ZONE DATA format is displayed as follows:1:TX TOTAL 000000001:RX TOTAL 000000001:RX ERROR 00000000x:x:x:8:TX TOTAL 000000008:RX TOTAL 000000008:RX ERROR 00000000All data is based on payload packets. Incoming network data may be divided up into multiple packets for over-the-air transfers. The number before the colon represents the zone. TX TOTAL is the transmit packet total. RX TOTAL is the receive packet total. RX ERROR is the total number of received packets with CRC errors. All zone data is reset with the ZONE CLEAR command.11.0 TROUBLESHOOTINGSuccessful troubleshooting of the radio system is not difficult, but requires a logical approach. It is best to begin troubleshooting at the master station, as the rest of the system depends on the master for polling instructions and synchronization data. If the master station has problems, the operation of the entire network will be affected.When communication problems are found, it is good practice to begin by checking the simple things. All radios in the network must meet these basic requirements:• Adequate and stable primary power• An efficient and properly aligned antenna system• Secure connections (RF, data & power)• Proper programming of the radio’s operating parameters, especially Mode selection (MODE), Network Address (ADDR), and interface Baud Rate (BAUD)• The correct interface between the radio and the connected data equipment (proper cable wiring, data format and timing).• In store-and-forward systems there are several areas that must be carefully evaluated:
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 53• Duplicate XADDR values on MODE M and MODE X radios will cause failures unless the radios are far enough apart to not hear each other.• Errors in the synchronization qualifiers, XPRI and XMAP, on corresponding Remote radios.•SAF must be enabled at the Master11.1 Alarm CodesWhen an alarm condition exists, the transceiver creates an alarm code. These codes can be very helpful in resolving many system difficulties.Checking for Alarms—STAT commandTo check for the presence of alarms, enter STAT. If no alarms exist, the message NO ALARMS PRESENT appears at the top of the display.If an alarm does exist, a two-digit alarm code (00–31) is displayed, and it is identified as a major or minor alarm. A brief description of the alarm is also given. Alarm codes and their meanings are listed in Table 17.If more than one alarm exists, the word MORE appears at the bottom of the screen; additional alarms can be viewed by pressing  .Major Alarms vs. Minor AlarmsMajor alarms report serious conditions that generally indicate a hardware failure, or other abnormal condition that will prevent (or seriously hamper) further operation of the transceiver.With the exception of alarm code 00 (network address not programmed), major alarms generally indicate the need for factory repair. Contact your factory representative for further assistance.Minor alarms report conditions which, under most circumstances, will not prevent transceiver operation. This includes out-of-tolerance conditions, baud rate mismatches, etc. The cause of these alarms should be investigated and corrected to prevent system failure.ENTER
54 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 Alarm Code DefinitionsTable 17 contains a listing of all event codes that may be reported by the transceiver.Additional alarm codes may be used in future firmware releases or are used by the factory.  Table 17. Alarm Codes  Alarm Code Alarm Type Description00 Major The network address is not programmed.01 Major Improper firmware detected for this radio model.04 Major One or more of the programmable synthesizer loops is reporting an out-of-lock condition.08 Major The system is reporting that it has not been calibrated. Factory calibration is required for proper radio operation.10 Major The DSP was unable to properly program the system to the ap-propriate defaults. A hardware problem may exist.12 Major Receiver time-out alarm.16 Minor The unit address is not programmed.17 Minor A data parity fault has been detected on the DATA connector. This usually indicates a parity setting mismatch between the ra-dio and the RTU.18 Minor A data framing error has been detected on the DATA connector. This may indicate a baud rate mismatch between the radio and the RTU.29 Minor RF output power fault detected. (Power differs by more than 2 dB from set level.) Often caused by high antenna system SWR. Check antenna, feedline and connectors.30 Minor The system is reporting an RSSI reading below –105 dBm. 31 Minor The transceiver’s internal temperature is approaching an out-of-tolerance condition. If the temperature drifts outside of the recommended operating range, system operation may fail.
