EA Technology UTP2A UltraTEV Plus2 User Manual EA Technology Report

EA Technology Limited UltraTEV Plus2 EA Technology Report

Contents

Users manual

    UltraTEV Plus2 Operating Manual     Product Code: UTP2 Version: 8 Date: March 2018
EA Technology UltraTEV Plus2 Operating Manual    2388L018    Contents FCC Warning Statement ........................................................................................................................................................... 1 IC Warning Statement ............................................................................................................................................................... 1 1. What does the UltraTEV Plus² do? ...................................................................................................................... 2 2. What’s in the Box? ........................................................................................................................................................ 3 3. Important Information .............................................................................................................................................. 4 4. Non-Intrusive Detection of Partial Discharge Activity ........................................................................... 5 4.1 What is Partial Discharge? ................................................................................................. 5 4.2 How can Partial Discharge be detected? .......................................................................... 5 4.3 Airborne Ultrasonic Discharge Activity ............................................................................ 5 4.4 Electromagnetic Discharge Activity .................................................................................. 6 4.5 Cable Partial Discharge Activity ........................................................................................ 6 5. Using the UltraTEV Plus² .......................................................................................................................................... 7 5.1 Charging the UltraTEV Plus2 .............................................................................................. 8 5.2 Turning the UltraTEV Plus² On/Off ................................................................................... 9 5.3 Self-Test .............................................................................................................................. 9 5.4 Notification Bar .................................................................................................................. 9 5.4.1 Temperature & Humidity ..................................................................................... 10 5.5 Menu Bar ........................................................................................................................... 11 5.6 Main Menu ........................................................................................................................ 12 5.7 TEV/Cable PD Menu ......................................................................................................... 13 5.7.1 Measure Screen .................................................................................................... 13 5.7.2 Phase Plot ............................................................................................................. 14 5.7.3 Waveform .............................................................................................................. 16 5.7.4 Histogram ............................................................................................................. 17 5.7.5 Interpretation ....................................................................................................... 18 5.8 Ultrasonic Screen ............................................................................................................. 20 5.8.1 Ultrasonic classification ....................................................................................... 21 5.9 Context Menu ................................................................................................................... 22 5.9.1 Audio output ........................................................................................................ 22 5.9.2 Filters .................................................................................................................... 23 5.9.3 Phase Reference ................................................................................................... 23 5.10 Settings Screen................................................................................................................. 26 5.10.1 System Settings .................................................................................................... 26 5.10.2 Measurement Settings ......................................................................................... 28 5.10.3 Wireless Settings .................................................................................................. 29 5.10.4 About .................................................................................................................... 30 5.10.5 In-field Firmware Upgrade ................................................................................... 31 5.10.6 Reset All Settings ................................................................................................. 33 5.11 File Browser ...................................................................................................................... 34 5.12 Screenshot ........................................................................................................................ 35 5.13 Function Check ................................................................................................................ 37 6. NFC Functionality ...................................................................................................................................................... 38 6.1 NFC Tag Installation ........................................................................................................ 38 6.2 Substation Tag ................................................................................................................. 39 6.3 Writing to a Substation Tag ............................................................................................ 39 6.4 Reading a Substation Tag ............................................................................................... 40
EA Technology UltraTEV Plus2 Operating Manual    2388L018    6.5 Asset Tag .......................................................................................................................... 40 6.6 Writing to an Asset Tag ................................................................................................... 41 6.7 Reading an Asset Tag ...................................................................................................... 42 6.8 Reading an NFC Tag from the Main Menu ..................................................................... 42 6.9 NFC Tag Trouble Shooting .............................................................................................. 43 7. Survey ............................................................................................................................................................................... 44 7.1 Create a Workflow using the Workflow Generator ........................................................ 44 7.2 Starting a Survey .............................................................................................................. 46 7.3 Select Workflow ................................................................................................................ 47 7.4 Skip Workflow .................................................................................................................. 49 7.5 Ad-hoc Measurement ....................................................................................................... 49 7.6 Survey Metadata Forms ................................................................................................... 49 7.7 Using Populated Lists ...................................................................................................... 52 7.8 Using the virtual keyboard .............................................................................................. 52 7.9 Background Measurements ............................................................................................. 53 7.10 Recording Data ................................................................................................................ 54 7.10.1 TEV recorded data ................................................................................................ 54 7.10.2 Cable PD recorded data ....................................................................................... 54 7.10.3 Ultrasonic recorded data ..................................................................................... 54 7.11 Viewing Survey Progress ................................................................................................. 55 7.12 Adding Media to a Survey ............................................................................................... 56 7.13 Completing a Survey ........................................................................................................ 56 8. Reviewing Results ..................................................................................................................................................... 57 8.1 Hotspot Connection ......................................................................................................... 57 8.2 Wi-Fi Connection .............................................................................................................. 58 8.3 USB Connection (Windows PC only) ................................................................................ 58 8.4 MicroSD Card & Data Zip Files ........................................................................................ 59 8.5 Data Analysis Screens ...................................................................................................... 59 8.5.1 TEV & Cable PD Analysis Screen ......................................................................... 60 8.5.2 Ultrasonic Analysis ............................................................................................... 62 9. Detecting Partial Discharge using the UltraTEV Plus² ........................................................................ 63 9.1 TEV Measurement ............................................................................................................ 63 9.1.1 Background Noise ................................................................................................ 63 9.1.2 Measuring TEV ..................................................................................................... 64 9.2 Cable PD Measurement ................................................................................................... 65 9.2.1 Practical RFCT Connection Requirements .......................................................... 65 9.2.2 Measuring PD in cables ....................................................................................... 65 9.3 Ultrasonic Measurement ................................................................................................. 66 9.3.1 Measuring Ultrasonic ........................................................................................... 66 9.3.2 Measuring Ultrasonic with the UltraDish............................................................ 67 9.3.3 Measuring Ultrasonic using the Flexible Sensor ................................................ 68 9.3.4 Ultrasonic Measurement using the Contact Probe Accessory .......................... 69 9.3.5 Using the Ultrasonic Contact Probe .................................................................... 70 9.3.6 Detection, Measurement and Localisation of the Partial Discharge ................ 71 9.3.7 Mounting Practices .............................................................................................. 71 9.3.8 Sources of Noise and Phantom Signals .............................................................. 73 10. UltraTEV Plus² Specification ............................................................................................................................... 74 TEV Measurements .......................................................................................................... 74 Ultrasonic Measurements ................................................................................................ 74 Cable PD Measurements .................................................................................................. 74 Hardware .......................................................................................................................... 75
