EasyIO FW14 Building Automation System User Manual

EasyIO Holdings Pte. Ltd. Building Automation System Users Manual

Users Manual

EasyIOFW‐14–UserReference1EasyIOFW14UserReference
EasyIOFW‐14–UserReference2DocumentChangeLog26thDec2016 Documentcreated.
EasyIOFW‐14–UserReference3DisclaimerEasyIOFW‐14isaproductbyEasyIOHoldingsPteLtdTheEasyIOFW‐14wasbuiltontheSedonaFramework®.SedonaFrameworkisatrademarkofTridium,Inc.CPTToolisbyOnlineToolsInc.
EasyIOFW‐14–UserReference4Federal Communication Commission Interference Statement This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: • Reorient or relocate the receiving antenna. • Increase the separation between the equipment and receiver. • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. • Consult the dealer or an experienced radio/TV technician for help. Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this equipment. FCC Caution: This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. FCC Radiation Exposure Statement: This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body. RF Exposure: A distance of 20 cm shall be maintained between the antenna and users, and the transmitter module may not be co-located with any other transmitter or antenna.  
EasyIOFW‐14–UserReference5TableofContentsIntroduction ....................................................................................................................................................6HardwareConfigurations................................................................................................................................7PowersupplyConnection...........................................................................................................................7RS485Connection.......................................................................................................................................8JumpersConfigurations ..............................................................................................................................9Wiringdiagram .........................................................................................................................................10DigitalOutputWiringConnection ............................................................................................................11AnalogueInputConnection ......................................................................................................................12AnalogueOutputConnection ...................................................................................................................14WirelessNetwork..........................................................................................................................................15ButtonsandIndications ................................................................................................................................15LoginDetails..................................................................................................................................................17ChangingIPaddress......................................................................................................................................18Restorefactorysettings................................................................................................................................20TechnicalSupport .........................................................................................................................................21