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 5511.2 LED IndicatorsThe LED indicators on the transceiver board (CR3, CR-4, CR-5 and CR-6) are an important troubleshooting tool and should be checked whenever a problem is suspected. Table 18 describes the function of each status LED. 11.3 Troubleshooting ChartTable 19 provides suggestions for resolving system difficulties that may be experienced in the radio system. If problems persist, contact the factory for further assistance. Refer to the inside back cover of this guide for contact information.Table 18. LED indicator descriptionsLED Name DescriptionRXD (CR3)Receive DataSerial receive data activity. Payload data from con-nected device.TXD (CR4)Transmit DataSerial transmit data activity. Payload data to con-nected device.DCD (CR5)Data Carrier DetectContinuous—Radio is receiving/sending synchroni-zation framesOn within 10 seconds of power-up under normal conditionsGP (CR6)General Purpose •Continuous—Power is applied to the radio; no problems detected•Flashing (5 times-per-second)—Fault indication. See “TROUBLESHOOTING” on Page 52•Off—Radio is unpowered or in Sleep modeRXDTXDDCDGP
56 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 11.4 Network-Wide Remote DiagnosticsDiagnostics data from a remote radio can be obtained by connecting a laptop or personal computer running InSite diagnostics software (V6.6 or later) at any radio in the network.Table 19. Troubleshooting chartDifficulty Recommended System ChecksUnit isinoperative. a.Check for the proper supply voltage at the transceiver, J3 Pins 5 and11.b.If using the Evaluation Board, the surface mount fuse may have opened. Refer to Section 4.3 below for replacement instruc-tions.Interference is suspected. a.Verify that the system has a unique network address. Nearby systems with the same address will cause interference.b.Check for interference and lockout any affected zone(s) using the SKIP command (Page 49).c.If omnidirectional antennas are used on remote stations, con-sider changing to directional antennas. This will often limit inter-ference to and from other stations.No synchroniza-tion with master, or poor overall performance.a.Check for secure interface connections at the radio and the connected device.b.Check the antenna, feedline and connectors. Reflected power should be less than 10% of the forward power reading (SWR ≈ 2:1 or lower).c.If the remote radio is in synchronization, but performance is poor, check the received signal strength using the RSSI com-mand (Page 48). If RSSI is low, it may indicate antenna prob-lems, or misalignment of directional antenna headings.d.Verify proper programming of system parameters: mode, net-work address, data interface baud rate, transmitter power, CTS delay, etc. For store-and-forward applications, also verify the following: SAF is ON; extended address is properly pro-grammed at each extension; remotes are using the proper val-ues for XPRI and XMAP.e.Check for alarms using the STAT command (Page 50)BER is too high. Data throughput is spotty.a.The RETRY and REPEAT commands may be increased to deal with interference, or decreased to increase throughput and reduce latency. b.Try turning on FEC. FEC on gives some coding gain, but comes at the cost of reduced throughput.Latency is too high. a.Reduce the REPEAT count.b.Turn BUFF OFF. BUFF ON insures that no gaps occur in the data, but this comes at the cost of increased latency.c.Make sure HOPTIME is set to 7.
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 57NOTE: The diagnostics feature may not be available in all radios. The ability to query and configure a radio via Network-wide Diagnostics is based on the feature op-tions purchased in the radio being polled.If a PC is connected to any radio in the network, intrusive polling (polling which briefly interrupts payload data transmission) can be performed. To perform diagnostics without interrupting payload data transmission, connect the PC to a radio defined as the “root” radio. A radio is defined as a root radio using the DTYPE ROOT command locally, at the radio.A complete explanation of remote diagnostics can be found in the Network-Wide Diagnostics System Handbook (Part No. 05-3467A01).1. Program one radio in the network as the root radio by entering the DTYPE ROOT command at the radio.2. At the root radio, use the DLINK ON and DLINK [baud rate] commands to configure the diagnostic link protocol on the RJ-11 