EA Technology UltraTEV Plus2 Operating Manual    2388L018    Environmental .................................................................................................................. 75 Dimensions ...................................................................................................................... 75 Power Supplies ................................................................................................................. 75 Battery Charger ................................................................................................................ 76 11. Declaration of Conformity ................................................................................................................................... 77 12. Maintenance ................................................................................................................................................................. 78 13. Warranty Policy ........................................................................................................................................................... 78 14. Calibration ..................................................................................................................................................................... 79 15. Repair ............................................................................................................................................................................... 79 16. Waste Electrical and Electronic Equipment Directive (WEEE) .......................................................... 79 17. Continuous Improvement .................................................................................................................................... 79 18. Contact Us ..................................................................................................................................................................... 80 19. Record of Changes ................................................................................................................................................... 81
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 1 of 82 FCC Warning Statement · This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. · This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. End users must follow the specific operating instructions for satisfying RF exposure compliance. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter. · Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment IC Warning Statement Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication. This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 2 of 82 1. What does the UltraTEV Plus² do? The UltraTEV Plus² is a versatile hand-held tool used to easily detect and classify  Partial Discharge (PD) in a wide range of electrical equipment.  The  UltraTEV  Plus²  uses  inbuilt  TEV  and  Ultrasonic  sensors  and  external  accessories  to detect the presence of potentially  damaging PD in switchgear, cables and overhead line equipment.  The UltraTEV Plus² brings together three complementary sensor modes in a single hand held instrument by regularly checking switchgear while it’s in service.  Using the UltraTEV Plus2,  failure  risks  can  be  identified  and  action  taken  to  avoid  faults  and  downtime.   Algorithms  and  analysis  capability  built  in  to  the  UltraTEV  Plus²  provide  vital  insight, classifying what you find to support the decisions you make and deliver the outcomes you need.  It’s never been simpler to interpret what you’re seeing and choose a course of action. The UltraTEV Plus² records measurements at the touch of a button. Internal storage can be used to provide access to historical data while you’re out in the field. Capturing what you’ve measured allows you to see trends in the performance of your network.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 3 of 82 2. What’s in the Box? Part Kit 1 Kit 2 Kit 3 Kit 2 Upgrade Kit 3 Upgrade UltraTEV Plus2      Mains Charger      Car Charger      USB Lead      8GB MicroSD & SD adapter      Environmental Sensor      Stylus x 2      NFC Starter Pack      Neckband Headphones       Ultrasonic Contact Probe      Flexible Microphone Sensor      UltraDish      RFCT & Cable      Tough Carry Case X (T-Loc II) X (T-Loc II) X (T-Loc IV) X (T-Loc II) X (T-Loc IV) For Spares and Accessories  For spares and accessories, please contact your local sales representative or sales@eatechnology.com
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 4 of 82 3. Important Information  • The UltraTEV Plus2 is designed for use at ground potential only.  • When testing electrical plant ensure that the metalwork is earthed before taking any measurements.  • Maintain safety clearances between structures at high voltage and the instrument, its probes and the operator at all times.  • RFCTs,  connecting  leads  and  test  equipment  do  not  provide protection against high voltage.  • Under  no  circumstances  are  earth/ground  connections  to  be loosened,  disconnected  or  otherwise  altered  to  allow  use  of  this equipment.  • Adhere strictly to local safety procedures.  • Do not make measurements when there are electrical storms in the vicinity.  • Do not make measurements immediately following the energisation of a circuit.  • Do not disturb plant during measurements either mechanically (e.g. by shaking or striking it), electrically (e.g. by increasing the voltage) or physically (e.g. by applying heat).  • Do  not  operate the  instrument  or  its  accessories  in  an  explosive atmosphere.  • Mains supply voltages are present within the battery charger.  • This  unit  contains no  user  serviceable  parts,  always  return  to  EA Technology or your local distributor for service and repair.  • Care must be taken where work is performed in tight corners, where the  proximity  of  other  earth  planes  will  affect  the  reading.  If possible maintain a distance of more than 30cm from metal work which runs perpendicular to the sensor faceplate.   For application information please contact: product-support@eatechnology.com
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 5 of 82 4. Non-Intrusive Detection of Partial Discharge Activity 4.1 What is Partial Discharge? Partial  discharges are  electrical  discharges that  do  not  completely  bridge the  insulation between electrodes.  The  magnitude of these  discharges is  usually small,  however they cause progressive deterioration of insulation that may eventually lead to failure. Non-intrusive partial discharge detection provides a means for identifying these potential sources of insulation failure. If not detected the discharge may result in failure causing not only in loss of supply to customers and damage to plant but could also endanger staff. 4.2 How can Partial Discharge be detected? A partial discharge emits energy in various ways and produces a number of effects which can be detected: Electromagnetic: • Radio • Light • Heat  Acoustic: • Audio • Ultrasonic  Gases: • Ozone • Nitrous oxides  The most practical techniques for non-intrusive testing are based on the detection of the radio  frequency  part  of  the  electromagnetic  spectrum  and  ultrasonic  emissions.    The UltraTEV Plus2  has  specifically  been developed to  enable  electromagnetic  and  ultrasonic activity to be detected in a single simple to use instrument. 4.3 Airborne Ultrasonic Discharge Activity Acoustic emissions from partial discharge activity occur over the whole acoustic spectrum.  Audible detection is possible but depends on the hearing ability of the individual.  Using an  instrument  to  detect  the  ultrasonic  part  of  the  acoustic  spectrum  has  several advantages;  instruments  are  more  sensitive  than  the  human  ear,  are  not  operator dependent and are more directional when operating above the audible frequency.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 6 of 82 The most sensitive method of detection is using an airborne ultrasonic Microphone centred at 40 kHz.  This method is very successful at detecting partial discharge activity provided there is an air passage between the source and the Microphone.   4.4 Electromagnetic Discharge Activity When  partial  discharge  activity  occurs  within  high  voltage  switchgear,  it  generates electromagnetic waves in the radio frequency range which can only escape from the inside of the switchgear through openings in the metal casing.  These openings may be air gaps around  covers,  or  gaskets,  or  other  insulating  components.    When  the  electromagnetic wave propagates outside the switchgear, it produces a Transient Earth Voltage (TEV) on the metal casing of the switchgear. The Transient Earth Voltage (TEV) is only a few millivolts, of  short  duration  having  a  rise  time  of  a  few  nanoseconds  and  can  be  detected  non-intrusively  by  placing  a  TEV  probe  on  the  outside  of  the  earthed  switchgear  whilst  the switchgear is in service. 4.5 Cable Partial Discharge Activity When a  partial discharge event occurs in a cable, there will be a resulting current pulse coupled onto the earthed sheath of the cable. These pulses will propagate away from the discharge site in both directions. Once the pulse reaches a change in impedance at a cable joint or termination, a partial reflection occurs. This results in the pulses travelling back down the  cable  several times  (depending on the  cable  length)  as  they  decay  away.  The current  pulses  can  be  detected  non-intrusively  using  a  Radio  Frequency  Current Transformer (RFCT) sensor placed around the cable earth strap.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 7 of 82 5. Using the UltraTEV Plus²                                  Smart Accessory Port Right Button Middle Button Left Button Home Button Photo Sensor microSD card slot LED charging indicator Audio out/headphone socket Ultrasonic Accessory Port Micro USB charging port Ultrasonic Microphone TEV sensor Lanyard loop
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 8 of 82 5.1 Charging the UltraTEV Plus2              UltraTEV Plus² is charging UltraTEV Plus² is fully charged   For  the  quickest  charging  time,  turn  off  the  UltraTEV  Plus2  instrument during charging. Charging time is extended when connected to a USB port compared to the mains charger.    The  TEV/Cable  PD  and  Ultrasonic  measuring  features  are  automatically disabled when the instrument is being charged. A fully-charged battery should provide approximately 6 hours of continuous use  while  switched  on  and  measuring.    For  practical  purposes,  a  fully charged battery should last a full day of surveying. The UltraTEV Plus² needs to have sufficient charge to remain powered on while viewing data through a USB port. A laptop USB port may not provide enough power to charge the UltraTEV Plus² and view data simultaneously.   Micro USB charging port Use the supplied USB cable to charge the UltraTEV  Plus²  with  the  mains  charger, in-car  charger  or  from  a  standard  USB port.  Battery Level Indicator Charging
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 9 of 82  5.2 Turning the UltraTEV Plus² On/Off Power on  press and hold   for 1 second Power off  press and hold   for 2 seconds 5.3 Self-Test During power up the UltraTEV Plus2  performs a self-test on TEV, ultrasonic and Cable PD using the inbuilt test sources.  The self-test is not a calibration check.   If self-test consistently fails, contact Product-support@eatechnology.com  5.4 Notification Bar      Below are other icons that could appear on the notification bar:  This icon indicates that the current audio source is TEV  This icon indicates that the current audio source is Ultrasonic  This icon indicates that the current audio source is the RFCT   This icon shows when a UltraDish has been connected to the UltraTEV Plus²  This icon shows when a RFCT has been connected to the UltraTEV Plus² Battery Level Indicator Temperature & Relative Humidity Audio Source Time Phase Reference
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 10 of 82  This icon shows when a Contact Probe has been connected to the UltraTEV Plus²  This icon shows when a Flexible Sensor has been connected to the UltraTEV Plus    This icon shows when the UltraTEV Plus² is charging  This icon is used to show when a Wi-Fi connection has been established 5.4.1 Temperature & Humidity The temperature and relative humidity  reading  is  displayed on the notification  bar only after connection of the Environmental Sensor.  The Environmental Sensor pictured below is connected to the Smart Accessory Port on the left hand side of the instrument. The connection of the accessory automatically starts the data collection with the latest reading being displayed in the notification bar at the top left of the screen.   In  order  to  allow  use  of  other  optional  accessories  whilst  still  displaying  a  reference temperature, the final reading on removal of the sensor is persisted. Additional brackets around the measurement demonstrate that this is a historic reading.     Wait for the temperature and humidity reading to settle.  This may take a while if it has been stored in very high or low temperatures.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 11 of 82 5.5 Menu Bar The menu bar is located at the bottom of the screen. It displays icons that correlate to the Left, Middle and Right Buttons. The icons on the Menu bar  change depending on  which mode the UltraTEV Plus2 is in.        The Left button    , Middle Button  and Right Button   can be pressed to select the Main menu buttons respectively
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 12 of 82 5.6 Main Menu After powering up, the UltraTEV Plus2 will load up to the Main Menu as shown below.         The Home Button   can be used to navigate back to the Main Menu at any time. The TEV icon on the main screen will change to a Cable PD icon  when a RFCT accessory is plugged in.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 13 of 82 5.7 TEV/Cable PD Menu The TEV/Cable PD screen, selected via the top left icon on the Main Menu contains different modes which can be used for the PD measurement. The locator modes require additional locator probe accessory.  The Interpretation option is only applicable when in TEV mode      5.7.1 Measure Screen The Measure mode is common to both TEV and Cable PD. This mode displays TEV readings in dBmV (dB) or (if the RFCT accessory is connected) Cable PD readings in picoCoulombs (pC).  To enter this mode, click the Measure icon .