EasyIOFW‐14–UserReference6IntroductionEasyIOFWSeriesisthemostpowerfulwirelessSedonacontrollerinthemarket.Itisequippedwithtwo32‐bitProcessors,thefirstintheAutomationindustry,witha580MHzMTKprocessorandanARMM0CortexfortheI/OmanagementandA‐Dprocessing,andalsowithaLinux3.18OSforpremiumperformance.SupportsBACnetasserverandTComorpremiumperformancewithNiagaraAXandN4.  TheBuildinbootloadercanbecarriedoutremotely.Nomoremanualservicebuttonneededisused. Firmwareupgradingcanbedoneremotelyandwithoutanyassistant. Firmwareupgradingisviaftpclient.Thisdocumentdescribeaboutbasicconnectionandtechnicalspecifications.  ItappliesforEasyIOFW‐14.         Item  FG‐32    DigitalOutput  2Channels   UniversalOutput  4Channels    UniversalInput  8Channels   TableshownaboveshowtheIOconfiguration
EasyIOFW‐14–UserReference7HardwareConfigurations PowersupplyConnection  BothACandDCcanbeusedforEasyIOFW‐14Seriescontroller.Refertoelectricalspecificationfortheworkingrange.Inordertoavoiddamageonthecontrollerinput/outputdevicesandRS485connection,useindividualpowersupplyforeachcontroller.IfasinglepowersupplyisusedtopowerupmultipleEasyIOFW‐14,makesurecontrollerpowersuppliesareconnectedwiththesamepolarity.   Electrical   Power Supply 24V AC +/- 5% or 24V DC +20%/-15%  Consumption 500 mA  Operating Temperature  32 to 150 Deg-F (0 to 65 Deg-C)  Storage Temperature -4 to 150 Deg-F (-20 to 65 Deg-C)  Operating Humidity 10% to 70% relative humidity non-condensing  PowerSupplyConnection  Multiplecontrollerssharesingletransformerconnection
EasyIOFW‐14–UserReference8RS485Connection  RS485connectionmustbeterminatedatbothendswithterminationresistor,typically120Ohms.Itisrecommendedtouseshieldedtwistedpairwire(STP)forthewiring. Lightningprotectioncircuitishighlyrecommendedtobeinstalledatoneendofthewiring.Thecontrollershouldbewiredindaisychainnetworktopologyasshownasimagebelow.Ifwirebranchcanbeavoided,keepitasshortaspossible,andneverconnectmorethanonedevicetothewirebranch(itisnotrecommended).  BecarefulifsinglepowersupplyisusedforallconnectedRS485device,makesurealldevicesarehavingthesamegroundconnection.Makesureyouareconnectingthesamewireforthesameterminalposition,all“H”terminalsconnectedtothesamewire.       Physical Interface  Remark            EIA-485   BUS A,B  Two Wire, Half Duplex Speed:(9.6K, 19.2k, 38.4K),          Data Bit:(8 bits),          Parity:(None)    Ethernet 10/100 Mbps  IP, TCP, UDP, ICMP, HTTP,FTP   Application Support  Sedona, BACnet MSTP Server and Tcom                            DaisyChainNetworkTopologyRS485ConnectionDiagram
EasyIOFW‐14–UserReference9JumpersConfigurations  BelowimageshowsthejumpersettingforUniversalInput,UniversalOutput,WatchdogandalsoEIA485120Ohmterminations. 
EasyIOFW‐14–UserReference10Wiringdiagram
EasyIOFW‐14–UserReference11DigitalOutputWiringConnection  EasyIOFW‐14Seriesdigitaloutputisforgeneralpurposeisolateddigitaloutputconnections(relayoutput).  Generalratingisasbelow(DirectDrive);   100VAC,0.5A 24VDC,2A PilotDutyratingisasbelow(PilotDuty);   24VAC,0.5A 24VDC,0.5ADigital Output 2 Channels Type Relay Contacts, SPST NO, 48VA at 24VAC,  Pilot Duty at 500mA max load.    Itdoesnotoutputvoltageorcurrent.Itisadryrelaycontact.                                   DigitalOutputConnection
EasyIOFW‐14–UserReference12AnalogueInputConnection  EasyIOFW‐14serieshasnon‐isolateduniversalinputs.Theuniversalinputsupportsthreetypeofanalogsignali.e.resistance,voltageandcurrenttransmitterviahardwarejumperandinternalregistersettings:  Universal Input 8 Channels  Voltage 0 - 10V DC (+/-0.005V) Resistance  500 - 500K (+/-10 Ohm) Thermistor 10K, 10K Shunt, 1K Balco, 1K Platinum : All (+/-0.01 Deg-C) UI as Digital Input  Voltage Free Contact   a) Resistance–Theworkingrangeofresistanceis500Ohm–500KOhms.IftheinputisconfiguredasThermistortype.ThecommonlyusedThermistorlike10K,10KwithShunt,1KBalcoand1KPlatinumareallsupportedb) Voltage–Supports0–10Vand0–5V(scalingrequired).Theminimuminputimpedanceofvoltagemodeinputis1MegaOhm.c) PulseInput–AllUniversalInputsarecapableofreceivinghighspeedpulse.Minimumontimepulseis20msandminimumofftimeis20ms.Approximately25Hz.Refertoimagebelow.