port.3. Program all other radios in the network as nodes by entering the DTYPE NODE command at each radio.4. Use the DLINK ON and DLINK [baud rate] commands to configure the diagnostic link protocol on the RJ-11 port of each node radio.5. Connect a PC on which InSite software is installed to the root radio, or to one of the nodes, at the radio’s diagnostics port.To connect a PC to the radio’s DIAG port, an RJ-11 to DB-9 adapter (Part No. 03-3246A01) is required. If desired, an adapter cable may be constructed from scratch, using the information shown in Figure 10 on Page 11.6. Launch the InSite program at the PC. (Refer to the InSite user’s manual for details.)Table 20. Network-Wide Diagnostics CommandsCommand DescriptionDLINK [xxxxx/ON/OFF]Details, page 43 Set baud rate of diagnostics linkDTYPE [NODE/ROOT]Details, page 44 Set radio’s operational characteristics for net-work-wide diagnostics
58 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 12.0 FIRMWARE UPGRADESFrom time to time, the factory releases new firmware for its radio products. An upgraded file can be installed in existing radios to take advantage of engineering improvements or additional features.12.1 Obtaining new firmwareThe latest firmware for each radio type may be obtained free of charge from our website: www.microwavedata.com/service/technical/support/downloads/.Firmware is also available on disks from the factory that are bundled with an installation utility (Radio Software Upgrade—upgrade.exe) for transferring the firmware file on the disk to the radio.Saving a Web-site firmware file to your PCFirmware upgrades are distributed as a plain-text (ASCII) file with a “.S28” extension. Browse to find the desired “.S28” file for your radio on the factory website at www.microwavedata.com. After finding your selection, use the right mouse button to select a path on your computer on which to save the file. (If this isn’t done, your browser may display the firmware file contents as text on the screen instead of downloading it to your local hard drive.) After the “.S28” file has been saved to your computer, you may use either TransNET Configuration Software or Radio Software Upgrade programs to install this firmware in your radios.12.2 Installing firmware in your radio1. Connect a PC to radio’s diagnostic interface. 2. Start the TransNET Configuration Software. Open diagnostics port to the radio. The program will automatically read the radio’s profile.3. From the File menu select Radio Firmware Upgrade and follow the prompts to install the new firmware into the radio. Do not press the Cancel button once the installation has started or it will leave the radio without any code. When the installation is complete, another radio may be connected to your PC and programmed.NOTE: If a firmware installation fails, the radio is left unprogrammed and inoperative. This is indicated by the PWR LED flashing slowly (1 second on/1 second off). This condition is only likely to occur if there is a power failure to the computer or radio during the installation process. The installation should be attempted again.13.0 SecurityToday, the operation and management of an enterprise is becoming increasing dependent on electronic information flow. An accompanying concern becomes the security of the communication infrastructure and the security of the data itself. We take this matter seriously, and provide several means for protecting the data carried over our wireless products.
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 59Our radios address this issue primarily through the use of the following items: 1) A proprietary modem/data link layer—Data signals are processed using code and hardware specifically designed by the manufacturer.2) A unique Network Address—This provides a unique identifier for each radio in a network. A radio is not addressable unless this unique code is included in the data string.3) An optional encryption value (code)—Setting an encryption code requires the use of the CODE command. This command scrambles the radio’s hop pattern and encrypts payload data content. A radio requires the correct Network Address (ADDR) and CODE value in order to synchronize. When the CODE command is used, the same value must be programmed into all radios in the network. See “CODE [NONE, 1…255]” on Page 42 for more details.The effective combination of CODE and ADDR discourage the use of an exhaustive search to gain access to a