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 14 of 82     • P/Cycle – Shows the pulses per cycle based on either a 50 or 60Hz mains frequency. • Severity – Shows the short term severity (calculated by multiplying TEV magnitude (mV) by Pulses Per Cycle). When in Cable PD mode, this is calculated by Charge (pC) multiplied by Pulses Per Cycle. • Max dB – displays the maximum dB value registered by the UltraTEV Plus2 since the screen was entered or paused/reset. This value is displayed in pC. • Chart - The bar chart is used to show the amplitude of the current values being read by the UltraTEV Plus2, from right to left. • Noise Level – This displays the amplitude in dB of the background noise level.  To exit the TEV screen back to the main menu, press the Home button  . There is an option to record a reading, this can be done by either clicking the red record icon on the screen   or by pressing the Middle button  . All recordings are stored within a ‘survey’ detailed in a later section of this manual.  Pausing a reading can also be achieved by either presing the Right button or clicking on the ‘Pause’   icon. Audio output is also muted during a pause operation.  After pausing the screen the measurment can be restarted by pressing the restart button. 5.7.2 Phase Plot The Phase Plot mode is common to both TEV and Cable PD. The upper section of the screen shows measurement values as detailed previously under the ‘Measure Screen’. The lower section contains a phase resolved intensity plot ‘Phase Plot’ of the measured activity.  The  plot  displays  either  TEV  or  Cable  PD  events’  phase  angles  (x-axis)  against  their amplitude (y-axis). The colour scale represents the intensity (pulse count) at a given phase angle and amplitude.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 15 of 82 This  option  is  useful  for  distinguishing  between  whether  a  measured  PD  activity  is  a genuine discharge source or  just  noise.  For  example, genuine  PD  activity may  manifest itself as a stable phase resolved plot which will occur at the same position with respect to phase angle cycle by cycle; whilst white noise will not be phase related occurring at irregular positions on the phase plot.        The Pause and Record option is also available in this mode; Severity, Noise Level and P/Cycle are calculated as described under the Measure Screen   To zoom in on a chart, slide your finger from bottom left to top right of the area of interest. To zoom out draw a diagonal line from top right to bottom left.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 16 of 82 5.7.3 Waveform The ‘Waveform’ mode is common to both TEV and Cable PD. When in Cable PD mode, values will be displayed in mA, whilst in TEV mode they will be measured in dBmV as below.  To enter this mode, click the Waveform icon   .  This mode displays a plot of a TEV or Cable PD activity as a function of time allowing an instantaneous view of an activity’s amplitude with respect to time. This option can be used to assist in distinguishing between genuine PD activity and noise. A Partial Discharge pulse will normally manifest as a sharp fast rising edge pulse whilst noise is often slower and less repeatable.        The Pause and Record option is  also available in this mode as described under the Measure Screen
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 17 of 82 5.7.4 Histogram This option (shown below)  displays the number of  events  registered (y-axis)  for  a given amplitude (x-axis).  This measurement option is useful for determining if more than one discharge source is present; two distinct groups of bars on this chart could mean there are two sources of discharge at the respective dB (or pC) levels.  The screen is also useful in positively identifying a genuine source of PD and assessing its pulse rate when there is a high pulse rate noise floor affecting the standard pulse per cycle calculation.         The Pause and Record option is also available in this mode; Severity, Noise level  and P/Cycle are calculated and as described under the Measure Screen
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 18 of 82 5.7.5 Interpretation The ‘Interpretation’ mode available for TEV readings only.  To enter this mode, click the Interpretation icon  . The interpretation screen provides a first pass summary of the switchgear’s condition by taking into account both the magnitude and repetition rate of any detected pulses. The guide distinguishes between noise, surface tracking and internal discharge providing an indication of the suggested action.    This  display  is  an  easy  to  use  software  implementation  of  the  TEV  measurement interpretation guide produced by EA Technology using decades of experience. The original summary document giving an overview of the original guidelines for the interpretation of TEV measurements is included on the next page.   The Interpretation screen is only available when in TEV mode
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 19 of 82
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 20 of 82 5.8 Ultrasonic Screen The Ultrasonic screen shows measurements taken using either the inbuilt Ultrasonic sensor or  the  external  Ultrasonic  sensors  (Contact  Probe,  Flexible  Sensor  or  UltraDish)  if connected.     Ultrasonic magnitude is measured in dBµV and is displayed on the chart as phase angle (x-axis) against amplitude (y-axis). The colour chart represents a key to show the intensity (pulse count) at a given amplitude and phase angle.  This phase resolved plot can be used to further confirm the presence of a partial discharge activity. In general PD activity will be displayed as a stable area which will occur at the same to phase angle each cycle; whilst noise tends to be out of phase and occurs at irregular positions on the phase plot.   The Pause and Record option is  also available in this mode as described under the Measure Screen
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 21 of 82 5.8.1 Ultrasonic classification The  Ultrasonic  display  on  the  UltraTEV  Plus²  includes  the  output  of  EA  Technology’s proprietary  ultrasonic  classification  algorithm.  The  algorithm  processes  measured ultrasonic data in real time to give an indication whether the input data is a background noise source or partial discharge activity.  The algorithm processes the  data from the ultrasonic  Microphone along with the phase reference  signal,  and  looks  for  patterns  within  the  data  stream  which  experts  at  EA Technology have identified as typical indicators of partial discharge.        The ultrasonic classification will not be displayed if the phase lock has not been achieved.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 22 of 82 5.9 Context Menu Pressing the Left Button whilst in TEV, Cable PD or Ultrasonic modes brings up the Context Menu as shown below. The Context Menu consists of a number of items with only those relevant to the current mode of operation visible at any time. This mode allows commonly used settings to be modified from within the measurement screen.    5.9.1 Audio output The UltraTEV Plus² allows audio output of either Ultrasonic, TEV or Cable PD (dependent on whether RFCT is connected or not) activity through the connection of external headphones. The audio context menu allows control of the headphone output.  To modify the current audio settings click on the Audio icon . Within this sub menu the audio output (TEV, Cable PD or Ultrasonic) can be selected, note this selection will persist across modes.  To turn off the  audio output toggle the  Mute  Button, the toggle icon  will turn green to indicate the Mute mode has been activated. The volume of the audio output can also be modified by adjusting the slider to the desired level as shown above.  The Context Menu contents is context specific; its contents will differ for each measurement mode
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 23 of 82 5.9.2 Filters  Select the filter icon   to change the filter properties; this option is only enabled when in  Cable  PD  Measurement  Mode  and  enables  noise  to  be  filtered  from  the  cable  PD measurement.    Select the desired filter properties, a tick should appear when a selection has been (shown above). • No Filter – This option passes all frequency types.  • 500 kHz High Pass – This option activates a high pass filter that passes all frequencies from 500kHz and above.  • 1.8 MHz High Pass – This option activates a high pass filter that passes all frequencies from 1.8 MHz and above.  5.9.3 Phase Reference  Select the   icon on the context menu to access the phase reference settings page. This allows the  source of the phase reference for  the UltraTEV Plus² to  be  selected from the following options: • Photo – This option selects the Photo-sensor located on the front upper section of the UltraTEV Plus² as the source of the Phase reference. The Photo-sensor requires line of sight to a mains frequency light source such as a fluorescent fitting.   • E field – This option selects the in-built E-field sensor as the source of Phase reference. The sensor detects the phase reference from the stray electric field within the substation.  • Manual – Allows the user to manually adjust the phase reference.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 24 of 82   The current status of the phase reference is indicated by the colour of the phase readout.   A white phase display indicates a phase lock has been achieved.  A red phase display indicates that a  phase  lock  has  not  been achieved.  A  continous  red  phase display  would  neccesitate  the change of mode.    An amber phase display indicates that  the  frequency  has  been  set manually.  When in  Manual Mode the Right   and Left   buttons can be used to increase or decrease the  phase  reference  respectively.  Once  the  desired  value  has  been  reached,  press  the middle button   to store as shown below.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 25 of 82   During a data capture the UltraTEV Plus² monitors the phase lock to ensure a continuous sync is achieved. If the phase lock is lost at any time during a capture the unit displays a warning message on completion of the recording. Every attempt should be made to ensure a phase lock is present as the lack of this may affect the analysis of the data captured.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 26 of 82 5.10 Settings Screen To access the settings page, click the Settings icon    on the Main Menu and the screen shown below will be displayed.   5.10.1 System Settings  • Key Beep – allows the turning ON/OFF of the audible beeps when any of the buttons are pressed and when a NFC tag is detected. The button toggles to a green colour when Key Beep is activated.   • Display Brightness – click on this to change the intensity of the backlight.   Keeping the backlight to a minimal level will improve battery life