EasyIOFW‐14–UserReference13 UniversalInputasPulseInputspecifications,Max25HzMinimumOnperiod20msMinimumOffperiod20ms
EasyIOFW‐14–UserReference14AnalogueOutputConnection  EasyIOFW‐14serieshasUniversalOutputconnections.EachUniversalOutputcanbeconfiguredtodrivevoltageorcurrentoutputordigitaloutputviahardwarejumperandinternalregistersettings.  Theworkingrangeforvoltageis0–10V.      Universal Output  4 Channels    Type   Voltage: 0 – 10VDC , Min Impedance 1000 Ohm.              UniversalOutputConnectionforVoltageandCurrent
EasyIOFW‐14–UserReference15WirelessNetwork EasyIOFW‐14comeswithonboardwirelessconnection.ItcomplytoIEEE802.11standards.ItsupportsB/G/Nband.Eachunitissuppliedwithtwo(2)2dBifemaleSMAjackantenna.ButtonsandIndications  ThecontrollerwilldoahardwareresetwhentheResetButtonispressedwhenevermanualrestartisrequired.TheServicebuttonisusedtoactivatethebuilt‐inbootloaderprogramforsoftwareupgrade.EachdigitaloutputhasacorrespondenceLEDtoindicateitscurrentstate.                    ImageshowstheResetbutton,ServicebuttonandalsoTXRXindicators. ImageshownisanEasyIOFW‐14unit.
EasyIOFW‐14–UserReference16   ImageshowstheStatusindicator,ErrorindicatorandindividualDigitalOutputindicatorButtonandLEDindications.ImageshownisanEasyIOFW‐14.                         LED Conditions Description                         Pattern: continuously blinking.  ERR is to indicate whenever there is   1    ERR Communication errors.  Pattern: constantly light up.  The controller is undergoing firmware upgrading. This is normal during firmware upgrade process.                      STS is used to indicate the heartbeat of the      Microcontroller. The STS LED will blink at   2      STS             1-second interval in normal operation          Condition.                     TXRX is used to indicate when there are      Communication activities in Port 1.   3     TX/RX             (Transmitting or Receiving) on the          Communication port.              
EasyIOFW‐14–UserReference17LoginDetails  EasyIOFW‐14Seriesdetailsareasbelow.  DefaultIPaddress :192.168.10.14 DefaultSubnet  :255.255.255.0 DefaultGateway :192.168.10.1  Note:  Inordertologin,thehostPC(laptop)hastobeinthesamesubnet.Example:  IPaddress:192.168.10.123 Subnet :255.255.255.0 SedonaLoginviaCPT  Username :admin  Password :<nopassword>   
EasyIOFW‐14–UserReference18ChangingIPaddress BydefaulttheEasyIOFW‐14seriescontrollerIPaddressis192.168.10.14. ChangingtheIPaddresscanonlybedoneviaCPTTool.  Step1  LogintotheFW‐14viaSedonaworkbench.Locatetheobject“IP”undertheSedonaservicefolder.          Step2 Gointothepropertysheetofthe“IP”object.                    CurrentIPaddressthatisassigntothecontroller NewIPaddressfield.KeyintherequiredIPaddressinthesefields.MakesuretheIPaddressandsubnetiscorrectbeforesaving
EasyIOFW‐14–UserReference19Step3 SavetheSedonaappsandcyclepower. Step4  ReconnecttothecontrollerviaSedonaworkbenchusingthenewconfiguredIPaddress.
EasyIOFW‐14–UserReference20 Restorefactorysettings  Thisfunctionisdonewithjustthebypressingthe“Service”buttonwhilethecontrollerisbootingup.  Arestoretofactorysettingswilldothefollowing;  1. RestoretheIPaddresstothedefaultwhichis192.168.10.142. CleartheSedonaapplicationintheSedonaVMbacktodefault(defaultappisanemptyapp)3. AdefaultSedonaappsdefaultloginisadmin,<nopassword>. Followthestepsbelowtorestoretofactorysettings.  Step1  MakesureyoubackuptheSedonaappsifyouhaveconnectiontotheEasyIOFW‐14.  Step2  Cyclepowerandwithin5secondspressandHOLDdowntheservicebuttonuntiltheErrorLEDstartstoflash.  Thisprocesswilltakeapproximately10secondsbeforetheerrorLedstarttoblink.                       Step3  OncetheRedLEDflashes,amomentarypressoftheservicebuttonwillrestorebacktheFW‐14controllerbacktofactorydefaultstate.
EasyIOFW‐14–UserReference21TechnicalSupportFortechnicalissue,pleasecontactEmail:support@easyio.com