system. The items described above provide sufficient security for most systems. For highly-sensitive applications, system designers should consider employing application level encryption into their polling protocols to further protect their systems. Third party software tools are available for adding encryption, and these should be considered as part of any advanced encryption scheme.14.0 Product SpecificationsGENERALFrequency Hopping Range: Up to xx frequencies within each band:2.4016–2.4270 GHz (Band A)2.4272–2.4526 GHz (Band B)2.4528–2.478.2 GHz (Band C)Above are configurable in 3.2 MHz zones.Hop Pattern: Based on network addressFrequency Stability: ±1.5 ppmHalf-Duplex Operation: ±1.6 MHz TX/RX splitNetwork Addresses: 65,000Temperature Range: –40° C to +70° CHumidity: <95% at +40° C; non-condensingPrimary Power: 13.8 Vdc (5–25 Vdc range)Current Draw (typical): Transmit: 510 mA @ 13.8 VdcReceive: 115 mA @ 13.8 VdcSleep Mode: 8 mA @ 13.8 VdcPhysical Dimensions: 1.81"W x 3.45"L x 0.63"H(46 x 87.5 x 16 mm)Agency Approvals (pending): • FCC Part 15.247 (E5MDS-EL806-2.4)• FCC Limited Modular Approval (LMA)• Industry Canada RSS-210 and RSS-139   (CAN 3738A-MDSEL806-2.4)
60 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 DATA CHARACTERISTICSData Interface: RS-232/422/485Interface Connector: 16 pin header, femaleData Rate: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps asynchronousData Latency: 7 ms (typical)Byte Length: 10 or 11 bitsMaximum Data Transmission: Continuous up to 115200 bpsRF CHARACTERISTICSTRANSMITTER:Power Output(at antenna connector): 50 mW to 0.5 Watt (+17 to +27 dBm)Refer to Table 7 on Page 24Duty Cycle: ContinuousModulation Type: Binary CPFSKOutput Impedance: 50 OhmsSpurious: –60 dBcHarmonics: –55 dBcRECEIVER:Type: Double conversion superheterodyneSensitivity: –108 dBm @ 1 x 10-6 BERIntermodulation: 54 dB minimum (EIA)Desensitization: 75 dBSpurious: 70 dB minimumBandwidth: 200 kHzInterference Ratio(SINAD degraded by 3dB): Co-channel:–10 dBAdjacent channel:+30 dBTwo channels away:+40 dBThree channels away:+48 dBTime Required to Synchronizewith Master Radio: 0.5 seconds (typical):14.1 Detailed Pin DescriptionsThe tables in this section give detailed pin functions for the transceiver’s 16-pin header connector, J3 (see Figure 21). The tables are organized according to the available signaling configurations of the OEM transceiver. (Figure 2 on Page 3 may be used to determine which configuration you have.) Signaling configuration is hardware fixed at the time of manufacture and will be one of the following:• TTL signaling for both Payload and Diagnostic data• Payload data TTL; Diagnostic data RS-232• Payload data RS-232/RS-485 selectable; Diagnostic data RS-232
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 61Figure 21. 16-pin Header Connector (J3) on OEM Transceiver Board(See parts list (Page18) for information on matching connector)Table 21. Transceiver Connector J3 Pinouts(Payload data TTL; Diagnostic data TTL)  Pin No. Input/Output SignalType Name/Description1IN --Ground—Connects to ground (negative supply potential).2 OUT TTL, 3 Vdc Diagnostic TXD—Supplies received diagnos-tic/administrative data to the connected device.3 OUT TTL, 3 Vdc Alarm condition—A low indicates normal opera-tion. A high indicates an alarm. (See ASENSE [HI/LO] command for more information.)4 IN TTL, 3 Vdc Diagnostic RXD—Accepts diagnostic/adminis-trative data from the connected device.5 IN -- FCC 6-18 Vdc version: DC Input (5-25 Vdc)— Supply Source must be capable of furnishing at least 7.5 watts.Non-FCC 3 Vdc version: Do not connect6 IN TTL, 3 Vdc Sleep Mode Input—A ground on this pin turns off most circuits in a remote radio. This allows for greatly reduced power consumption, yet pre-serves the radio’s ability to be brought quickly back on line. See “Sleep Mode Operation (Re-mote units only)” on Page 31 for details.7 OUT TTL, 3 Vdc Data Carrier Detect (DCD)—A low indicates hop-ping synchronization has been achieved.8 IN TTL, 3 Vdc Power Supply Shutdown Control—A ground on this pin causes the OEM module’s power supply to shut down.9 -- -- Non-FCC 3 Vdc version: DC Input (Regulated 3.3 Vdc)—Supply Source must be capable of fur-nishing at least 7.5 watts.FCC 6-18 Vdc version: Do not connect116253487691514 1312 1110