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 27 of 82 • Language – select this option to change the UltraTEV Plus² display language.   • Time/Date – select this option to change the Time and Date settings on the   UltraTEV Plus². The time zone can also be changed here as shown below.    • Auto Shutdown – this option can be used to Enable/Disable the Auto shutdown feature of the UltraTEV Plus². After a defined period of push button inactivity, the UltraTEV Plus² will display a warning message and then proceed to shut itself down to conserve power. The inactivity period can also be changed here as shown below.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 28 of 82 5.10.2 Measurement Settings The Alarm Mode can be toggled on and off in this option. When the Alarm mode is activated, the inbuilt beeper of the UltraTEV Plus² will be activated whenever the set Red threshold level has been exceeded. In addition to this, threshold levels (Red and Amber levels) for the various measurement features of the UltraTEV Plus² can be modified here together with the line frequency.    The Ultrasonic only contains a Red Level threshold setting
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 29 of 82 5.10.3 Wireless Settings This section allows the setting of the Wi-Fi & NFC features of the UltraTEV Plus².    The NFC is enabled system wide by sliding the toggle switch to green. Once active the NFC features can be accessed through the survey and measurement screens.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 30 of 82 The Wi-Fi functionality can be switched on/off using the toggle button shown above. Select ‘Network Connect’ above to connect it to a Wi-Fi network.     Using the on-screen keyboard, enter the Wi-Fi password and then the Middle Button   to save the network.  The connection status of the UltraTEV Plus² can be viewed by selecting ‘Network Status’. 5.10.4 About The about screen displays  a  summary of the UltraTEV Plus² components including  both hardware  and  software  version  numbers.  The  display  also  provides  details  of  EA Technology’s dedicated Product Support team should any further information be required.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 31 of 82    5.10.5 In-field Firmware Upgrade Through the ‘About’ screen, the firmware of the UltraTEV Plus² can be updated. To access the firmware update screen press the update icon .  The UltraTEV Plus² can be updated in the field from an update file loaded onto the MicroSD card. Please check with Product Support for any available update files. To use this feature the image will initially need to be copied from the distribution media to the ‘updates’ folder on the  MicroSD card. An SD to  MicroSD adapter is  supplied for use  with laptops or PCs which have an in built SD card reader.  To install a firmware update from the MicroSD card, press the “Check MicroSD for Update” button on the above screen. The MicroSD card will be checked for any available updates, and details populated on the display as shown below. To install the update found, press the tick icon on the right of the menu bar and await the process to complete.  An update can only be installed if the instrument is plugged into the mains charger to avoid any unwanted shutdown due to low battery whilst performing the update process. Once installed, the instrument must be restarted to run the latest update.  To book the UltraTEV Plus² in for calibration ahead of its recommended due date, please contact Product support : Email: product-support@eatechnology.com  Tel: +44 (0)151 347 2293
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 32 of 82      To  check  you  have  the  most  current  software  version  or  if  you  need assistance in updating your instrument, please contact product support
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 33 of 82 5.10.6 Reset All Settings This  option  can  be  used  to  reset  the  UltraTEV  Plus²  back  to  the  default  settings.  Upon pressing the option a notification will appear asking for the action to be confirmed.     Once confirmed the follow settings will be reset back to their default state: • Key Beep Enable • Display Brightness • Language • Auto Shutdown Enable • Auto Shutdown Time • Line Frequency  • TEV Red and Amber Measurement Thresholds • Ultrasonic Red Threshold • Cable PD Thresholds  • Wi-Fi enable  Any Wi-Fi networks previously connected to and their login credentials will be preserved, and will not be cleared with the above.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 34 of 82 5.11 File Browser The File Browser screen can be used to manage files and folders stored on the UltraTEV Plus²’s microSD card. To access the file browser, click File icon   on the Home screen.   Upon  opening  the  File  Browser,  the  contents  at  the  root  of  the  memory  card  will  be displayed.  Selecting  a  folder,  represented  by  the  folder  icon  ,  will  cause  it  to  be highlighted within the File Browser. The contents of the folder can then be displayed by pressing the   icon  or the  physical button below  it  on the  instrument.  A  folder can be deleted by pressing the   icon or the physical button below it.  Selecting a folder, represented by the file icon  , will cause it to be highlighted within the File Browser. Information regarding the file such as size, date modified and time modified can  then  be  displayed  by  pressing  the   icon  or  the  physical  button  below  it  on  the instrument. A file can be deleted by pressing the   icon or the physical button below it.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 35 of 82 5.12 Screenshot The UltraTEV Plus² allows the user to capture an image of the screen at any time. To initiate a capture press both the left and right hand buttons simultaneously for two seconds.    Once  capture  completes  a  pop  up  window  will  appear  giving  a  preview  of  the  screen capture. This preview can either be rejected by pressing cancel which discards the image and returns to normal operations or accepted which will move onto the file naming screen.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 36 of 82 The file name screen provides the opportunity to rename the file from the default as shown below. Selecting the tick in the bottom left hand corner of the image stores the file to the removable microSD Card. The files are stored at \data and can be verified through the file browser    The screen shot image can be viewed by removing the SD card and inserting in to a PC or similar device and navigating to \data and opening the relevant .png file, or by connecting to the UltraTEV Plus² interface.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 37 of 82 5.13 Function Check The UltraTEV Plus²’s function checker is designed to allow users to verify the functionality of their instrument using in built test sources. The Function Check display option can be used to toggle these inbuilt test sources. To launch the Function Check display, press the Function Check icon   on the Home screen.   To test  a given  function, for example, the  TEV  function, toggle on the  TEV  test  source. Navigate  to  any  of  the  TEV  measurement  displays  which  should  display  TEV  activity. Multiple test sources can also be toggled and checked.        Please note that this option is not in any form a calibration check.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 38 of 82 6. NFC Functionality The UltraTEV Plus² has a built-in NFC tag reader/writer that can program the tags when they are used for the first time and recall the information during a survey. 6.1 NFC Tag Installation • NFC tags are not designed for outdoor installation • NFC tags are designed to work on metal surfaces • Clean the surface with alcohol prior to installation • Install in a convenient place where the UltraTEV Plus² can be held in contact with the NFC tag while the display is observed  NFC functionality is enabled by default.  To turn off the NFC function, go to Main Menu, Settings, Wireless Settings.         The NFC tag reader antenna is located behind the CE mark. When taking a reading, align the centre button with the NFC tag.    Blank NFC tags are  identical and can  be  programmed  with substation or asset information.  There is a space on the tag to write ‘asset’, ‘substation’ or other information.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 39 of 82 6.2 Substation Tag Use one NFC tag per substation to hold all the information relative to the substation being surveyed.  This tag can be installed anywhere in the substation The following information is stored: Substation Name    (up to 127 characters) Substation type    (Indoor, outdoor, cabinet, other) Switchgear Manufacturer  (up to 127 characters) Switchgear Type    (up to 127 characters) Installation Date    (Day, Month, Year) Rated Voltage    (In KV) Operating Voltage    (in KV) Busbar Insulation Type  (Unknown, Air, Oil, Compound, SF6, Paper, XLPE, EPR) 6.3 Writing to a Substation Tag From the Main Menu select Survey, Start Survey, Skip Workflow      Enter unique survey reference Enter substation name & type Enter switchgear information    Take background readings Align the centre button with the NFC tag The  UltraTEV  Plus²  will  beep once  to  indicate  a  tag  has been  detected,  followed  by
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 40 of 82 two  beeps  to  indicate  a successful tag write.  Following a successful tag write, the UltraTEV Plus² will continue in Survey mode. 6.4 Reading a Substation Tag Substation tag reads can take place in the Job, Substation and Switchgear screens within Survey mode. From the Main Menu select Survey, Start Survey, Skip Workflow.  Align the  centre button with the NFC tag and press the centre button or NFC icon to trigger a scan.  The UltraTEV Plus² will beep once to indicate a tag has been detected, followed by another beep to indicate a successful tag read.         Successful scan Substation information added to survey  6.5 Asset Tag We suggest two NFC tags per panel, one on the front and one on the rear.  The asset tag will store the following information required in the Metadata screen of Survey mode. Asset Name    (up to 127 characters) Panel Number  (up to 127 characters)
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 41 of 82 6.6 Writing to an Asset Tag The recording data option is available in Survey, TEV and Ultrasonic mode.        On any screen press record Input asset information Select ‘yes’ and align the centre button with the NFC tag    The UltraTEV Plus² will beep once to indicate a tag has been detected, followed by two beeps to indicate a successful tag write.    Once completed, the asset information is available for re-call on future measurements.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 42 of 82 6.7 Reading an Asset Tag  Whenever the record option is used in Survey mode and the measurement ‘Metadata’ screen is displayed, a tag read is possible.       Press the centre button or NFC icon to trigger a scan The UltraTEV Plus² will beep once to indicate a tag has been detected, followed by another beep to indicate a successful tag read. Data will populate asset information   6.8 Reading an NFC Tag from the Main Menu NFC tags which have previously been written to, can be read or erased from the Main Menu.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 43 of 82 6.9 NFC Tag Trouble Shooting  ‘blank tag detected, no data read’   The tag has no data ‘wrong tag type’  Attempting to read substation data from an asset tag ‘no tag detected’ Re-position the UTP2 in contact with the NFC tag and try again.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 44 of 82 7. Survey The Survey mode of the UltraTEV Plus² is a powerful yet easy way to collect and store data from a range of assets. Data from TEV, Cable PD or Ultrasonic measurement modes can be recorded  and  stored  with  corresponding  metadata  linking  the  data  and  its  associated context.  All data recorded on the UltraTEV Plus² takes the form of a survey in order to give the data context and a common structure for use when analysing the data offline. 7.1 Create a Workflow using the Workflow Generator Workflows are a pre-populated description of the measurements to be undertaken as part of a substation survey. A workflow consists of information regarding the assets and the specific measurements per asset that are to be performed. Insert the UltraTEV Plus² SD card into your PC or laptop and open the Workflow Generator with Micorsoft Excel.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 45 of 82 1. Enter substation information  Substation name cannot contain any special symbols *%^$#@!’ etc.  Pre-defined fields for Manufacturer and Type, or customise to suit by selecting ‘Other:’.  We  recommend  selecting  ‘Yes’  in Conditions/Job  fields.  ‘Yes’  will  request that  they  are  measured/entered  during PD survey.   2. Enter Panel Names and Numbers  Maximum of 63 panels.  We recommend panel number 1 through to required number in sequential order.  Panel names must be unique and are case sensitive.         3. TEV, Ultrasonic or Cable PD Locations  Pre-determined locations for TEV, Ultrasonic or Cable PD can be designed into the substation layout.  This information is reviewed using the ‘View Progress’ screen within the UltraTEV Plus².  4a.  Save Excel Substation File Save the Excel Substation File for later use.  This allows for any changes to be made to Substation details or layout in the future The name of the Excel file will be ‘substation-name.xlsm’.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 46 of 82 4b.   Save Workflow to PC Save the workflow file so that it can be used in the  UltraTEV  Plus²  Instrument  during  a  PD survey.  The file will be saved as substation-name.json.    4b.   Save Workflow to SD card Save  the  workflow  file  or  substation-name.json  file  under  the  folder ‘workflows’ in the UltraTEV Plus² units microSD card.  If this folder does not exist, it must be created (case sensitive).      7.2 Starting a Survey There are two ways to start a survey; either by going through the Survey display off the Main menu, or by starting a data capture from any measurement screen.            Pressing the Survey icon   on the Main menu will display the Survey Mode display. This display allows users to start, stop and view the progress of a survey. To start a survey, press ‘Start Survey’ on the display. Doing this will show two options to select from; Select Workflow or Skip Workflow.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 47 of 82 7.3 Select Workflow   Recall workflow from substation tag Read tag    Go to workflow list Select workflow
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 48 of 82 Enter your unique job number, the substation and switchgear information will be filled in using the information from the Workflow.     Capture background readings, if  ‘yes’ was not selected when the workflow was created, this data will not be captured.   A workflow can be created from a previous survey using the ‘Generate Workflow’ option in the UltraTEV Plus² interface page.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 49 of 82 7.4 Skip Workflow To perform a survey without a workflow, press the “Skip Workflow” button. Similarly to the Workflow  route,  a  series  of  forms  will  be  displayed  with  fields  about  the  substation, switchgear  and  conditions.  The  form  field  can  be  populated  using  the  inbuilt  virtual keyboard or a drop down list of available options.     7.5 Ad-hoc Measurement If a survey is not in progress when the record button is pressed in any of the TEV, Cable PD or Ultrasonic measurement screens the data is still captured. On completion of the record, the default  survey  information fields are  displayed to  capture the measurement  context data. This data is the same as entered when starting a survey through the menu icon. Once this information has been entered, survey mode stays active ready for further data to be recorded and added to the survey. 7.6 Survey Metadata Forms As mentioned in the previous section, each survey requires the input of information about the substation the survey is being conducted in. Some fields have populated lists of values to select from, with each having the option to override by inputting a custom value, others allow only virtual keyboard input and a select few have special behaviours. Navigation through the forms is done using the left and right buttons on the menu bar or using the corresponding physical buttons. The last form to be populated is indicated by the right hand button on the menu bar changing to become a tick icon. Pressing this will close the last form, save the entered information and return to the home menu ready to start recording data. If a workflow is not being used, the default form fields used are set out below along with their behaviour:  Form 1   Name Job   Field Description Behaviour Job Number The  job  number  of  the  survey,  used  by many users to link a survey to a contract or package of work Pressing  the  input  field  will  show the virtual keyboard   The  Notification  bar  changes  from  blue  to  green  to  indicate  a  survey  is currently running.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 50 of 82  Form 2   Name Substation   Field Description Behaviour Name Name of the substation being surveyed Pressing  the  input  field  will  show the virtual keyboard Type Type of the substation being surveyed Pressing the input field will show a populated  list  of  substation  types, with  the  option  to  enter  a  custom value using the virtual keyboard   Form 3   Name Switchgear   Field Description Behaviour Manufacturer Manufacturer  name  of  the  switchgear being surveyed Pressing the input field will show a populated  list  of  switchgear manufacturers,  with  the  option  to enter  a  custom  value  using  the virtual keyboard Type The type of switchgear being surveyed Pressing the input field will show a populated  list  of  switchgear  types with  the  option  to  enter  a  custom value using the virtual keyboard Installation Date Installation date of the switchgear Pressing the input field will show a date  selector  to  input  the switchgear installation date Rated Voltage The rated voltage of the switchgear Pressing the input field will show a populated  list  of  voltages  with  the option  to  enter  a  custom  value using the virtual keyboard Operating Voltage The operating voltage of the switchgear Pressing the input field will show a populated  list  of  voltages  with  the option  to  enter  a  custom  value using the virtual keyboard Busbar Insulation The  insulation  material  of  the switchgear's busbar Pressing the input field will show a populated  list  of  busbar  insulation materials with the option to enter a custom  value  using  the  virtual keyboard
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 51 of 82  Form 4   Name Conditions   Field Description Behaviour Background Metal Background metalwork TEV value Pressing the input field will cause a background  TEV  measurement  to be performed Background Air Background Air TEV value Pressing the input field will cause a background  TEV  measurement  to be performed Temperature Temperature  as  read  by  the Environmental Sensor Pressing the input field will cause it to  be  populated  with  the  current Temperature.  The  Temperature  & Humidity sensor must be connected to do this. Humidity Humidity  as  read  by  the  Environmental Sensor Pressing the input field will cause it to  be  populated  with  the  current Humidity.  The  Temperature  & Humidity sensor must be connected to do this.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 52 of 82 7.7 Using Populated Lists Populated lists used in many of the above fields will look like that of below.  The list can be scrolled by dragging the list up and down using a finger or stylus. Selecting an item is done by pressing an item then pressing the tick in the menu bar. If the “Other…” option is selected a virtual keyboard prompt will be displayed for custom input. If the cross in the menu bar is pressed, the list will be closed and no input recorded. 7.8 Using the virtual keyboard The virtual keyboard allows custom text to be input. Characters can be input using the buttons on the layout, with additional characters and numbers available through the “123” button. Uppercase letters can be entered by pressing the arrow (between A and Z). Double tapping the 0arrow will activate Caps lock, giving uppercase letters until it is next pressed.  To accept the input text as input to the field, press the tick button on the menu bar, to cancel, press the cross on the menu bar of the Left button.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 53 of 82 7.9 Background Measurements The  background  measurements  fields  on  the  survey  metadata  forms  have  special behaviour, pressing the input field triggers the UltraTEV Plus² to start measuring the TEV level for a ten second period. Following this, the average measurement for the period is stored. When performing the Background Metal measurement, the TEV plate of the UltraTEV Plus²  should  be  held  against  an  unearthed  piece  of  metalwork  in  the  substation  not connected  to  the  switchgear.  The  Background  Air  measurement  requires  holding  the instrument in free space in order to get an ambient reading. The background temperature and humidity is taken directly from the current measurement by the  Environmental  Sensor.  Please note that the sensor needs to be connected to the UltraTEV Plus² device.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 54 of 82 7.10 Recording Data Once a survey has been started, data can be recorded from any TEV, Cable PD or Ultrasonic displays. The same data is recorded for TEV or Cable PD independent of which TEV/Cable PD screen is currently displayed. To record data, simply press the record icon visible on the menu bar, which will then start a 10 second period of data capture.   Different data is recorded for the different measurement modes as summarised below: 7.10.1 TEV recorded data When recording data in any of the TEV modes, the following data is recorded and stored: • Event data including phase angle, cycle count, amplitude, pulse width and rise time • TEV Waveforms • TEV audio 7.10.2 Cable PD recorded data When recording data  in  any of the  Cable PD modes, the following data is recorded and stored: • Event data including integral, pulse width and rise time • Cable PD Waveforms 7.10.3 Ultrasonic recorded data When recording data in Ultrasonic measurement modes, the following data is recorded and stored: • Raw Ultrasonic audio • Heterodyned Ultrasonic audio • Processed Ultrasonic audio