62 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 10 IN TTL, 3 Vdc Transmitted Data (TXD)—Accepts payload data from the connected device.11 IN -- FCC 6-18 Vdc version: DC Input (5-25 Vdc)— Supply Source must be capable of furnishing at least 7.5 watts.Non-FCC 3 Vdc version: Do not connect12 IN TTL, 3 Vdc Request to Send (RTS)—A high causes CTS to follow after the programmed CTS delay time has elapsed (DCE).13 -- -- Reserved—Do not connect.14 OUT TTL, 3 Vdc Received Data (RXD)—Supplies received pay-load data to the connected device.15 IN -- Ground—Connects to ground (negative supply potential).16 OUT TTL, 3 Vdc Clear to Send (CTS)—Goes high after the pro-grammed CTS delay time has elapsed (DCE), or keys an attached radio when RF data arrives (CTS KEY).Table 22. Transceiver Connector J3 Pinouts(Payload data TTL; Diagnostic data RS-232)  Pin No. Input/Output SignalType Name/Description1IN --Ground—Connects to ground (negative supply potential).2 OUT RS-232 Diagnostic TXD—Supplies received diagnos-tic/administrative data to the connected device.3 OUT TTL, 3 Vdc Alarm condition—A low indicates normal opera-tion. A high indicates an alarm. (See ASENSE [HI/LO] command for more information.)4 IN RS-232 Diagnostic RXD—Accepts diagnostic/adminis-trative data from the connected device.5 IN -- FCC 6-18 Vdc version: DC Input (6-18 Vdc)— Supply Source must be capable of furnishing at least 7.5 watts.Non-FCC 3 Vdc version: Do not connectTable 21. Transceiver Connector J3 Pinouts(Payload data TTL; Diagnostic data TTL)  (Continued)
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 636 IN TTL, 3 Vdc Sleep Mode Input—A ground on this pin turns off most circuits in a remote radio. This allows for greatly reduced power consumption, yet pre-serves the radio’s ability to be brought quickly back on line. See “Sleep Mode Operation (Re-mote units only)” on Page 31 for details.7 OUT TTL, 3 Vdc Data Carrier Detect (DCD)—A low indicates hop-ping synchronization has been achieved.8 IN TTL, 3 Vdc Power Supply Shutdown Control—A ground on this pin causes the OEM module’s power supply to shut down.9 -- -- Reserved—Do not connect.10 IN TTL, 3 Vdc Transmitted Data (TXD)—Accepts payload data from the connected device.11 IN -- FCC 6-18 Vdc version: DC Input (6-18 Vdc)— Supply Source must be capable of furnishing at least 7.5 watts.Non-FCC 3 Vdc version: Do not connect12 IN TTL, 3 Vdc Request to Send (RTS)—A high causes CTS to follow after the programmed CTS delay time has elapsed (DCE).13 -- -- Reserved—Do not connect.14 OUT TTL, 3 Vdc Received Data (RXD)—Supplies received pay-load data to the connected device.15 IN -- Ground—Connects to ground (negative supply potential).16 OUT TTL, 3 Vdc Clear to Send (CTS)—Goes high after the pro-grammed CTS delay time has elapsed (DCE), or keys an attached radio when RF data arrives (CTS KEY).Table 22. Transceiver Connector J3 Pinouts(Payload data TTL; Diagnostic data RS-232)  (Continued)
64 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 Table 23. Transceiver Connector J3 Pinouts(Payload data RS-232; Diagnostic data RS-232)  Pin No. Input/Output SignalType Name/Description1IN --Ground—Connects to ground (negative supply potential).2 OUT RS-232 Diagnostic TXD—Supplies received diagnos-tic/administrative data to the connected device.3 OUT TTL, 3 Vdc Alarm condition—A low indicates normal opera-tion. A high indicates an alarm. (See ASENSE [HI/LO] command for more information.)4 IN RS-232 Diagnostic RXD—Accepts diagnostic/adminis-trative data from the connected device.5 IN -- FCC 6-18 Vdc version: DC Input (6-18 Vdc)— Supply Source must be capable of furnishing at least 7.5 watts.Non-FCC 3 Vdc version: Do not connect6 IN TTL, 3 Vdc Sleep Mode Input—A ground on this pin turns off most circuits in a remote radio. This allows for greatly reduced power consumption, yet pre-serves the radio’s ability to be brought quickly back on line. See “Sleep Mode Operation (Re-mote units only)” on Page 31 for details.7 OUT TTL, 3 Vdc Data Carrier Detect (DCD)—A low indicates hop-ping synchronization has been achieved.8 IN TTL, 3 Vdc Power Supply Shutdown Control—A ground on this pin causes the OEM module’s power supply to shut down.9 -- -- Reserved—Do not connect.10 IN RS-232, +/- 5 Vdc Transmitted Data (TXD)—Accepts payload data from the connected device.11 IN -- FCC 6-18 Vdc version: DC Input (6-18 Vdc)— Supply Source must be capable of furnishing at least 7.5 watts.Non-FCC 3 Vdc version: Do not connect12 IN RS-232, +/- 5 Vdc Request to Send (RTS)—A high causes CTS to follow after the programmed CTS delay time has elapsed (DCE).