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 55 of 82 7.11 Viewing Survey Progress The progress of a survey can be viewed at by navigating to the Survey menu then pressing ‘View Progress’. The view progress display shows a top view of a switchgear panel with the different components making up a panel separated out. Each component shows the total number of measurements taken on that component against the number of expected measurements.  The  expected  measurements  are  only  applicable  to  surveys  which  are following a workflow, which sets out the measurements that should be taken as part of that survey. Using the left and right buttons on the menu bar, other panels within the survey’s progress can be viewed.  Pressing any component on the panel view will display details of the measurements on that component, including the measurement location, sub-location and average measurement values.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 56 of 82 7.12 Adding Media to a Survey A photograph or video can be added to the survey file by connecting your smart device to the UltraTEV Plus², via the Hotspot function,  To add an image or video, open the UltraTEV Plus² interface by entering 192.168.10.1 to your web browser and select ‘add image/video’.    7.13 Completing a Survey A survey can be completed at any time by going to the Survey Menu and pressing the “Stop Survey” button. Upon completing a survey, a summary of the survey is written to the survey directory  and  the  entire  directory  is  archived  into  a  zip  file  for  safe  keeping.  If  a  large amount  of  data  has  been  recorded,  archiving  the  data  can  take  up  to  a  minute.  Once archiving is completed the notification bar will return to its blue colour indicating that a survey is now no longer in progress.     Create a shortcut on your mobile device’s homepage for quick access to the UltraTEVPlus² interface
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 57 of 82 8. Reviewing Results  • Data  collected  during  Survey  mode  or  though  ad-hoc  recording  is  stored  on  the UltraTEV Plus²’s MicroSD card. To facilitate viewing of the data the UltraTEV Plus² provides four methods of connection. • Hotspot  –  Allows  direct  connection  via  the  UltraTEV²  personal  hotspot  to  a  Wi-Fi enabled device • Wi-Fi – Allows a direct connection from the UltraTEV Plus² to a Wi-Fi enabled device.  • USB – Direct connection from the UltraTEV Plus² to a Windows based machine.  Removal of the MicroSD card for viewing on a Windows/Linux/ Mac OS X based machine.  8.1 Hotspot Connection Go to Main Menu, Settings, Wireless Settings and enable Hotspot.  Go to Wi-Fi settings on your Wi-Fi device, select the SSID and enter the Passphrase.     Once  connected,  enter  the  IP  address  192.168.10.1  in  a  web  browser  such  as  Google Chrome, Mozilla Firefox or Microsoft Edge/Internet Explorer.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 58 of 82 8.2 Wi-Fi Connection Go to Main Menu, Settings, Wireless Settings and enable Wi-Fi.  Select Network Connect, choose your network from the list and connect.  Once connected, go to Network Status and make a note of the  IP  address.    Enter this IP address in  a  web  browser  such  as  Google Chrome, Mozilla Firefox or Microsoft Edge/Internet Explorer. The home page, shown below displays a list of all surveys and screenshots stored on the UltraTEV Plus²’s MicroSD Card.   8.3 USB Connection (Windows PC only) Connect the UltraTEV Plus² via the USB port using the supplied cable.  The UltraTEV Plus² should install as an Ethernet Gadget. If the drivers do not install automatically, you can install them as follows: Go to device manager and select the instrument from the network adaptors list, it will have a yellow triangle by it, then right click this and update driver software: • Browse my computer for driver • Let me pick from list of drivers on my computer • Network adaptors • Microsoft Corporation • Remote NDIS based internet sharing device, next install Note: The user needs to have administrator rights for the computer. The index of surveys on the UltraTEV Plus² can be used to quickly identify the site of interest allowing  the  user  to  navigate  either  directly  to  the  data  analysis  (view  button)  or  to download a zip file (compressed folder) containing the raw data (download button).  Clicking the view button takes the user to the data analysis screens detailed overleaf.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 59 of 82 8.4 MicroSD Card & Data Zip Files An alternative method of viewing the data held on the UltraTEV Plus² is by direct file access. This can either be from a previously  downloaded data zip as above or by accessing the MicroSD card directly.  To directly access the MicroSD card ensure the UltraTEV Plus² is powered down, then locate the MicroSD card at the base of the instrument and gently push on the card to eject it.  The MicroSD card will contain a separate .zip file (compressed folder) for each survey and ad-hoc  measurement  undertaken.  Inside  each  folder  there  is  an  html  page  named ‘index.html’. Extracting the zip file and then opening the ‘index.html’ file inside this folder will direct you to the analysis pages.   8.5 Data Analysis Screens The UltraTEV Plus2 has a web interface for analysing data captured by the instrument. These analysis pages can be accessed through a web browser or downloaded for offline analysis as detailed above. Following selection of ‘View’ on the landing page, or opening of an ‘index.html’ file from the decompressed zip folder, a new page will appear with a visualisation of the switchgear surveyed.  The  overview  or  ‘index’  page  provides  diagrammatic  representation  of  the  switchgear surveyed  along  with  an  icon  detailing  each  measurement.  An  overview  of the  metadata entered during the substation visit is included on the left hand side of the page. This data
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 60 of 82 includes  substation  information  such  as  site  name  and  switchgear  information  such  as manufacturer,  voltage  etc.  Below  the  metadata  on  the  left  hand  side  of  the  page  a ‘download  survey  summary’  button  is  available. When  pressed this  button  downloads  a Comma Separated Variable (CSV) file containing an overview of the survey results.  The  measurement  icons  shown  below  are  positioned  on  the  panels  as  per  the  location entered  during  the  site  survey.  Clicking  any  of  the  available  measurements  on  a  panel component  will  open  the  analysis  page  for  the  corresponding  measurement.  The measurement section is colour coded, to correspond with the green/amber/red thresholds. - TEV - Cable PD    - Ultrasonic 8.5.1 TEV & Cable PD Analysis Screen Both TEV and Cable PD recorded data share the same suite of analysis screens. Once a TEV or Cable PD measurement has been selected from the index page a new tab will open in the  browser  displaying  the  analysis  page  corresponding  to  the  measurement  selected. Multiple  individual  analysis  pages  can  be  opened  simultaneously  in  this  way  to  aid comparison.  The  TEV  and  Cable  PD  analysis  pages  both  have  metadata  regarding  the  current measurement on the left side of the page, with another button beneath to download the raw  dataset  for  each  graph  to  CSV.  The  chart  displayed  on  each  page  can  be  changed between Waveform, Histogram and Phase Resolved by clicking the tabs in the upper right hand corner.  Both Phase Resolved and Waveform graphs are able to be zoomed by clicking and dragging on the graph area; the original zoom level can be returned to by clicking the respective graphing tab in the upper right hand corner. Hovering the mouse over a point/bar on each respective graph will produce a tooltip with information regarding that event. On the Phase Resolved graph a legend can be seen on the upper right of the graph area, indicating the scaling of colours for each point.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 61 of 82  When the Waveforms tab is opened, a new control will appear beneath the metadata on the left.  The  ‘Waveform Control’  section allows  navigation through the  waveforms  collected using the  up/down arrows next to the waveform number.  The  ‘Show  All’ button  can be used to show all waveforms on the same graph.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 62 of 82 8.5.2 Ultrasonic Analysis Once an ‘Ultrasonic’ measurement has been selected on the index page, a  new  tab  will open in the browser with the analysis page corresponding to the measurement selected. The metadata section will be displayed to the left side of the page, and the ‘Play’ button aligned with the ‘Heterodyned Ultrasonic’ label can be used to listen to or download the .wav file (browser dependent). If the browser does open the file and begin to play it, right click the player and select ‘Save file as’ to save the file.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 63 of 82 9. Detecting Partial Discharge using the UltraTEV Plus² Due to the tri-sensor capability, the UltraTEV Plus² is able to detect Partial Discharge activity on the surface of insulation using Ultrasonic detection, internal to insulation by measuring TEV signals and in cables and cable accessories using the RFCT accessory.  This  section  covers how  to  use  the  UltraTEV  Plus² to  detect  PD activity  using  the three sensor technologies. 9.1 TEV Measurement TEV measurements are performed using the TEV sensor embedded into the front face of the instrument.    9.1.1 Background Noise Electromagnetic signals from sources outside the switchgear can also produce voltages on the outside of the switchgear.  These electromagnetic sources can come from a multitude of sources such as overhead line insulators, transformer bushings and strong radio signals.  These  sources  will  produce  equivalent  signals  on  metalwork  which  is  not  electrically connected to the switchgear such as  metal substation doors or  fencing.  Measuring the interference levels on these surfaces before taking readings from the switchgear will help allow identification of PD over background noise.       TEV measurements cannot be taken with the RFCT accessory connected to the instrument   If the  background noise  is  less than  10dB then  the  UltraTEV Plus²  pulse counter is not incremented and will read zero
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 64 of 82 9.1.2 Measuring TEV Switch on the UltraTEV Plus² and wait until home menu is displayed. Press the TEV icon on the home menu then choose which TEV display is required. The ‘Interpretation’ display is recommended  for  first  pass  with  the  advanced  functionality  of  the  other  modes  being utilised to further inform the user once a signal is detected.  To take a measurement, hold the TEV sensor squarely against the metalwork of the asset under  test  as  shown  overleaf.  Any  readings  will  be  displayed  on  the  screen  with  the interpretation message adjusted to take account of the reading’s amplitude and pulses per cycle. Please note that the readings will not remain on the screen once the TEV sensor has been removed from the metalwork.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 65 of 82 9.2 Cable PD Measurement To perform  Cable  PD  measurements, the  RFCT  accessory needs to  be  connected to  the UltraTEV Plus².  The RFCT connects to the Smart accessory port found on the left hand side of the instrument.    9.2.1 Practical RFCT Connection Requirements Using the RFCT for online PD tests on medium voltage power cables requires direct access to the earth bonding strap. If present the split core radio frequency current transformer RFCT  can  simply  be  clamped  around  the  earth  cable.  This  method  can  be  used  on-line without disconnecting cables or switching off supplies to customers.   With XLPE cable installations the user can normally get access to the cable earth strap or the core of the cables. The earth strap can be looped out of the termination box to give better access. With PILC (Paper Insulated Lead Covered) cables difficulty may arise attaching the RFCT as the cable earth and switchgear earth can be bonded together. This is more usual on older PILC cables using compound filled cable boxes.  9.2.2 Measuring PD in cables Switch on the UltraTEV Plus² and wait until home menu is displayed. If the conditions set out above are met, install the RFCT around the earth strap of the cable under test.  Proceed to connect the fitted RFCT to the UltraTEV Plus² using the supplied cable; connect the BNC to the RFCT and the LEMO™ connector into the Smart accessory port. The home menu on the UltraTEV Plus² will now display a Cable PD icon in place of the usual TEV icon.    EA Technology RFCTs are designed to be installed by suitably competent operators on cable earth/ground straps which are suitably and efficiently connected to earth/ground to maintain safety.   RFCTs,  connecting  leads  and  test  equipment  do  not  provide  protection against high voltage.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 66 of 82   RFCTs,  connecting  leads  and  test  equipment  do  not  provide  protection against high voltage. Ensure that the accessory is only connected to cables at earth potential.  Press the Cable PD icon on the home menu and proceed to press on the Measure option. The screen will display a bar graph of the measured PD values in picocoulombs (pC). To obtain a further insight into the discharge activity on a cable, select the ‘Phase Plot’ option on the Cable PD screen. This screen provides a phase resolved reading of Cable PD activity within the cable under test.  The cable type can be changed by pressing the text ‘paper’ or ‘polymeric’.  The UltraTEV Plus² green/amber/red thresholds will change according to which cable insulation type has been selected.            9.3 Ultrasonic Measurement The UltraTEV Plus² is equipped with a built-in ultrasonic sensor which can be used to detect the acoustic emissions of surface partial discharge activity. External ultrasonic sensors are also available to use with the UltraTEV Plus² allowing use in outdoor compounds, on sealed assets  or  in  hard  to  reach  places.  When  taking  airborne  ultrasonic  readings  the  sensor should not touch the asset or plant being investigated. 9.3.1 Measuring Ultrasonic Switch on the UltraTEV Plus² and wait until home menu is displayed. Proceed to plug in the supplied Headphones; select the Ultrasonic icon on the main menu. The screen will now display a phase resolved plot of ultrasonic activity.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 67 of 82 Ultrasonic activity above the background level may be significant. Genuine discharge can be identified by a crackling sound (like a sizzling frying pan) in the headphones or by phase related groups on phase plot. Further confidence of a detection can be obtained by the classification algorithm output displayed on the top left of the screen.  9.3.2 Measuring Ultrasonic with the UltraDish The UltraDish provides a means of detecting discharge sources at a distance. It comprises a transparent parabolic reflector that focuses the ultrasonic sound on to a sensor mounted at  the  focus  point  of  the  reflector.    The  UltraDish  gives  an  effective  increase  in  gain compared  to  the  built  in  sensor  allowing  discharges  to  be  detected  at  much  greater distances such as insulator strings on overhead assets.   To use an UltraDish the connector must be plugged in to the Ultrasonic sensor input on the side of the UltraTEV Plus².  The UltraDish is aimed at the point of interest with either the optical sight or by switching on the laser pointer with the button on the handle.     The UltraTEV Plus² defaults to the built-in ultrasonic sensor if no accessory is plugged into the Ultrasonic Accessory port  Due to the gain of the UltraDish, readings taken with the UltraDish cannot be compared to readings taken with the Internal Sensor, the Flexible Sensor or the Contact Probe.  This accessory is available with the Kit 3 package. To discuss procuring this accessory please contact the product support team via email:   product-support@eatechnology.com
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 68 of 82 9.3.3 Measuring Ultrasonic using the Flexible Sensor The Flexible Sensor provides a means of reaching inaccessible parts on the switchgear. The sensor is mounted at the end of a flexible goose-neck which allows the angle of the sensor to the handle to be adjusted.  This allows the user to make measurements where it would be difficult to use the built in sensor and still be able to read the display. To use a Flexible Sensor the connector must be plugged into the external sensor input on the Ultrasonic  Accessory  port  of the  UltraTEV Plus².    To  avoid damage to the  socket  or connector ensure that the red dots are lined up before attempting to plug in the Flexible Sensor.  The Flexible Sensor is used in the same manner as the Internal Sensor.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 69 of 82 9.3.4 Ultrasonic Measurement using the Contact Probe Accessory The Ultrasonic Contact Probe is provided to enable discharges to be detected in enclosed areas where there is no direct air path from the discharge source to the sensor. The Probe connects to the external sensor connector and is clamped on to the area of interest using the magnets surrounding the sensor plate.  To avoid damage to the socket or connector ensure that the red dots are lined up before attempting to plug in the Ultrasonic Contact Probe.  The probe will detect discharge sources inside the enclosed area by detecting the energy transmitted to the enclosure.  Care must be taken to eliminate other sources that could cause the signals from discharges to be masked, e.g. accidental movement of the probe itself or strong vibration on the panel.
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 70 of 82 9.3.5 Using the Ultrasonic Contact Probe The Ultrasonic Contact Probe should be used if there is not a direct path between the PD source and instrument sensor as shown in the second image below.  However, it must not be  used  if  the  tank  containing  the  expected  PD  source  is  separated  with  another  layer (shown in the third image).  In cases where there is a direct air path between the source of PD and the  instrument,  an  airborne  sensor should  be  used  as  shown  in the  first  image below.  Due to the physics of ultrasound, in most cases using an airborne sensor may offer better sensitivity than that obtained using the Ultrasonic Contact Probe.   1)  Ultrasonic  signal  can  propagate  through the  air  path.    The  Ultrasonic  Contact Probe  can  be  used;  however,  better  results  may  be  obtained  using  the  airborne sensor. 2) No available air gaps - using an Ultrasonic Contact Probe is the best practice. 3) There is no access to the tank containing PD source, neither the airborne sensor nor the Ultrasonic Contact Probe will provide a valid reading.    CP Surface PD CP Surface PD CP Surface PD 1 2 3  Contact   Sensor Head (stainless steel) Aluminium Body Cable Socket Asset surface or measurement point  (Where the Ultrasonic Contact Probe is attached)
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 71 of 82 9.3.6 Detection, Measurement and Localisation of the Partial Discharge Detection of the Partial Discharge using the Ultrasonic Contact Probe is based on the PD pattern recognition carried out by operators.  The audio signature of a Partial Discharge detected by the Contact Probe is similar to those obtained using airborne sensors.  Special care has to be taken to distinguish phantom signals from genuine signals caused by surface PD. Due to the differing propagation paths of the ultrasonic signals, measurements carried out using the Ultrasonic Contact Probe cannot be compared against measurements carried out using airborne sensors.  In general signals detected by the Contact Probe are smaller as a result of the physical properties of the asset and propagation path.  Comparisons between two  measurements  should  only  be  made  on  assets  of  the  same  type  using  the  same configuration of the Contact Probe. 9.3.7 Mounting Practices The Ultrasonic Contact Probe was designed to provide sufficient sensitivity to allow it to be used to detect low level ultrasonic sources.   The  image  below  shows  scenarios  where  the  Ultrasonic  Contact  Probe  is  mounted ineffectively to the asset enclosure. Any air gap between Sensor Head and measurement point will effectively attenuate signals to a level where even strong discharges will not be detected.  Therefore before any permanent or temporary installation, the Sensor Head and asset surface need to be cleaned of any loose or unstable material.  If the assets surface is very rough and uneven this will create air gaps which will result in poor contact between the Sensor Head and the asset.  1) Dust ingress between Ultrasonic Contact Probe Sensor Head and the asset surface 2) A rough or uneven surface will drastically decrease the amount of signal being transferred to the Sensor Head The images below show the correct way of mounting the Ultrasonic Contact Probe to the asset in order to take a valid measurement.  Ideally the Ultrasonic Contact Probe will be attached  to  a  relatively  flat  surface  using  its  magnetic  clamp.  This  will  eliminate  any phantom noises which are described in the section below. The second image shows a case where the surface is very rough and uneven.  One of the following couplants may be used:- • Water based – suitable for quick measurement offers very good coupling. • Oil based – suitable for long term monitoring as the oil will not evaporate quickly.  Contact   Contact  1a 2