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 6513 -- -- Reserved—Do not connect.14 OUT RS-232, +/- 5 Vdc Received Data (RXD)—Supplies received pay-load data to the connected device.15 IN -- Ground—Connects to ground (negative supply potential).16 OUT RS-232, +/- 5 Vdc Clear to Send (CTS)—Goes high after the pro-grammed CTS delay time has elapsed (DCE), or keys an attached radio when RF data arrives (CTS KEY).Table 24. Transceiver Connector J3 Pinouts(Payload data RS-485; Diagnostic data RS-232)  Pin No. Input/Output SignalType Name/Description1IN -- Ground—Connects to ground (negative supply potential).2 OUT RS-232 Diagnostic TXD—Supplies received diagnos-tic/administrative data to the connected device.3 OUT TTL, 3 Vdc Alarm condition—A low indicates normal opera-tion. A high indicates an alarm. (See ASENSE [HI/LO] command for more information.)4 IN RS-232 Diagnostic RXD—Accepts diagnostic/adminis-trative data from the connected device.5 IN -- FCC 6-18 Vdc version: DC Input (6-18 Vdc)— Supply Source must be capable of furnishing at least 7.5 watts.Non-FCC 3 Vdc version: Do not connect6 IN TTL, 3 Vdc Sleep Mode Input—A ground on this pin turns off most circuits in a remote radio. This allows for greatly reduced power consumption, yet pre-serves the radio’s ability to be brought quickly back on line. See “Sleep Mode Operation (Re-mote units only)” on Page 31 for details.7 OUT TTL, 3 Vdc Data Carrier Detect (DCD)—A low indicates hop-ping synchronization has been achieved.8 IN TTL, 3 Vdc Power Supply Shutdown Control—A ground on this pin causes the OEM module’s power supply to shut down.9 -- -- Reserved—Do not connect.Table 23. Transceiver Connector J3 Pinouts(Payload data RS-232; Diagnostic data RS-232)  (Continued)
66 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01 10 IN Differential RXD+/RXA (Transmitted Data+)—Non-inverting receiver input. Accepts payload data from the connected device.11 IN -- FCC 6-18 Vdc version: DC Input (6-18 Vdc)— Supply Source must be capable of furnishing at least 7.5 watts.Non-FCC 3 Vdc version: Do not connect12 IN Differential RXD-/RXA (Transmitted Data-)—Inverting re-ceiver input.13 -- -- Reserved—Do not connect.14 OUT Differential TXD+/TXA (Received Data+)—Non-inverting driver output. Supplies received payload data to the connected device.15 IN -- Ground—Connects to ground (negative supply potential).16 OUT Differential TXD-/TXA (Received Data-)—Inverting driver output.Table 24. Transceiver Connector J3 Pinouts(Payload data RS-485; Diagnostic data RS-232)  (Continued)
MDS 05-xxxxA01, Rev.  01 TransNET OEM 2.4 Integration Guide 6715.0 dBm-Watts-Volts Conversion ChartTable 25 is provided as a convenience for determining the equivalent voltage or wattage of an RF power expressed in dBm with 50 Ohms load.Table 25. dBm-Watts-Volts Conversion ChartdBm V Po+53 100.0 200W+50 70.7 100W+49 64.0 80W+48 58.0 64W+47 50.0 50W+46 44.5 40W+45 40.0 32W+44 32.5 25W+43 32.0 20W+42 28.0 16W+41 26.2 12.5W+40 22.5 10W+39 20.0 8W+38 18.0 6.4W+37 16.0 5W+36 14.1 4W+35 12.5 3.2W+34 11.5 2.5W+33 10.0 2W+32 9.0 1.6W+31 8.0 1.25W+30 7.10 1.0W+29 6.40 800mW+28 5.80 640mW+27 5.00 500mW+26 4.45 400mW+25 4.00 320mW+24 3.55 250mW+23 3.20 200mW+22 2.80 160mW+21 2.52 125mW+20 2.25 100mW+19 2.00 80mW+18 1.80 64mW+17 1.60 50mW+16 1.41 40mW+15 1.25 32mW+14 1.15 25mW+13 1.00 20mW+12 .90 16mW+11 .80 12.5mW+10 .71 10mW+9 .64 8mW+8 .58 6.4mW+7 .500 5mW+6 .445 4mW+5 .400 3.2mW+4 .355 2.5mW+3 .320 2.0mW+2 .280 1.6mW+1 .252 1.25mWdBm V Po0 .225 1.0mW-1 .200 .80mW-2 .180 .64mW-3 .160 .50mW-4 .141 .40mW-5 .125 .32mW-6 .115 .25mW-7 .100 .20mW-8 .090 .16mW-9 .080 .125mW-10 .071 .10mW-11 .064-12 .058-13 .050-14 .045-15 .040-16 .0355dBm mV Po-17 31.5-18 28.5-19 25.1-20 22.5 .01mW-21 20.0-22 17.9-23 15.9-24 14.1-25 12.8-26 11.5-27 10.0-28 8.9-29 8.0-30 7.1 .001mW-31 6.25-32 5.8-33 