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 72 of 82 • Solid state – suitable for long term monitoring but does not offer as good coupling as oil based. • Use of existing stickers on the switchgear such as ‘danger’ notices  The last image shows the application of pressure to the Ultrasonic Contact Probe against the  asset  under  investigation.    This  can  improve  the  signal  transfer  and  increases  its detection abilities.  Please note,  when the instrument  dB  values are read for comparison purposes, always use the same type of the sensor, in the same position as previously used. The asset measuring point can be marked on the plant item to facilitate easy location in future.   1) Relatively flat and smooth surface 2) Using suitable couplant in the case of a rough surface 3)  Carefully  pressing  the  Ultrasonic  Contact  Probe  towards  the  asset  to  increase coupling may eliminate the need to use a couplant    Contact   Contact  1 2  Contact  3
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 73 of 82 9.3.8 Sources of Noise and Phantom Signals The following images present some examples of how unwanted signals may be introduced during the PD detection process when using the Ultrasonic Contact Probe. These can be categorised as sources of noise and sources of phantom PD signals. The difference between the two is that noise decreases our detection capabilities by masking the PD signal, whereas phantom signals may be confused as a PD source. The first image shows that when the UCP is kept in the hand during measurements, even tiny  movements  of  the  hand  can  introduce  significant  noise  to  measurements  through surface noise.  In cases where it is necessary to hold the Ultrasonic Contact Probe during measurements  (e.g.  pushing  the  sensor  to  obtain  more  signal  or  non-magnetic  asset enclosure),  a coupling fluid may help to reduce this type of noise. Any vibrations of the asset surface caused for example by rain in outdoor assets or vibration of transformers may cause phantom signals. In such cases the audible signal may be appear exactly the same as a genuine PD source.  These two examples are illustrated in the second and third images.  1) Shaking Ultrasonic Contact Probe, e.g. when held in the hand 2) Rain in outdoor assets 3) Vibration (including transformers) of asset enclosure where the Ultrasonic Contact Probe is attached   Contact   Contact  1 2  Contact  3
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 74 of 82 10. UltraTEV Plus² Specification TEV Measurements Sensor:        Capacitive Measurement Range:    0 – 60 dBmV Measurement Bandwidth:   3 – 80 MHz Resolution:  1dB Accuracy:  ±1dB Max Number of Pulses/Cycle:  1953 at 50Hz or 1627 at 60Hz Min Level for Pulse Count:  10 dBmV  Ultrasonic Measurements Sensor:        Ultrasonic Microphone Measurement Range:    -7dBµV to 68 dBµV Resolution:        1dB Accuracy:        ±1dB Transducer Sensitivity:    -65dB (0dB = 1volt/µbar RMS SPL) Transducer Centre Frequency:  40 kHz Transducer Diameter:    16mm  Cable PD Measurements Sensor:        Radio Frequency Current Transformer Measurement Range:    100 – 100 000 pC Measurement Bandwidth:   41 MHz
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 75 of 82 Hardware Enclosure:        Self-coloured vacuum formed plastic case Screen:        3.5” TFT Touchscreen           LED Backlight           640 x 480 Resolution Indicators:        Charging indicator LED Controls:        4 x Push-Buttons Connectors:        Micro USB connection port           MicroSD Slot           2 x Accessory connection ports     Headphones:      3.5mm jack; Min.  8 ohms Wireless Communication:   NFC & Wi-Fi  Environmental Operating Temperature:    -20 - 50 °C Humidity:        0 - 90 % RH non-condensing IP Rating:        54  Dimensions Size:          201mm x 76mm x 34mm Weight:        0.44kg  Power Supplies Internal Batteries:      3.7V, 6.6Ah rechargeable Lithium-Ion Typical Operating Time:    Approx.  8 hours Battery Conservation:  Automatic  shutdown  after  5  minutes  of  inactivity (configurable) Charging Time:  Approx. 6 hours
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 76 of 82 Battery Charger Rated Voltage:      100 – 240 AC Frequency:        50 - 60Hz Charger Output Current:    2 A Battery Charging Current:  1.8A @ 5V nominal Dimensions:       61.89mm x 39mm x 32.3mm  Weight:        65g (approx.) Operating Temperature:    0 - 40°C Operating Humidity:    20% – 85% Storage Humidity:      5% – 95%
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 77 of 82 11. Declaration of Conformity Manufacturers Name:  EA Technology Ltd Manufacturers Address:  Capenhurst Technology Park         Capenhurst         Chester         CH1 6ES UK  Type of Equipment:   UltraTEV Plus² Model Number:    UTP2  I hereby  declare that the equipment specified  above  is tested to and conforms with the essential radio test suites included in the following standards:  Standard Issue Date ETSI EN 300 328-2 V1.8.1 April 2012 ETSI EN 302 291-1 V.1.1.1 July 2005  and  therefore  complies  with  the  essential  requirements  and  provisions  of  the  R&TTE directive 1995/5/EC of the European Parliament and of the council of 9th March 1999 on radio equipment and Telecommunications Terminal Equipment and the mutual recognition of their conformity and the requirements of Annex III (conformity assessment procedure referred to in article 10(4)).    Robert Davis Chief Executive Officer EA Technology Ltd
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 78 of 82 12. Maintenance No attempt should be made to gain access to the internal circuitry of the UltraTEV Plus², or its  accessories.  Advice should  be  sought  from the  manufacturer, or the  supplier,  if  any doubt exists over the equipment's performance or operation. Avoid  storage  in  damp  and  humid  conditions  and  do  not  subject  it  to  temperature extremes, excessive vibration or shocks. Do not stand on the case of the UltraTEV Plus². 13. Warranty Policy What Does the Warranty Policy Cover? EA  Technology  products  and  accessories  are  warranted  against  defects  in  material  and workmanship for twelve months from the date of despatch from our premises. During  the  warranty  period,  EA  Technology  will,  at  its  option,  either  repair  or  replace products, parts or accessories which prove defective.  What is Not Covered by the Warranty Policy? The  following  are  not  covered:  damage  caused  by  accident,  misuse,  abuse,  product modification or neglect; damage resulting from failure to follow instructions contained in your operating manual; damage resulting from the performance of repairs by someone not authorised by EA Technology.  Warranty Policy for Repairs  Repaired products are warranted against defects in workmanship and materials for a period of six months, or the remainder of the original warranty period, whichever is greater.   product-support@eatechnology.com  +44 (0)151 347 2293
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 79 of 82 14. Calibration Calibration interval: 12 months The calibration date and due date  can be viewed through the About screen.  A  warning message will be displayed on start up, when the UltraTEV Plus² is past the calibration due date. Your application may require a different calibration interval dependant on the frequency of use.   15. Repair  For information on repairs  product-support@eatechnology.com 16. Waste Electrical and Electronic Equipment Directive (WEEE) EA Technology is a member of an approved compliance scheme as defined by the WEEE directive.   When an EA Technology product reaches the end of its operational life, it must be recycled by a licensed waste management operator or returned to EA Technology for recycling. 17. Continuous Improvement EA  Technology  has  a  policy  of  continual  product  development  and  enhancement.  Consequently, there  may be  minor  variations in specifications or operation that are not covered in this operating manual. Every  effort  has  been  made  to  ensure  that  the  information  provided  in  this  operating manual is accurate at the time of going to print. If any errors or omissions are noticed, please notify  product-support@eatechnology.com
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 80 of 82 18. Contact Us Head Office  EA Technology Ltd Capenhurst Technology Park Chester, UK, CH1 6ES Tel: +44 (0)151 339 4181  For details of our international offices and distributors, please visit our website: www.eatechnology.com/contact-us/corporate-offices    Sales Email: sales@eatechnology.com  Freephone: 0800 027 7243 (UK only)   Product Support Email: product-support@eatechnology.com  Freephone: 0800 032 6657 (UK only) Tel: +44 (0)151 347 2293
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 81 of 82 19. Record of Changes Date Version Author(s) 15th April 2016 2388L011 Gareth Devine 20th April 2016 2388L012 Gareth Devine 27th May 2016 2388L013 Gareth Devine 25th August 2016 2388L014 Gareth Devine, Sion Hughes 07th October 2016 2388L015 Gareth Devine 14th November 2016 2388L016 Gareth Devine 19th July 2017 2388L017 Jo Cahill, Stuart Aird March 2018 2388L018 Jo Cahill, Stuart Aird
EA Technology UltraTEV Plus2 Operating Manual    2388L018   Page 82 of 82                       All rights reserved.   No part of this publication may be reproduced or transmitted in any form or by any means electronic,  mechanical, photocopied, recorded  or  otherwise, or stored in any  retrieval system of any  nature without the written permission of the copyright holder. © EA Technology Ltd 2017 EA Technology Limited, Capenhurst Technology Park, Capenhurst, Chester, CH1 6ES, UK Tel: +44 (0)151 339 4181 Fax: +44 (0)151 347 2404 http://www.eatechnology.com Registered in England number 256631
 www.eatechnology.com Australia | China | Singapore | UAE | Europe | USA Main reception: +44(0) 151 339 4181 EA Technology, Capenhurst Technology Park, Capenhurst, Chester, CH1 6ES, United Kingdom  Global Footprint We provide products, services and support  for customers in  90 countries, through  our offices in Australia, China, Europe, Singapore, UAE and USA, together with more than 40 distribution partners.  Our Expertise We provide world-leading asset management solutions for power plant and networks. Our  customers  include  electricity  generation,  transmission  and  distribution  companies,  together with major power plant operators in the private and public sectors.  Our products, services, management systems and knowledge enable customers to:  Prevent outages  Assess the condition of assets  Understand why assets fail  Optimise network operations  Make smarter investment decisions  Build smarter grids  Achieve the latest standards  Develop their power skills