5.0-34 4.5-35 4.0-36 3.5-37 3.2-38 2.85-39 2.5-40 2.25 .1µW-41 2.0-42 1.8-43 1.6-44 1.4-45 1.25-46 1.18-47 1.00-48 0.90dBm mV Po-49 0.80-50 0.71 .01µW-51 0.64-52 0.57-53 0.50-54 0.45-55 0.40-56 0.351-57 0.32-58 0.286-59 0.251-60 0.225 .001µW-61 0.200-62 0.180-63 0.160-64 0.141dBm µV Po-65 128-66 115-67 100-68 90-69 80-70 71 .1nW-71 65-72 58-73 50-74 45-75 40-76 35-77 32-78 29-79 25-80 22.5 .01nW-81 20.0-82 18.0-83 16.0-84 11.1-85 12.9-86 11.5-87 10.0-88 9.0-89 8.0-90 7.1 .001nW-91 6.1-92 5.75-93 5.0-94 4.5-95 4.0-96 3.51-97 3.2dBm µV Po-98 2.9-99 2.51-100 2.25 .1pW-101 2.0-102 1.8-103 1.6-104 1.41-105 1.27-106 1.18dBm nV Po-107 1000-108 900-109 800-110 710 .01pW-111 640-112 580-113 500-114 450-115 400-116 355-117 325-118 285-119 251-120 225.001pW-121 200-122 180-123 160-124 141-125 128-126 117-127 100-128 90-129 80 .1ƒW-130 71-131 61-132 58-133 50-134 45-135 40-136 35-137 33-138 29-139 25-140 23 .01ƒW
68 TransNET OEM 2.4 Integration Guide  MDS 05-xxxxA01, Rev.  01
IN CASE OF DIFFICULTY...MDS products are designed for long life and trouble-free operation. However, this equipment, as with all electronic equipment, may have an occasional component failure. The following information will assist you in the event that servicing becomes necessary.CUSTOMER ASSISTANCEAssistance for MDS products is available from our Customer Support Team during business hours (8:00 A.M.–5:30 P.M. Eastern Time). When calling, please give the complete model number of the radio, along with a description of the trouble/symptom(s) that you are experiencing. In many cases, problems can be resolved over the telephone, without the need for returning the unit to the factory. Please use one of the following means for product assistance:Phone: 585 241-5510  E-Mail: techsupport@microwavedata.comFAX: 585 242-8369 Web: www.microwavedata.comFACTORY SERVICEComponent level repair of radio equipment is not recommended in the field. Many components are installed using surface mount technology, which requires specialized training and equipment for proper servicing. For this reason, the equipment should be returned to the factory for any PC board repairs. The factory is best equipped to diagnose, repair and align your radio to its proper operating specifications.If return of the equipment is necessary, you will be issued a Service Request Order (SRO) number. The SRO number will help expedite the repair so that the equipment can be repaired and returned to you as quickly as possible. Please be sure to include the SRO number on the outside of the shipping box, and on any correspondence relating to the repair. No equipment will be accepted for repair without an SRO number.A statement should accompany the radio describing, in detail, the trouble symptom(s), and a description of any associated equipment normally connected to the radio. It is also important to include the name and telephone number of a person in your organization who can be contacted if additional information is required.The radio must be properly packed for return to the factory. The original ship-ping container and packaging materials should be used whenever possible. All factory returns should be addressed to:Microwave Data SystemsProduct Service Department(SRO No. XXXX)175 Science ParkwayRochester, NY 14620 USAWhen repairs have been completed, the equipment will be returned to you by the same shipping method used to send it to the factory. Please specify if you wish to make different shipping arrangements. To inquire about an in-process repair, you may contact our Product Services Group at 585-241-5540 (FAX: 585-242-8400), or via e-mail at ProductServices@microwavedata.com.
Microwave Data Systems Inc.Rochester, NY 14620General Business: +1 585 242-9600FAX: +1 585 242-9620Web: www.microwavedata.com175 Science ParkwayA product of Microwave Data Systems Inc.